In the Control Point panel’s VAV submenu dedicated to airflow settings, it is possible to configure the following parameters:
MAXC: allows to set a maximum airflow value for cooling;
-
MaxOccCoolAirflowSetpoint:
-
Modbus register: 40212;
-
BACnet object: AV11, property: Present Value;
-
MINC: allows to set a minimum airflow value for cooling;
-
MinOccCoolAirflowSetpoint:
-
Modbus register: 40213;
-
BACnet object: AV12, property: Present Value;
-
MAXH: allows to set a maximum airflow for heating;
-
MaxOccHeatAirflowSetpoint:
-
Modbus register: 40214;
-
BACnet object: AV13, property: Present Value;
-
MINH: allows to set a minimum airflow for heating;
-
MinOccHeatAirflowSetpoint:
-
Modbus register: 40215;
-
BACnet object: AV14, property: Present Value;
-
STBY: allows to set a minimum airflow in a standby state;
-
StandbyAirflowSetpoint:
-
Modbus register: 40216;
-
BACnet object: AV15, property: Present Value;
-
UNOC: allows to set a minimum airflow in an unoccupied state;
-
UnoccAirflowSetpoint:
-
Modbus register: 40217;
-
BACnet object: AV16, property: Present Value;
-
FANS: allows to set a minimum airflow value for a fan to start operating;
-
StartupFanAirflowSetpoint:
-
Modbus register: 40218;
-
BACnet object: AV17, property: Present Value;
-
KFAC: allows to set a K-factor value according to the type of device for use in the airflow calculations;
-
K-Factor:
-
Modbus register: 40289;
-
BACnet object: AV61, property: Present Value.
-