Skip to main content
Skip table of contents

List of Modbus Registers

Modbus Address

Decimal Address

Hex Address

Register Name

Access

Description

40001

0

0x0

VERSION TYPE

Read/Write Memory

First byte means a version and another one a type of device. Allows to enable 1 of 4 device actions.

30002

1

0x1

ADDRESS DIPSWITCH

Read-only

Address selected by address DIP switches

30003

2

0x2

CFG DIPSWITCH

Read-only

Configuration selected by CFG DIP switches

30004

3

0x3

RECEIVED FRAMES COUNTER

Read-only

Number of received frames

30006

5

0x5

ERROR FRAMES COUNTER

Read-only

Number of error frames

30008

7

0x7

TRANSMITTED FRAMES COUNTER

Read-only

Number of transmitted frames

30012

11

0xB

UP TIME

Read-only

Controller up time

40017

16

0x10

BAUD RATE

Read/Write Memory

The default value is 76800

30018

17

0x11

STOP BITS

Read-only

The constant value is 1

30019

18

0x12

DATA BITS

Read-only

The constant value is 8

30020

19

0x13

PARITY BITS

Read-only

The constant value is 0(none)

40021

20

0x14

REPLY DELAY

Read/Write Memory

The default value is 0

30041

40

0x28

DIGITAL INPUTS STATUS

Read-only

Bit0 – DI1 Status

Bit1 – DI2 Status

Bit2 – DI3 Status

Bit3 – DI4 Status

30042

41

0x29

DIGITAL OUTPUTS STATUS

Read-only

Bit0 – Light 1  Status O1

Bit1 – Light 2  Status O2

30043

42

0x2A

SPECIAL INPUTS STATUS

Read-only

Bit0 – SI1 Status

Bit1 – SI2 Status

40101

100

0x64

DIGITAL COMMANDS

Read/Write

Bit0 – DI1 Command

Bit1 – DI2 Command

Bit2 – DI3 Command

Bit3 – DI4 Command

40102

101

0x65

DIGITAL INPUT BLOCKING

Read/Write Memory

Value range from 0 to 1 (0 – no blocking; 1 – blocked)

Bit0 – DI1 Blocking

Bit1 – DI2 Blocking

Bit2 – DI3 Blocking

Bit3 – DI4 Blocking

40103

102

0x66

SPECIAL INPUT 1 PIR TYPE

Read/Write Memory

Value range from 5 to 6.

5 – time relay NO,

6 – time relay NC (default value)

40104

103

0x67

SPECIAL INPUT 2 PIR TYPE

Read/Write Memory

Value range from 5 to 6.

5 – time relay NO,

6 – time relay NC (default value)

40107

106

0x6A

SPECIAL INPUT 1 DELAY OFF TIME

Read/Write Memory

Value range from 0 to 65535 seconds.

The default value is 300s.

40108

107

0x6B

SPECIAL INPUT 2 DELAY OFF TIME

Read/Write Memory

Value range from 0 to 65535 seconds.

The default value is 300s.

30148

147

0x93

SPECIAL INPUTS PIR STATUS

Read-only

Bit0 – SI1 PIR Status

Bit1 – SI2 PIR Status

30156

155

0x9B

DIPSWITCH_CFG_REGISTER

Read-only

Value range 0-1.

Bit0 – DI1_DI2_SWITCH_TYPE

(0 – monostable; 1 – bistable)

Bit1 – DI1_CONTROL_MODE

(0 - DALI 1 only; 1 - DALI 1 + DALI2)

Bit2 – SI1_CONTROL_MODE

(0 - DALI 1 only; 1 - DALI 1 + DALI2)

Bit3 – DI2_CONTROL_MODE

(0 - DALI 2 only; 1 - DALI 1 + DALI2)

Bit4 – SI2_CONTROL_MODE

(0 - DALI 2 only; 1 - DALI 1 + DALI2)

Bit5 - LIGHT_CONTROL_MODE

(0 – DALI mode; 1 – ON/OFF mode)

Bit6 – DI3_DI4_SWITCH_TYPE

(0 – monostable; 1 – bistable)

30157

156

0x9C

DALI1 FAULT STATUS REGISTER

Read-only

Ballasts fault status storage (0 – no fault, 1 – fault)

Bit0 – Ballast 1 fault

Bit1 – Ballast 2 fault

Bit2 – Ballast 3 fault

Bit3 – Ballast 4 fault

Bit4 – Ballast 5 fault

Bit5 – Ballast 6 fault

Bit6 – Ballast 7 fault

Bit7 – Ballast 8 fault

Bit8 – Ballast 9 fault

Bit9 – Ballast 10 fault

Bit10 – Ballast 11 fault

Bit11 – Ballast 12 fault

Bit12 – Ballast 13 fault

Bit13 – Ballast 14 fault

Bit14 – Ballast 15 fault

Bit15 – Ballast 16 fault

30158

157

0x9D

DALI2 FAULT STATUS REGISTER

Read-only

Ballasts fault status storage (0 – no fault, 1 – fault)

Bit0 – Ballast 1 fault

Bit1 – Ballast 2 fault

Bit2 – Ballast 3 fault

Bit3 – Ballast 4 fault

Bit4 – Ballast 5 fault

Bit5 – Ballast 6 fault

Bit6 – Ballast 7 fault

Bit7 – Ballast 8 fault

Bit8 – Ballast 9 fault

Bit9 – Ballast 10 fault

Bit10 – Ballast 11 fault

Bit11 – Ballast 12 fault

Bit12 – Ballast 13 fault

Bit13 – Ballast 14 fault

Bit14 – Ballast 15 fault

Bit15 – Ballast 16 fault

30161

160

0xA0

DALI1 BALLAST 1 ACTUAL LEVEL

Read-only

Actual BALLAST1 state. Value range 0-255. (255 - fault)

30162

161

0xA1

DALI1 BALLAST 2 ACTUAL LEVEL

Read-only

Actual BALLAST2 state. Value range 0-255. (255 - fault)

30163

162

0xA2

DALI1 BALLAST 3 ACTUAL LEVEL

Read-only

Actual BALLAST3 state. Value range 0-255. (255 - fault)

30164

163

0xA3

DALI1 BALLAST 4 ACTUAL LEVEL

Read-only

Actual BALLAST4 state. Value range 0-255. (255 - fault)

30165

164

0xA4

DALI1 BALLAST 5 ACTUAL LEVEL

Read-only

Actual BALLAST5 state. Value range 0-255. (255 - fault)

30166

165

0xA5

DALI1 BALLAST 6 ACTUAL LEVEL

Read-only

Actual BALLAST6 state. Value range 0-255. (255 - fault)

30167

166

0xA6

DALI1 BALLAST 7 ACTUAL LEVEL

Read-only

Actual BALLAST7 state. Value range 0-255. (255 - fault)

30168

167

0xA7

DALI1 BALLAST 8 ACTUAL LEVEL

Read-only

Actual BALLAST8 state. Value range 0-255. (255 - fault)

30169

168

0xA8

DALI1 BALLAST 9 ACTUAL LEVEL

Read-only

Actual BALLAST9 state. Value range 0-255. (255 - fault)

30170

169

0xA9

DALI1 BALLAST 10 ACTUAL LEVEL

Read-only

Actual BALLAST10 state. Value range 0-255. (255 - fault)

30171

170

0xAA

DALI1 BALLAST 11 ACTUAL LEVEL

Read-only

Actual BALLAST11 state. Value range 0-255. (255 - fault)

30172

171

0xAB

DALI1 BALLAST 12 ACTUAL LEVEL

Read-only

Actual BALLAST12 state. Value range 0-255. (255 - fault)

30173

172

0xAC

DALI1 BALLAST 13 ACTUAL LEVEL

Read-only

Actual BALLAST13 state. Value range 0-255. (255 - fault)

30174

173

0xAD

DALI1 BALLAST 14 ACTUAL LEVEL

Read-only

Actual BALLAST14 state. Value range 0-255. (255 - fault)

30175

174

0xAE

DALI1 BALLAST 15 ACTUAL LEVEL

Read-only

Actual BALLAST15 state. Value range 0-255. (255 - fault)

30176

175

0xAF

DALI1 BALLAST 16 ACTUAL LEVEL

Read-only

Actual BALLAST16 state. Value range 0-255. (255 - fault)

30177

176

0xB0

DALI2 BALLAST 1 ACTUAL LEVEL

Read-only

Actual BALLAST1 state. Value range 0-255. (255 - fault)

30178

177

0xB1

DALI2 BALLAST 2 ACTUAL LEVEL

Read-only

Actual BALLAST2 state. Value range 0-255. (255 - fault)

30179

178

0xB2

DALI2 BALLAST 3 ACTUAL LEVEL

Read-only

Actual BALLAST3 state. Value range 0-255. (255 - fault)

30180

179

0xB3

DALI2 BALLAST 4 ACTUAL LEVEL

Read-only

Actual BALLAST4 state. Value range 0-255. (255 - fault)

30181

180

0xB4

DALI2 BALLAST 5 ACTUAL LEVEL

Read-only

Actual BALLAST5 state. Value range 0-255. (255 - fault)

30182

181

0xB5

DALI2 BALLAST 6 ACTUAL LEVEL

Read-only

Actual BALLAST6 state. Value range 0-255. (255 - fault)

30183

182

0xB6

DALI2 BALLAST 7 ACTUAL LEVEL

Read-only

Actual BALLAST7 state. Value range 0-255. (255 - fault)

30184

183

0xB7

DALI2 BALLAST 8 ACTUAL LEVEL

Read-only

Actual BALLAST8 state. Value range 0-255. (255 - fault)

30185

184

0xB8

DALI2 BALLAST 9 ACTUAL LEVEL

Read-only

Actual BALLAST9 state. Value range 0-255. (255 - fault)

30186

185

0xB9

DALI2 BALLAST 10 ACTUAL LEVEL

Read-only

Actual BALLAST10 state. Value range 0-255. (255 - fault)

30187

186

0xBA

DALI2 BALLAST 11 ACTUAL LEVEL

Read-only

Actual BALLAST11 state. Value range 0-255. (255 - fault)

30188

187

0xBB

DALI2 BALLAST 12 ACTUAL LEVEL

Read-only

Actual BALLAST12 state. Value range 0-255. (255 - fault)

30189

188

0xBC

DALI2 BALLAST 13 ACTUAL LEVEL

Read-only

Actual BALLAST13 state. Value range 0-255. (255 - fault)

30190

189

0xBD

DALI2 BALLAST 14 ACTUAL LEVEL

Read-only

Actual BALLAST14 state. Value range 0-255. (255 - fault)

30191

190

0xBE

DALI2 BALLAST 15 ACTUAL LEVEL

Read-only

Actual BALLAST15 state. Value range 0-255. (255 - fault)

30192

191

0xBF

DALI2 BALLAST 16 ACTUAL LEVEL

Read-only

Actual BALLAST16 state. Value range 0-255. (255 - fault)

30225

224

0xE0

DALI1 DISCOVERY PROGRESS

Read-only

Value range 0-100%.

30226

225

0xE1

DALI2 DISCOVERY PROGRESS

Read-only

Value range 0-100%.

30229

228

0xE4

DALI1 RECEIVED FRAMES COUNTER

Read-only

Number of correct answers from ballasts on DALI1 interface

30231

230

0xE6

DALI2 RECEIVED FRAMES COUNTER

Read-only

Number of correct answers from ballasts on DALI2 interface

30237

236

0xEC

DALI1 ERROR FRAMES COUNTER

Read-only

Number of incorrect answers from ballasts on DALI1 interface

30239

238

0xEE

DALI2 ERROR FRAMES COUNTER

Read-only

Number of incorrect answers from ballasts on DALI2 interface

30245

244

0xF4

DALI1 TRANSMITTED FRAMES COUNTER

Read-only

Number of send commands to ballasts on DALI1 interface

30247

246

0xF6

DALI2 TRANSMITTED FRAMES COUNTER

Read-only

Number of send commands to ballasts on DALI2 interface

40253

252

0xFC

DALI COMMAND REGISTER

Read/Write Memory

Value range 0-1. (0 – OFF (default); 1 – ON)

Bit0 – DALI1 ON/OFF state

Bit1 – DALI1 Broadcast Last Scene

Bit2 – DALI1 Broadcast OFF

Bit3 – DI1 Command

Bit4 – DALI2 ON/OFF state

Bit5 – DALI2 Broadcast Last Scene

Bit6 – DALI2 Broadcast OFF

Bit7 – DI2 Command

40254

253

0xFD

DALI1 CFG REGISTER

Read/Write Memory

Value range 0-1.

Bit0 – DALI1 ON/OFF state (0 – OFF (default); 1 – ON)

Bit1 – Broadcast Last Scene (0 – OFF (default); 1 – ON)

Bit2 – Broadcast OFF (0 – OFF (default); 1 – ON)

Bit3 – SI1 Blocking (0 – OFF; 1 – ON (default))

Bit4 – DI1 Dimming OFF (0 – Active (default); 1 – Inactive)

Bit11 –  All ballasts reset (0 – OFF (default); 1 – ON)

Bit12 –  Discover new initialization (0 – OFF (default); 1 – ON)

Bit13 –  Replace ballast (0 – OFF (default); 1 – ON)

Bit14 –  Add new ballast (0 – OFF (default); 1 – ON)

Bit15 –  Clear short addresses (0 – OFF (default); 1 – ON)

40255

254

0xFE

DALI2 CFG REGISTER

Read/Write Memory

Value range 0-1.

Bit0 – DALI1 ON/OFF state (0 – OFF (default); 1 – ON)

Bit1 – Broadcast Last Scene (0 – OFF (default); 1 – ON)

Bit2 – Broadcast OFF (0 – OFF (default); 1 – ON)

Bit3 – SI1 Blocking (0 – OFF; 1 – ON (default))

Bit4 – DI1 Dimming OFF (0 – Active (default); 1 – Inactive)

Bit11 –  All ballasts reset (0 – OFF (default); 1 – ON)

Bit12 –  Discover new initialization (0 – OFF (default); 1 – ON)

Bit13 –  Replace ballast (0 – OFF (default); 1 – ON)

Bit14 –  Add new ballast (0 – OFF (default); 1 – ON)

Bit15 –  Clear short addresses (0 – OFF (default); 1 – ON)

40258

257

0x101

DALI1 NUMBER OF BALLASTS

Read-only

Give the number of detected ballasts on DALI1 interface

40259

258

0x102

DALI2 NUMBER OF BALLASTS

Read-only

Give the number of detected ballasts on DALI2 interface

40262

261

0x105

DALI1 BLINK REGISTER

Read/Write Memory

Ballasts blinking procedure. Value 1 will turn ON blinking until value 0 would be send or device would be reset.

Bit0 – Ballast 1 blink

Bit1 – Ballast 2 blink

Bit2 – Ballast 3 blink

Bit3 – Ballast 4 blink

Bit4 – Ballast 5 blink

Bit5 – Ballast 6 blink

Bit6 – Ballast 7 blink

Bit7 – Ballast 8 blink

Bit8 – Ballast 9 blink

Bit9 – Ballast 10 blink

Bit10 – Ballast 11 blink

Bit11 – Ballast 12 blink

Bit12 – Ballast 13 blink

Bit13 – Ballast 14 blink

Bit14 – Ballast 15 blink

Bit15 – Ballast 16 blink

40263

262

0x106

DALI2 BLINK REGISTER

Read/Write Memory

Ballasts blinking procedure. Value 1 will turn ON blinking until value 0 would be send or device would be reset.

Bit0 – Ballast 1 blink

Bit1 – Ballast 2 blink

Bit2 – Ballast 3 blink

Bit3 – Ballast 4 blink

Bit4 – Ballast 5 blink

Bit5 – Ballast 6 blink

Bit6 – Ballast 7 blink

Bit7 – Ballast 8 blink

Bit8 – Ballast 9 blink

Bit9 – Ballast 10 blink

Bit10 – Ballast 11 blink

Bit11 – Ballast 12 blink

Bit12 – Ballast 13 blink

Bit13 – Ballast 14 blink

Bit14 – Ballast 15 blink

Bit15 – Ballast 16 blink

40266

265

0x109

DALI1 DIMMING STATE

Read/Write Memory

Value is set from BMS – send after every value change. 255 – will stop fade if it is in process and stops there. Value range 0 - 255. 

40267

266

0x10A

DALI2 DIMMING STATE

Read/Write Memory

Value is set from BMS – send after every value change. 255 – will stop fade if it is in process and stops there. Value range 0 - 255. 

40270

269

0x10D

DALI1 BALLAST1 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40271

270

0x10E

DALI1 BALLAST2 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40272

271

0x10F

DALI1 BALLAST3 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40273

272

0x110

DALI1 BALLAST4 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40274

273

0x111

DALI1 BALLAST5 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40275

274

0x112

DALI1 BALLAST6 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40276

275

0x113

DALI1 BALLAST7 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40277

276

0x114

DALI1 BALLAST8 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40278

277

0x115

DALI1 BALLAST9 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40279

278

0x116

DALI1 BALLAST10 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40280

279

0x117

DALI1 BALLAST11 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40281

280

0x118

DALI1 BALLAST12 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40282

281

0x119

DALI1 BALLAST13 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40283

282

0x11A

DALI1 BALLAST14 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40284

283

0x11B

DALI1 BALLAST15 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40285

284

0x11C

DALI1 BALLAST16 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40286

285

0x11D

DALI2 BALLAST1 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40287

286

0x11E

DALI2 BALLAST2 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40288

287

0x11F

DALI2 BALLAST3 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40289

288

0x120

DALI2 BALLAST4 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40290

289

0x121

DALI2 BALLAST5 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40291

290

0x122

DALI2 BALLAST6 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40292

291

0x123

DALI2 BALLAST7 SETPOINT

Read/Write Memory

Value range 1-254.  (254 – default)

40293

292

0x124

DALI2 BALLAST8 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40294

293

0x125

DALI2 BALLAST9 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40295

294

0x126

DALI2 BALLAST10 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40296

295

0x127

DALI2 BALLAST11 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40297

296

0x128

DALI2 BALLAST12 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40298

297

0x129

DALI2 BALLAST13 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40299

298

0x12A

DALI2 BALLAST14 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40300

299

0x12B

DALI2 BALLAST15 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40301

300

0x12C

DALI2 BALLAST16 SETPOINT

Read/Write Memory

Value range 1-254. (254 – default)

40334

333

0x14D

DALI1 BALLAST1 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40335

334

0x14E

DALI1 BALLAST2 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40336

335

0x14F

DALI1 BALLAST3 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40337

336

0x150

DALI1 BALLAST4 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40338

337

0x151

DALI1 BALLAST5 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40339

338

0x152

DALI1 BALLAST6 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40340

339

0x153

DALI1 BALLAST7 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40341

340

0x154

DALI1 BALLAST8 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40342

341

0x155

DALI1 BALLAST9 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40343

342

0x156

DALI1 BALLAST10 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40344

343

0x157

DALI1 BALLAST11 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40345

344

0x158

DALI1 BALLAST12 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40346

345

0x159

DALI1 BALLAST13 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40347

346

0x15A

DALI1 BALLAST14 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40348

347

0x15B

DALI1 BALLAST15 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40349

348

0x15C

DALI1 BALLAST16 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40350

349

0x15D

DALI2 BALLAST1 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40351

350

0x15E

DALI2 BALLAST2 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40352

351

0x15F

DALI2 BALLAST3 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40353

352

0x160

DALI2 BALLAST4 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40354

353

0x161

DALI2 BALLAST5 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40355

354

0x162

DALI2 BALLAST6 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40356

355

0x163

DALI2 BALLAST7 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40357

356

0x164

DALI2 BALLAST8 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40358

357

0x165

DALI2 BALLAST9 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40359

358

0x166

DALI2 BALLAST10 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40360

359

0x167

DALI2 BALLAST11 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40361

360

0x168

DALI2 BALLAST12 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40362

361

0x169

DALI2 BALLAST13 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40363

362

0x16A

DALI2 BALLAST14 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40364

363

0x16B

DALI2 BALLAST15 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40365

364

0x16C

DALI2 BALLAST16 MIN

Read/Write Memory

Minimum setpoint value. Value range 0-253. (0 – default)

40398

397

0x18D

DALI1 BALLAST1 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40399

398

0x18E

DALI1 BALLAST2 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40400

399

0x18F

DALI1 BALLAST3 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40401

400

0x190

DALI1 BALLAST4 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40402

401

0x191

DALI1 BALLAST5 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40403

402

0x192

DALI1 BALLAST6 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40404

403

0x193

DALI1 BALLAST7 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40405

404

0x194

DALI1 BALLAST8 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40406

405

0x195

DALI1 BALLAST9 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40407

406

0x196

DALI1 BALLAST10 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40408

407

0x197

DALI1 BALLAST11 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40409

408

0x198

DALI1 BALLAST12 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40410

409

0x199

DALI1 BALLAST13 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40411

410

0x19A

DALI1 BALLAST14 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40412

411

0x19B

DALI1 BALLAST15 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40413

412

0x19C

DALI1 BALLAST16 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40414

413

0x19D

DALI2 BALLAST1 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40415

414

0x19E

DALI2 BALLAST2 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40416

415

0x19F

DALI2 BALLAST3 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40417

416

0x1A0

DALI2 BALLAST4 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40418

417

0x1A1

DALI2 BALLAST5 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40419

418

0x1A2

DALI2 BALLAST6 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40420

419

0x1A3

DALI2 BALLAST7 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40421

420

0x1A4

DALI2 BALLAST8 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40422

421

0x1A5

DALI2 BALLAST9 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40423

422

0x1A6

DALI2 BALLAST10 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40424

423

0x1A7

DALI2 BALLAST11 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40425

424

0x1A8

DALI2 BALLAST12 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40426

425

0x1A9

DALI2 BALLAST13 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40427

426

0x1AA

DALI2 BALLAST14 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40428

427

0x1AB

DALI2 BALLAST15 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40429

428

0x1AC

DALI2 BALLAST16 MAX

Read/Write Memory

Maximum setpoint value. Value range 1-254. (254 – default)

40462

461

0x1CD

DALI1 FADE RATE

Read/Write Memory

Dimming speed. Value range 1-15. (1 – from MIN to MAX in 0.7 sec; 15 – from MIN to MAX in 90 sec)

40463

462

0x1CD

DALI2 FADE RATE

Read/Write Memory

Dimming speed. Value range 1-15. (1 – from MIN to MAX in 0.7 sec; 15 – from MIN to MAX in 90 sec)

40466

465

0x1D1

DALI1 FADE TIME

Read/Write Memory

Setpoint change speed. Value range 0-15. (0 – no transition; 15 – transition from one state to another state in 90 sec)

40467

466

0x1D2

DALI2 FADE TIME

Read/Write Memory

Setpoint change speed. Value range 0-15. (0 – no transition; 15 – transition from one state to another state in 90 sec)

40470

469

0x1D5

DALI1 POWER ON LEVEL

Read/Write Memory

Ballasts setpoint after power supply. Value range 0-254.

40471

470

0x1D6

DALI2 POWER ON LEVEL

Read/Write Memory

Ballasts setpoint after power supply. Value range 0-254.

40474

473

0x1D9

DALI1 SYSTEM FAILURE LEVEL

Read/Write Memory

Ballasts setpoint after DALI interface failure or disconnect from it. Value range 0-254.

40475

474

0x1DA

DALI2 SYSTEM FAILURE LEVEL

Read/Write Memory

Ballasts setpoint after DALI interface failure or disconnect from it. Value range 0-254.

404894880x1E8LLC_SETPOINT_ZONE_1Read/write

Setpoint value of the light level for zone 1

Value range: 0-60000 lx

Default: 1000 lx
404904890x1E9LLC_SETPOINT_ZONE_2Read/write

Setpoint value of the light level for zone 2

Value range: 0-60000 lx

Default: 1000 lx
404934920x1ECLLC_ZONE_COUNTRead/write

Quantity of zones to be controlled separately

Value range: 1/2

Default: 2
404944930x1EDLUX_MIN_SENSOR_1Read/write

Minimum value of the light level sensor for zone 1

Value range: 0-60000 lx

Default: 0 lx
404954940x1EELUX_MIN_SENSOR_2Read/write

Minimum value of the light level sensor for zone 2

Value range: 0-60000 lx

Default: 0 lx
404984970x1F1LUX_MAX_SENSOR_1Read/write

Maximum value of the light level sensor for zone 1

Value range: 0-60000 lx

Default: 3000 lx
404994980x1F2LUX_MAX_SENSOR_2Read/write

Maximum value of the light level sensor for zone 2

Value range: 0-60000 lx

Default: 3000 lx
404784770x1DDLLC_OFFSETRead/write

Offset value between the values controlled on the DALI2 bus in reference to the DALI1 bus

Value range: -254 - 254

Default: 0
405025010x1F5LUX_SENSOR_TYPE_1Read/write

Special input mode used to read the signal from the lux level sensor 1

Value range: 0-10 V [0], 0-5 V [1], 2-10 V [2], 0-20 mA [3], 4-20 mA [4]

Default: 0-10 V
405035020x1F6LUX_SENSOR_TYPE_2Read/write

Special input mode used to read the signal from the lux level sensor 2

Value range: 0-10 V [0], 0-5 V [1], 2-10 V [2], 0-20 mA [3], 4-20 mA [4]

Default: 0-10 V
405065050x1F9LUX_SENSOR_ENABLERead/write

Enables either lux level sensor

Value range: 0/1

Default: 1
404854840x1E4LLC_PIR_1_DIMM_TIMERead/write

Time, which, upon expiring, dims the light in the zone 1 if the presence sensor detects no movement

Value range: 0-65535 s

Default: 0
404864850x1E5LLC_PIR_2_DIMM_TIMERead/write

Time, which, upon expiring, dims the light in the zone 2 if the presence sensor detects no movement

Value range: 0-65535 s

Default: 0
404814800x1E0LLC_PIR_1_DIMM_LEVELRead/writeDimmed light level after counting down the time set in the LLC_PIR_1_DIMM_TIME register

Value range: 0-65535%

Default: 20%
404824810x1E1LLC_PIR_2_DIMM_LEVELRead/write

Dimmed light level after counting down the time set in the LLC_PIR_2_DIMM_TIME register

Value range: 0-100%

Default: 20%
405075060x1FALLC_KP_ZONE_1Read/write

Proportional gain of the PID controller for zone 1

Default: 0,021
405095080x1FCLLC_KP_ZONE_2Read/write

Proportional gain of the PID controller for zone 2

Default: 0,021
405155140x202LLC_KI_ZONE_1Read/write

Integral gain of the PID controller for zone 1

Default: 0,007
405175160x204LLC_KI_ZONE_2Read/write

Integral gain of the PID controller for zone 2

Default: 0,007
405235220x20ALLC_KD_ZONE_1Read/write

Derivative gain of the PID controller for zone 1

Default: 0,012
405255240x20CLLC_KD_ZONE_2Read/write

Derivative gain of the PID controller for zone 2

Default: 0,012
406816800x2A8LUX_STATUS_1Read-onlyLight intensity value read from S1
406826810x2A9LUX_STATUS_2Read-onlyLight intensity value read from S2
List of Modbus registers


JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.