Power Supply |
Voltage |
24 V AC/DC ± 20% |
|
|---|---|---|---|
|
Power consumption |
At 24 V DC |
At 24 V AC |
|
|
5 W |
7.5 VA |
||
|
RS485 Interface |
RS485 |
Up to 128 devices |
|
|
Communication protocols |
Modbus RTU, Modbus ASCII set by switch |
||
|
Baud rate |
From 2400 to 115200 set by switch |
||
|
Address |
0 to 99 set by switch |
||
|
M-Bus Interface |
M-Bus |
Up to 60 devices |
|
|
Baud rate |
From 300 to 38400 |
||
|
Ethernet |
1 Fast Ethernet |
IP Interface |
|
|
Baud rate |
10/100 Mb/s |
||
|
USB |
USB |
Mini USB 2.0 |
|
|
Ingress protection |
IP |
IP40 |
|
|
Temperature |
Storage |
-40°C to 85°C (-40°F to 185°F) |
|
|
Operating |
-10°C to 50°C (14°F to 122°F) |
||
|
Humidity |
Relative |
5% to 95% |
|
|
Connectors |
Type |
Removable |
|
|
Maximum cable size |
2.5 mm2 (18-12 AWG) |
||
|
Dimensions |
Width |
110 mm (4.331 in) |
|
|
Length |
37 mm (1.457 in) |
||
|
Height |
62 mm (2.441 in) |
||
Technical specification