Modbus Address |
Decimal Address |
Hex Address |
Register Name |
Access |
Description |
|---|---|---|---|---|---|
|
40001 |
0 |
0x0 |
VERSION TYPE |
Read/Write Memory |
First byte means a version and another one a type of device. Allows to enable 1 of 4 device actions. |
|
30002 |
1 |
0x1 |
ADDRESS DIPSWITCH |
Read-only |
Address selected by address DIP switches |
|
30003 |
2 |
0x2 |
CFG DIPSWITCH |
Read-only |
Configuration selected by CFG DIP switches |
|
30004 |
3 |
0x3 |
RECEIVED FRAMES COUNTER |
Read-only |
Number of received frames |
|
30006 |
5 |
0x5 |
ERROR FRAMES COUNTER |
Read-only |
Number of error frames |
|
30008 |
7 |
0x7 |
TRANSMITTED FRAMES COUNTER |
Read-only |
Number of transmitted frames |
|
30012 |
11 |
0xB |
UP TIME |
Read-only |
Controller up time |
|
40017 |
16 |
0x10 |
BAUD RATE |
Read/Write Memory |
The default value is 76800 |
|
30018 |
17 |
0x11 |
STOP BITS |
Read-only |
The constant value is 1 |
|
30019 |
18 |
0x12 |
DATA BITS |
Read-only |
The constant value is 8 |
|
30020 |
19 |
0x13 |
PARITY BITS |
Read-only |
The constant value is 0(none) |
|
40021 |
20 |
0x14 |
REPLY DELAY |
Read/Write Memory |
The default value is 0 |
|
30041 |
40 |
0x28 |
DIGITAL INPUTS STATUS |
Read-only |
Bit0 – DI1 Status Bit1 – DI2 Status Bit2 – DI3 Status Bit3 – DI4 Status |
|
30042 |
41 |
0x29 |
DIGITAL OUTPUTS STATUS |
Read-only |
Bit0 – Light 1 Status O1 Bit1 – Light 2 Status O2 |
|
30043 |
42 |
0x2A |
SPECIAL INPUTS STATUS |
Read-only |
Bit0 – SI1 Status Bit1 – SI2 Status |
|
40101 |
100 |
0x64 |
DIGITAL COMMANDS |
Read/Write |
Bit0 – DI1 Command Bit1 – DI2 Command Bit2 – DI3 Command Bit3 – DI4 Command |
|
40102 |
101 |
0x65 |
DIGITAL INPUT BLOCKING |
Read/Write Memory |
Value range from 0 to 1 (0 – no blocking; 1 – blocked) Bit0 – DI1 Blocking Bit1 – DI2 Blocking Bit2 – DI3 Blocking Bit3 – DI4 Blocking |
|
40103 |
102 |
0x66 |
SPECIAL INPUT 1 PIR TYPE |
Read/Write Memory |
Value range from 5 to 6. 5 – time relay NO, 6 – time relay NC (default value) |
|
40104 |
103 |
0x67 |
SPECIAL INPUT 2 PIR TYPE |
Read/Write Memory |
Value range from 5 to 6. 5 – time relay NO, 6 – time relay NC (default value) |
|
40107 |
106 |
0x6A |
SPECIAL INPUT 1 DELAY OFF TIME |
Read/Write Memory |
Value range from 0 to 65535 seconds. The default value is 300s. |
|
40108 |
107 |
0x6B |
SPECIAL INPUT 2 DELAY OFF TIME |
Read/Write Memory |
Value range from 0 to 65535 seconds. The default value is 300s. |
|
30148 |
147 |
0x93 |
SPECIAL INPUTS PIR STATUS |
Read-only |
Bit0 – SI1 PIR Status Bit1 – SI2 PIR Status |
|
30156 |
155 |
0x9B |
DIPSWITCH_CFG_REGISTER |
Read-only |
Value range 0-1. Bit0 – DI1_DI2_SWITCH_TYPE (0 – monostable; 1 – bistable) Bit1 – DI1_CONTROL_MODE (0 - DALI 1 only; 1 - DALI 1 + DALI2) Bit2 – SI1_CONTROL_MODE (0 - DALI 1 only; 1 - DALI 1 + DALI2) Bit3 – DI2_CONTROL_MODE (0 - DALI 2 only; 1 - DALI 1 + DALI2) Bit4 – SI2_CONTROL_MODE (0 - DALI 2 only; 1 - DALI 1 + DALI2) Bit5 - LIGHT_CONTROL_MODE (0 – DALI mode; 1 – ON/OFF mode) Bit6 – DI3_DI4_SWITCH_TYPE (0 – monostable; 1 – bistable) |
|
30157 |
156 |
0x9C |
DALI1 FAULT STATUS REGISTER |
Read-only |
Ballasts fault status storage (0 – no fault, 1 – fault) Bit0 – Ballast 1 fault Bit1 – Ballast 2 fault Bit2 – Ballast 3 fault Bit3 – Ballast 4 fault Bit4 – Ballast 5 fault Bit5 – Ballast 6 fault Bit6 – Ballast 7 fault Bit7 – Ballast 8 fault Bit8 – Ballast 9 fault Bit9 – Ballast 10 fault Bit10 – Ballast 11 fault Bit11 – Ballast 12 fault Bit12 – Ballast 13 fault Bit13 – Ballast 14 fault Bit14 – Ballast 15 fault Bit15 – Ballast 16 fault |
|
30158 |
157 |
0x9D |
DALI2 FAULT STATUS REGISTER |
Read-only |
Ballasts fault status storage (0 – no fault, 1 – fault) Bit0 – Ballast 1 fault Bit1 – Ballast 2 fault Bit2 – Ballast 3 fault Bit3 – Ballast 4 fault Bit4 – Ballast 5 fault Bit5 – Ballast 6 fault Bit6 – Ballast 7 fault Bit7 – Ballast 8 fault Bit8 – Ballast 9 fault Bit9 – Ballast 10 fault Bit10 – Ballast 11 fault Bit11 – Ballast 12 fault Bit12 – Ballast 13 fault Bit13 – Ballast 14 fault Bit14 – Ballast 15 fault Bit15 – Ballast 16 fault |
|
30161 |
160 |
0xA0 |
DALI1 BALLAST 1 ACTUAL LEVEL |
Read-only |
Actual BALLAST1 state. Value range 0-255. (255 - fault) |
|
30162 |
161 |
0xA1 |
DALI1 BALLAST 2 ACTUAL LEVEL |
Read-only |
Actual BALLAST2 state. Value range 0-255. (255 - fault) |
|
30163 |
162 |
0xA2 |
DALI1 BALLAST 3 ACTUAL LEVEL |
Read-only |
Actual BALLAST3 state. Value range 0-255. (255 - fault) |
|
30164 |
163 |
0xA3 |
DALI1 BALLAST 4 ACTUAL LEVEL |
Read-only |
Actual BALLAST4 state. Value range 0-255. (255 - fault) |
|
30165 |
164 |
0xA4 |
DALI1 BALLAST 5 ACTUAL LEVEL |
Read-only |
Actual BALLAST5 state. Value range 0-255. (255 - fault) |
|
30166 |
165 |
0xA5 |
DALI1 BALLAST 6 ACTUAL LEVEL |
Read-only |
Actual BALLAST6 state. Value range 0-255. (255 - fault) |
|
30167 |
166 |
0xA6 |
DALI1 BALLAST 7 ACTUAL LEVEL |
Read-only |
Actual BALLAST7 state. Value range 0-255. (255 - fault) |
|
30168 |
167 |
0xA7 |
DALI1 BALLAST 8 ACTUAL LEVEL |
Read-only |
Actual BALLAST8 state. Value range 0-255. (255 - fault) |
|
30169 |
168 |
0xA8 |
DALI1 BALLAST 9 ACTUAL LEVEL |
Read-only |
Actual BALLAST9 state. Value range 0-255. (255 - fault) |
|
30170 |
169 |
0xA9 |
DALI1 BALLAST 10 ACTUAL LEVEL |
Read-only |
Actual BALLAST10 state. Value range 0-255. (255 - fault) |
|
30171 |
170 |
0xAA |
DALI1 BALLAST 11 ACTUAL LEVEL |
Read-only |
Actual BALLAST11 state. Value range 0-255. (255 - fault) |
|
30172 |
171 |
0xAB |
DALI1 BALLAST 12 ACTUAL LEVEL |
Read-only |
Actual BALLAST12 state. Value range 0-255. (255 - fault) |
|
30173 |
172 |
0xAC |
DALI1 BALLAST 13 ACTUAL LEVEL |
Read-only |
Actual BALLAST13 state. Value range 0-255. (255 - fault) |
|
30174 |
173 |
0xAD |
DALI1 BALLAST 14 ACTUAL LEVEL |
Read-only |
Actual BALLAST14 state. Value range 0-255. (255 - fault) |
|
30175 |
174 |
0xAE |
DALI1 BALLAST 15 ACTUAL LEVEL |
Read-only |
Actual BALLAST15 state. Value range 0-255. (255 - fault) |
|
30176 |
175 |
0xAF |
DALI1 BALLAST 16 ACTUAL LEVEL |
Read-only |
Actual BALLAST16 state. Value range 0-255. (255 - fault) |
|
30177 |
176 |
0xB0 |
DALI2 BALLAST 1 ACTUAL LEVEL |
Read-only |
Actual BALLAST1 state. Value range 0-255. (255 - fault) |
|
30178 |
177 |
0xB1 |
DALI2 BALLAST 2 ACTUAL LEVEL |
Read-only |
Actual BALLAST2 state. Value range 0-255. (255 - fault) |
|
30179 |
178 |
0xB2 |
DALI2 BALLAST 3 ACTUAL LEVEL |
Read-only |
Actual BALLAST3 state. Value range 0-255. (255 - fault) |
|
30180 |
179 |
0xB3 |
DALI2 BALLAST 4 ACTUAL LEVEL |
Read-only |
Actual BALLAST4 state. Value range 0-255. (255 - fault) |
|
30181 |
180 |
0xB4 |
DALI2 BALLAST 5 ACTUAL LEVEL |
Read-only |
Actual BALLAST5 state. Value range 0-255. (255 - fault) |
|
30182 |
181 |
0xB5 |
DALI2 BALLAST 6 ACTUAL LEVEL |
Read-only |
Actual BALLAST6 state. Value range 0-255. (255 - fault) |
|
30183 |
182 |
0xB6 |
DALI2 BALLAST 7 ACTUAL LEVEL |
Read-only |
Actual BALLAST7 state. Value range 0-255. (255 - fault) |
|
30184 |
183 |
0xB7 |
DALI2 BALLAST 8 ACTUAL LEVEL |
Read-only |
Actual BALLAST8 state. Value range 0-255. (255 - fault) |
|
30185 |
184 |
0xB8 |
DALI2 BALLAST 9 ACTUAL LEVEL |
Read-only |
Actual BALLAST9 state. Value range 0-255. (255 - fault) |
|
30186 |
185 |
0xB9 |
DALI2 BALLAST 10 ACTUAL LEVEL |
Read-only |
Actual BALLAST10 state. Value range 0-255. (255 - fault) |
|
30187 |
186 |
0xBA |
DALI2 BALLAST 11 ACTUAL LEVEL |
Read-only |
Actual BALLAST11 state. Value range 0-255. (255 - fault) |
|
30188 |
187 |
0xBB |
DALI2 BALLAST 12 ACTUAL LEVEL |
Read-only |
Actual BALLAST12 state. Value range 0-255. (255 - fault) |
|
30189 |
188 |
0xBC |
DALI2 BALLAST 13 ACTUAL LEVEL |
Read-only |
Actual BALLAST13 state. Value range 0-255. (255 - fault) |
|
30190 |
189 |
0xBD |
DALI2 BALLAST 14 ACTUAL LEVEL |
Read-only |
Actual BALLAST14 state. Value range 0-255. (255 - fault) |
|
30191 |
190 |
0xBE |
DALI2 BALLAST 15 ACTUAL LEVEL |
Read-only |
Actual BALLAST15 state. Value range 0-255. (255 - fault) |
|
30192 |
191 |
0xBF |
DALI2 BALLAST 16 ACTUAL LEVEL |
Read-only |
Actual BALLAST16 state. Value range 0-255. (255 - fault) |
|
30225 |
224 |
0xE0 |
DALI1 DISCOVERY PROGRESS |
Read-only |
Value range 0-100%. |
|
30226 |
225 |
0xE1 |
DALI2 DISCOVERY PROGRESS |
Read-only |
Value range 0-100%. |
|
30229 |
228 |
0xE4 |
DALI1 RECEIVED FRAMES COUNTER |
Read-only |
Number of correct answers from ballasts on DALI1 interface |
|
30231 |
230 |
0xE6 |
DALI2 RECEIVED FRAMES COUNTER |
Read-only |
Number of correct answers from ballasts on DALI2 interface |
|
30237 |
236 |
0xEC |
DALI1 ERROR FRAMES COUNTER |
Read-only |
Number of incorrect answers from ballasts on DALI1 interface |
|
30239 |
238 |
0xEE |
DALI2 ERROR FRAMES COUNTER |
Read-only |
Number of incorrect answers from ballasts on DALI2 interface |
|
30245 |
244 |
0xF4 |
DALI1 TRANSMITTED FRAMES COUNTER |
Read-only |
Number of send commands to ballasts on DALI1 interface |
|
30247 |
246 |
0xF6 |
DALI2 TRANSMITTED FRAMES COUNTER |
Read-only |
Number of send commands to ballasts on DALI2 interface |
|
40253 |
252 |
0xFC |
DALI COMMAND REGISTER |
Read/Write Memory |
Value range 0-1. (0 – OFF (default); 1 – ON) Bit0 – DALI1 ON/OFF state Bit1 – DALI1 Broadcast Last Scene Bit2 – DALI1 Broadcast OFF Bit3 – DI1 Command Bit4 – DALI2 ON/OFF state Bit5 – DALI2 Broadcast Last Scene Bit6 – DALI2 Broadcast OFF Bit7 – DI2 Command |
|
40254 |
253 |
0xFD |
DALI1 CFG REGISTER |
Read/Write Memory |
Value range 0-1. Bit0 – DALI1 ON/OFF state (0 – OFF (default); 1 – ON) Bit1 – Broadcast Last Scene (0 – OFF (default); 1 – ON) Bit2 – Broadcast OFF (0 – OFF (default); 1 – ON) Bit3 – SI1 Blocking (0 – OFF; 1 – ON (default)) Bit4 – DI1 Dimming OFF (0 – Active (default); 1 – Inactive) Bit11 – All ballasts reset (0 – OFF (default); 1 – ON) Bit12 – Discover new initialization (0 – OFF (default); 1 – ON) Bit13 – Replace ballast (0 – OFF (default); 1 – ON) Bit14 – Add new ballast (0 – OFF (default); 1 – ON) Bit15 – Clear short addresses (0 – OFF (default); 1 – ON) |
|
40255 |
254 |
0xFE |
DALI2 CFG REGISTER |
Read/Write Memory |
Value range 0-1. Bit0 – DALI1 ON/OFF state (0 – OFF (default); 1 – ON) Bit1 – Broadcast Last Scene (0 – OFF (default); 1 – ON) Bit2 – Broadcast OFF (0 – OFF (default); 1 – ON) Bit3 – SI1 Blocking (0 – OFF; 1 – ON (default)) Bit4 – DI1 Dimming OFF (0 – Active (default); 1 – Inactive) Bit11 – All ballasts reset (0 – OFF (default); 1 – ON) Bit12 – Discover new initialization (0 – OFF (default); 1 – ON) Bit13 – Replace ballast (0 – OFF (default); 1 – ON) Bit14 – Add new ballast (0 – OFF (default); 1 – ON) Bit15 – Clear short addresses (0 – OFF (default); 1 – ON) |
|
40258 |
257 |
0x101 |
DALI1 NUMBER OF BALLASTS |
Read-only |
Give the number of detected ballasts on DALI1 interface |
|
40259 |
258 |
0x102 |
DALI2 NUMBER OF BALLASTS |
Read-only |
Give the number of detected ballasts on DALI2 interface |
|
40262 |
261 |
0x105 |
DALI1 BLINK REGISTER |
Read/Write Memory |
Ballasts blinking procedure. Value 1 will turn ON blinking until value 0 would be send or device would be reset. Bit0 – Ballast 1 blink Bit1 – Ballast 2 blink Bit2 – Ballast 3 blink Bit3 – Ballast 4 blink Bit4 – Ballast 5 blink Bit5 – Ballast 6 blink Bit6 – Ballast 7 blink Bit7 – Ballast 8 blink Bit8 – Ballast 9 blink Bit9 – Ballast 10 blink Bit10 – Ballast 11 blink Bit11 – Ballast 12 blink Bit12 – Ballast 13 blink Bit13 – Ballast 14 blink Bit14 – Ballast 15 blink Bit15 – Ballast 16 blink |
|
40263 |
262 |
0x106 |
DALI2 BLINK REGISTER |
Read/Write Memory |
Ballasts blinking procedure. Value 1 will turn ON blinking until value 0 would be send or device would be reset. Bit0 – Ballast 1 blink Bit1 – Ballast 2 blink Bit2 – Ballast 3 blink Bit3 – Ballast 4 blink Bit4 – Ballast 5 blink Bit5 – Ballast 6 blink Bit6 – Ballast 7 blink Bit7 – Ballast 8 blink Bit8 – Ballast 9 blink Bit9 – Ballast 10 blink Bit10 – Ballast 11 blink Bit11 – Ballast 12 blink Bit12 – Ballast 13 blink Bit13 – Ballast 14 blink Bit14 – Ballast 15 blink Bit15 – Ballast 16 blink |
|
40266 |
265 |
0x109 |
DALI1 DIMMING STATE |
Read/Write Memory |
Value is set from BMS – send after every value change. 255 – will stop fade if it is in process and stops there. Value range 0 - 255. |
|
40267 |
266 |
0x10A |
DALI2 DIMMING STATE |
Read/Write Memory |
Value is set from BMS – send after every value change. 255 – will stop fade if it is in process and stops there. Value range 0 - 255. |
|
40270 |
269 |
0x10D |
DALI1 BALLAST1 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40271 |
270 |
0x10E |
DALI1 BALLAST2 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40272 |
271 |
0x10F |
DALI1 BALLAST3 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40273 |
272 |
0x110 |
DALI1 BALLAST4 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40274 |
273 |
0x111 |
DALI1 BALLAST5 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40275 |
274 |
0x112 |
DALI1 BALLAST6 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40276 |
275 |
0x113 |
DALI1 BALLAST7 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40277 |
276 |
0x114 |
DALI1 BALLAST8 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40278 |
277 |
0x115 |
DALI1 BALLAST9 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40279 |
278 |
0x116 |
DALI1 BALLAST10 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40280 |
279 |
0x117 |
DALI1 BALLAST11 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40281 |
280 |
0x118 |
DALI1 BALLAST12 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40282 |
281 |
0x119 |
DALI1 BALLAST13 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40283 |
282 |
0x11A |
DALI1 BALLAST14 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40284 |
283 |
0x11B |
DALI1 BALLAST15 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40285 |
284 |
0x11C |
DALI1 BALLAST16 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40286 |
285 |
0x11D |
DALI2 BALLAST1 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40287 |
286 |
0x11E |
DALI2 BALLAST2 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40288 |
287 |
0x11F |
DALI2 BALLAST3 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40289 |
288 |
0x120 |
DALI2 BALLAST4 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40290 |
289 |
0x121 |
DALI2 BALLAST5 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40291 |
290 |
0x122 |
DALI2 BALLAST6 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40292 |
291 |
0x123 |
DALI2 BALLAST7 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40293 |
292 |
0x124 |
DALI2 BALLAST8 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40294 |
293 |
0x125 |
DALI2 BALLAST9 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40295 |
294 |
0x126 |
DALI2 BALLAST10 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40296 |
295 |
0x127 |
DALI2 BALLAST11 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40297 |
296 |
0x128 |
DALI2 BALLAST12 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40298 |
297 |
0x129 |
DALI2 BALLAST13 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40299 |
298 |
0x12A |
DALI2 BALLAST14 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40300 |
299 |
0x12B |
DALI2 BALLAST15 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40301 |
300 |
0x12C |
DALI2 BALLAST16 SETPOINT |
Read/Write Memory |
Value range 1-254. (254 – default) |
|
40334 |
333 |
0x14D |
DALI1 BALLAST1 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40335 |
334 |
0x14E |
DALI1 BALLAST2 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40336 |
335 |
0x14F |
DALI1 BALLAST3 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40337 |
336 |
0x150 |
DALI1 BALLAST4 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40338 |
337 |
0x151 |
DALI1 BALLAST5 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40339 |
338 |
0x152 |
DALI1 BALLAST6 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40340 |
339 |
0x153 |
DALI1 BALLAST7 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40341 |
340 |
0x154 |
DALI1 BALLAST8 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40342 |
341 |
0x155 |
DALI1 BALLAST9 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40343 |
342 |
0x156 |
DALI1 BALLAST10 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40344 |
343 |
0x157 |
DALI1 BALLAST11 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40345 |
344 |
0x158 |
DALI1 BALLAST12 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40346 |
345 |
0x159 |
DALI1 BALLAST13 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40347 |
346 |
0x15A |
DALI1 BALLAST14 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40348 |
347 |
0x15B |
DALI1 BALLAST15 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40349 |
348 |
0x15C |
DALI1 BALLAST16 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40350 |
349 |
0x15D |
DALI2 BALLAST1 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40351 |
350 |
0x15E |
DALI2 BALLAST2 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40352 |
351 |
0x15F |
DALI2 BALLAST3 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40353 |
352 |
0x160 |
DALI2 BALLAST4 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40354 |
353 |
0x161 |
DALI2 BALLAST5 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40355 |
354 |
0x162 |
DALI2 BALLAST6 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40356 |
355 |
0x163 |
DALI2 BALLAST7 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40357 |
356 |
0x164 |
DALI2 BALLAST8 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40358 |
357 |
0x165 |
DALI2 BALLAST9 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40359 |
358 |
0x166 |
DALI2 BALLAST10 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40360 |
359 |
0x167 |
DALI2 BALLAST11 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40361 |
360 |
0x168 |
DALI2 BALLAST12 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40362 |
361 |
0x169 |
DALI2 BALLAST13 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40363 |
362 |
0x16A |
DALI2 BALLAST14 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40364 |
363 |
0x16B |
DALI2 BALLAST15 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40365 |
364 |
0x16C |
DALI2 BALLAST16 MIN |
Read/Write Memory |
Minimum setpoint value. Value range 0-253. (0 – default) |
|
40398 |
397 |
0x18D |
DALI1 BALLAST1 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40399 |
398 |
0x18E |
DALI1 BALLAST2 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40400 |
399 |
0x18F |
DALI1 BALLAST3 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40401 |
400 |
0x190 |
DALI1 BALLAST4 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40402 |
401 |
0x191 |
DALI1 BALLAST5 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40403 |
402 |
0x192 |
DALI1 BALLAST6 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40404 |
403 |
0x193 |
DALI1 BALLAST7 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40405 |
404 |
0x194 |
DALI1 BALLAST8 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40406 |
405 |
0x195 |
DALI1 BALLAST9 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40407 |
406 |
0x196 |
DALI1 BALLAST10 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40408 |
407 |
0x197 |
DALI1 BALLAST11 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40409 |
408 |
0x198 |
DALI1 BALLAST12 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40410 |
409 |
0x199 |
DALI1 BALLAST13 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40411 |
410 |
0x19A |
DALI1 BALLAST14 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40412 |
411 |
0x19B |
DALI1 BALLAST15 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40413 |
412 |
0x19C |
DALI1 BALLAST16 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40414 |
413 |
0x19D |
DALI2 BALLAST1 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40415 |
414 |
0x19E |
DALI2 BALLAST2 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40416 |
415 |
0x19F |
DALI2 BALLAST3 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40417 |
416 |
0x1A0 |
DALI2 BALLAST4 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40418 |
417 |
0x1A1 |
DALI2 BALLAST5 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40419 |
418 |
0x1A2 |
DALI2 BALLAST6 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40420 |
419 |
0x1A3 |
DALI2 BALLAST7 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40421 |
420 |
0x1A4 |
DALI2 BALLAST8 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40422 |
421 |
0x1A5 |
DALI2 BALLAST9 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40423 |
422 |
0x1A6 |
DALI2 BALLAST10 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40424 |
423 |
0x1A7 |
DALI2 BALLAST11 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40425 |
424 |
0x1A8 |
DALI2 BALLAST12 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40426 |
425 |
0x1A9 |
DALI2 BALLAST13 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40427 |
426 |
0x1AA |
DALI2 BALLAST14 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40428 |
427 |
0x1AB |
DALI2 BALLAST15 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40429 |
428 |
0x1AC |
DALI2 BALLAST16 MAX |
Read/Write Memory |
Maximum setpoint value. Value range 1-254. (254 – default) |
|
40462 |
461 |
0x1CD |
DALI1 FADE RATE |
Read/Write Memory |
Dimming speed. Value range 1-15. (1 – from MIN to MAX in 0.7 sec; 15 – from MIN to MAX in 90 sec) |
|
40463 |
462 |
0x1CD |
DALI2 FADE RATE |
Read/Write Memory |
Dimming speed. Value range 1-15. (1 – from MIN to MAX in 0.7 sec; 15 – from MIN to MAX in 90 sec) |
|
40466 |
465 |
0x1D1 |
DALI1 FADE TIME |
Read/Write Memory |
Setpoint change speed. Value range 0-15. (0 – no transition; 15 – transition from one state to another state in 90 sec) |
|
40467 |
466 |
0x1D2 |
DALI2 FADE TIME |
Read/Write Memory |
Setpoint change speed. Value range 0-15. (0 – no transition; 15 – transition from one state to another state in 90 sec) |
|
40470 |
469 |
0x1D5 |
DALI1 POWER ON LEVEL |
Read/Write Memory |
Ballasts setpoint after power supply. Value range 0-254. |
|
40471 |
470 |
0x1D6 |
DALI2 POWER ON LEVEL |
Read/Write Memory |
Ballasts setpoint after power supply. Value range 0-254. |
|
40474 |
473 |
0x1D9 |
DALI1 SYSTEM FAILURE LEVEL |
Read/Write Memory |
Ballasts setpoint after DALI interface failure or disconnect from it. Value range 0-254. |
|
40475 |
474 |
0x1DA |
DALI2 SYSTEM FAILURE LEVEL |
Read/Write Memory |
Ballasts setpoint after DALI interface failure or disconnect from it. Value range 0-254. |
|
40489 |
488 |
0x1E8 |
LLC_SETPOINT_ZONE_1 |
Read/write |
Setpoint value of the light level for zone 1 Value range: 0-60000 lx Default: 1000 lx |
|
40490 |
489 |
0x1E9 |
LLC_SETPOINT_ZONE_2 |
Read/write |
Setpoint value of the light level for zone 2 Value range: 0-60000 lx Default: 1000 lx |
|
40493 |
492 |
0x1EC |
LLC_ZONE_COUNT |
Read/write |
Quantity of zones to be controlled separately Value range: 1/2 Default: 2 |
|
40494 |
493 |
0x1ED |
LUX_MIN_SENSOR_1 |
Read/write |
Minimum value of the light level sensor for zone 1 Value range: 0-60000 lx Default: 0 lx |
|
40495 |
494 |
0x1EE |
LUX_MIN_SENSOR_2 |
Read/write |
Minimum value of the light level sensor for zone 2 Value range: 0-60000 lx Default: 0 lx |
|
40498 |
497 |
0x1F1 |
LUX_MAX_SENSOR_1 |
Read/write |
Maximum value of the light level sensor for zone 1 Value range: 0-60000 lx Default: 3000 lx |
|
40499 |
498 |
0x1F2 |
LUX_MAX_SENSOR_2 |
Read/write |
Maximum value of the light level sensor for zone 2 Value range: 0-60000 lx Default: 3000 lx |
|
40478 |
477 |
0x1DD |
LLC_OFFSET |
Read/write |
Offset value between the values controlled on the DALI2 bus in reference to the DALI1 bus Value range: -254 - 254 Default: 0 |
|
40502 |
501 |
0x1F5 |
LUX_SENSOR_TYPE_1 |
Read/write |
Special input mode used to read the signal from the lux level sensor 1 Value range: 0-10 V [0], 0-5 V [1], 2-10 V [2], 0-20 mA [3], 4-20 mA [4] Default: 0-10 V |
|
40503 |
502 |
0x1F6 |
LUX_SENSOR_TYPE_2 |
Read/write |
Special input mode used to read the signal from the lux level sensor 2 Value range: 0-10 V [0], 0-5 V [1], 2-10 V [2], 0-20 mA [3], 4-20 mA [4] Default: 0-10 V |
|
40506 |
505 |
0x1F9 |
LUX_SENSOR_ENABLE |
Read/write |
Enables either lux level sensor Value range: 0/1 Default: 1 |
|
40485 |
484 |
0x1E4 |
LLC_PIR_1_DIMM_TIME |
Read/write |
Time, which, upon expiring, dims the light in the zone 1 if the presence sensor detects no movement Value range: 0-65535 s Default: 0 |
|
40486 |
485 |
0x1E5 |
LLC_PIR_2_DIMM_TIME |
Read/write |
Time, which, upon expiring, dims the light in the zone 2 if the presence sensor detects no movement Value range: 0-65535 s Default: 0 |
|
40481 |
480 |
0x1E0 |
LLC_PIR_1_DIMM_LEVEL |
Read/write |
Dimmed light level after counting down the time set in the LLC_PIR_1_DIMM_TIME register Value range: 0-65535% Default: 20% |
|
40482 |
481 |
0x1E1 |
LLC_PIR_2_DIMM_LEVEL |
Read/write |
Dimmed light level after counting down the time set in the LLC_PIR_2_DIMM_TIME register Value range: 0-100% Default: 20% |
|
40507 |
506 |
0x1FA |
LLC_KP_ZONE_1 |
Read/write |
Proportional gain of the PID controller for zone 1 Default: 0,021 |
|
40509 |
508 |
0x1FC |
LLC_KP_ZONE_2 |
Read/write |
Proportional gain of the PID controller for zone 2 Default: 0,021 |
|
40515 |
514 |
0x202 |
LLC_KI_ZONE_1 |
Read/write |
Integral gain of the PID controller for zone 1 Default: 0,007 |
|
40517 |
516 |
0x204 |
LLC_KI_ZONE_2 |
Read/write |
Integral gain of the PID controller for zone 2 Default: 0,007 |
|
40523 |
522 |
0x20A |
LLC_KD_ZONE_1 |
Read/write |
Derivative gain of the PID controller for zone 1 Default: 0,012 |
|
40525 |
524 |
0x20C |
LLC_KD_ZONE_2 |
Read/write |
Derivative gain of the PID controller for zone 2 Default: 0,012 |
|
40681 |
680 |
0x2A8 |
LUX_STATUS_1 |
Read-only |
Light intensity value read from S1 |
|
40682 |
681 |
0x2A9 |
LUX_STATUS_2 |
Read-only |
Light intensity value read from S2 |
List of Modbus registers