The RaiseLower component simplifies the control of 3-point valve actuators. This component has the following functions:
-
analog input, works with PID regulators;
-
2 digital outputs for 3-point direct control valve actuators;
-
analog output for 3-point control valve actuators by voltage level (additional device required);
-
midnight reset function to automatically adjust physical and virtual valve position.
The RaiseLower component has the following slots:
-
Function: the current function description (Lower_State, Static_State, Raise_State, Adjustment_Opening, Adjustment_Closing);
-
Virtual Position: shows the valve virtual position in %;
-
Out: the analog output slot;
-
Rise Out: the digital output for rising function;
-
Lower Out: the digital output for lowing function;
-
In: allows to set the valve position demand;
-
Full Open Time: allows to set the time for opening valve position from 0% to 100%;
-
Full Close Time: allows to set the time for closing valve position from 100% to 0%;
-
Adjustment Active: triggers the remote adjustment procedure;
-
Adjustment Period: allows to set the adjustment procedure recall period in hours;
-
Next Adjustment In: shows the time (in minutes) to the next adjustment procedure.
The RaiseLower component has the following action:
-
Adjust: valve adjustment procedure recall (adjusts physical and virtual valve position).
|
Out Value |
Rise |
Lower |
Description |
|---|---|---|---|
|
0 |
Off |
Off |
Off |
|
4 |
Off |
On |
Lower |
|
7 |
Off |
Off |
Static |
|
10 |
On |
Off |
Rise |
Analog output voltage level function