Registered Access
|
Modbus |
Dec |
Hex |
Register Name |
Access |
Description |
|---|---|---|---|---|---|
|
30001 |
0 |
0x00 |
Version/Type |
Read |
Version and type of the device |
|
30002 |
1 |
0x01 |
Switches |
Read |
Switches state |
|
40003 |
2 |
0x02 |
Baud Rate |
Read/write |
RS485 baud rate |
|
40004 |
3 |
0x03 |
Stop Bits & Data Bits |
Read/write |
No. of stop bits & data bits |
|
40005 |
4 |
0x04 |
Parity |
Read/write |
Parity bit |
|
40006 |
5 |
0x05 |
Response Delay |
Read/write |
Response delay in ms |
|
40007 |
6 |
0x06 |
Modbus Mode |
Read/write |
Modbus Mode (ASCII or RTU) |
|
40009 |
8 |
0x08 |
Watchdog |
Read/write |
Watchdog |
|
40033 |
32 |
0x20 |
Received Packets LSR (Least Significant Register) |
Read/write |
No. of received packets |
|
40034 |
33 |
0x21 |
Received Packets MSR (Most Significant Register) |
Read/write |
|
|
40035 |
34 |
0x22 |
Incorrect Packets LSR |
Read/write |
No. of received packets with error |
|
40036 |
35 |
0x23 |
Incorrect Packets MSR |
Read/write |
|
|
40037 |
36 |
0x24 |
Sent Packets LSR |
Read/write |
No. of sent packets |
|
40038 |
37 |
0x25 |
Sent Packets MSR |
Read/write |
|
|
30051 |
50 |
0x32 |
Outputs |
Read |
Bit is set if value ≠ 0 |
|
40053 |
52 |
0x34 |
Analog output 1 |
Read/write |
Value of Analog Output:
|
|
40054 |
53 |
0x35 |
Analog Output 2 |
Read/write |
|
|
40055 |
54 |
0x36 |
Analog Output 3 |
Read/write |
|
|
40056 |
55 |
0x37 |
Analog Output 4 |
Read/write |
|
|
40057 |
56 |
0x38 |
Analog Output 5 |
Read/write |
|
|
40058 |
57 |
0x39 |
Analog Output 6 |
Read/write |
|
|
40059 |
58 |
0x3A |
Analog Output 7 |
Read/write |
|
|
40060 |
59 |
0x3B |
Analog Output 8 |
Read/write |
|
|
40061 |
60 |
0x3C |
Default Output 1 Value |
Read/write |
Default value of output set when power is on or when watchdog reset occurs |
|
40062 |
61 |
0x3D |
Default Output 2 Value |
Read/write |
|
|
40063 |
62 |
0x3E |
Default Output 3 Value |
Read/write |
|
|
40064 |
63 |
0x3F |
Default Output 4 Value |
Read/write |
|
|
40065 |
64 |
0x40 |
Default Output 5 Value |
Read/write |
|
|
40066 |
65 |
0x41 |
Default Output 6 Value |
Read/write |
|
|
40067 |
66 |
0x42 |
Default Output 7 Value |
Read/write |
|
|
40068 |
67 |
0x43 |
Default Output 8 Value |
Read/write |
|
|
40069 |
68 |
0x44 |
Output 1 Setting |
Read/write |
Setting of output mode:
|
|
40070 |
69 |
0x45 |
Output 2 Setting |
Read/write |
|
|
40071 |
70 |
0x46 |
Output 3 Setting |
Read/write |
|
|
40072 |
71 |
0x47 |
Output 4 Setting |
Read/write |
|
|
40073 |
72 |
0x48 |
Output 5 Setting |
Read/write |
|
|
40074 |
73 |
0x49 |
Output 6 Setting |
Read/write |
|
|
40075 |
74 |
0x4A |
Output 7 Setting |
Read/write |
|
|
40076 |
75 |
0x4B |
Output 8 Setting |
Read/write |
|
Registered access
Bit Access
|
Modbus Address |
Dec Address |
Hex
|
Register Name |
Access |
Description |
|---|---|---|---|---|---|
|
801 |
800 |
0x320 |
Output 1 |
Read |
If voltage or current is greater than 0 then according bit is set.
|
|
802 |
801 |
0x321 |
Output 2 |
Read |
|
|
803 |
802 |
0x322 |
Output 3 |
Read |
|
|
804 |
803 |
0x323 |
Output 4 |
Read |
|
|
805 |
804 |
0x324 |
Output 5 |
Read |
|
|
806 |
805 |
0x325 |
Output 6 |
Read |
|
|
807 |
806 |
0x326 |
Output 7 |
Read |
|
|
808 |
807 |
0x327 |
Output 8 |
Read |
Bit access