Power Supply |
DC |
20-34 V |
|---|---|---|
|
AC |
24 V ± 20% |
|
|
Power consumption |
0.5 W at 24 V DC, 0.75 VA at 24 V AC - up too 1 W peaks in max. configuration |
|
|
Built-in Sensors |
Temperature sensor |
10k NTC type, range: 0-50˚C, accuracy: ± 0.5˚C, resolution: ± 0.1˚C |
|
Humidity sensor (applies to versions with humidity sensor) |
Range: 0-100% RH, accuracy: ± 2% RH in range 10-90% RH, resolution: ± 0.1% RH |
|
|
CO2 sensor (applies to versions with CO2 sensor) |
Range: 400-4000 ppm, accuracy: ± 30 ppm |
|
|
COM1 |
RS485 interface |
Up to 128 devices |
|
Half-duplex |
||
|
Communication protocols |
Modbus RTU/ASCII, BACnet MS/TP |
|
|
Ports |
2 RJ45, screw connector |
|
|
Baud rate |
2400-115200 |
|
|
Front Panel |
Surface |
White/black glass |
|
Display (applies to version with display) |
TFT 0.96" |
|
|
Backlight (does not apply to the Touch Point Network Sensor series) |
3 intensity modes |
|
|
Buttons (does not apply to the Touch Point Network Sensor series) |
5 (Touch Point series) / 3 (Touch Point VAV series) |
|
|
LED (does not apply to the Touch Point Network Sensor series) |
3 blue and 3 red for temperature |
|
|
3 white for fan (only the Touch Point series) |
||
|
1 white for occupancy |
||
|
LED (all series) |
1 configurable RGB |
|
|
Ingress Protection |
IP rating |
IP20 for indoor installation |
|
Temperature |
Operating |
From 0°C to +40°C |
|
Storage |
From -40°C to +70°C |
|
|
Humidity |
Relative |
From 5% to 95% RH (without condensation) |
|
Screw Connector |
Type |
Removable screw terminals |
|
Maximum cable size |
1.5 mm2 (24…16 AWG) |
|
|
Housing |
Material |
Plastic, self-extinguishing ABS |
|
Mounting |
Standard 60 mm wall back box |
|
|
Dimensions |
Metric |
86.00x86.00x14.50 mm |
|
Inches |
3.39x3.39x0.57 in |
Technical specification