Modbus Address |
Decimal Address |
Hex Address |
Register Name |
Access |
Description |
||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
30001 |
0 |
0x00 |
VERSION AND DEVICE TYPE |
Read-only |
|
||||||||||||
|
30002 |
1 |
0x01 |
DEVICE ADDRESS (state of switch) |
Read-only |
|
||||||||||||
|
30003 |
2 |
0x02 |
BAUD RATE AND PROTOCOL (state of switch) |
Read-only |
|
||||||||||||
|
30004 |
3 |
0x03 |
MODBUS RECEIVED FRAMES COUNTER (32-bit) |
Read-only |
Default state is 0. Reset at the device start and change of transmission parameters. |
||||||||||||
|
30006 |
5 |
0x05 |
MODBUS ERROR FRAMES COUNTER 32-bit) |
Read-only |
Default state is 0. Reset at the device start and change of transmission parameters. |
||||||||||||
|
30008 |
7 |
0x07 |
MODBUS TRANSMITTED FRAMES COUNTER (32-bit) |
Read-only |
Default state is 0. Reset at the device start and change of transmission parameters. |
||||||||||||
|
30012 |
11 |
0x0B |
UP TIME |
|
Up device time in sec |
||||||||||||
|
30015 |
14 |
0x0E |
M-BUS RECEIVED FRAMES COUNTER |
Read-only |
Default state is 0. Reset at the device start and change of transmission parameters. |
||||||||||||
|
30017 |
16 |
0x10 |
M-BUS TRANSMITTED FRAMES COUNTER |
Read-only |
Default state is 0. Reset at the device start and change of transmission parameters. |
||||||||||||
|
30019 |
18 |
0x12 |
M-BUS ALARMS COUNTER |
Read-only |
Default state is 0. Reset at the device start and change of transmission parameters. |
||||||||||||
|
30130 |
129 |
0x81 |
HARDWARE_VERSION |
Read-only |
The current hardware version of a device |
||||||||||||
|
30131 |
130 |
0x82 |
MAC_ADDRESS (48-bit) |
Read-only |
The MAC address of a device |
||||||||||||
|
40001 |
0 |
0x00 |
DEVICE ACTIONS |
Read/write |
Allows to enable 1 of 3 device actions |
||||||||||||
|
40023 |
22 |
0x16 |
M-BUS BAUD RATE (32-bit) |
Read/write memory |
Baud rate for M-Bus
|
||||||||||||
|
40025 |
24 |
0x18 |
M-BUS CONNECTION TIMEOUT (32-bit) |
Read/write memory |
Timeout of M-Bus connection (default 2000 ms) |
||||||||||||
|
40136 |
135 |
0x87 |
BAUD RATE |
Read/write memory |
Transmission speed is defined by the user calculated using the formula: The value is considered only when sections 1, 2 and 3 of S3 switch is in the OFF position The default value is 7680 (76800 bps) |
||||||||||||
|
40137 |
136 |
0x88 |
STOP BITS |
Read/write memory |
Supported values are 1 and 2. The default value 1. Bit No. 8 activates RS485 biasing resistors in order to pull-up the voltage on the RS485 bus. |
||||||||||||
|
40138 |
137 |
0x89 |
DATA BITS |
Read/write memory |
Supported values are 7 and 8. The default value 8. |
||||||||||||
|
40139 |
138 |
0x8A |
PARITY BIT |
Read/write memory |
Parity Bit (40139) The default value is 0 (no parity) Allowed values:
|
||||||||||||
|
40140 |
139 |
0x8B |
RESPONSE DELAY |
Read/write memory |
Delay in ms before sending response. The default value is 0. |
||||||||||||
|
30293 |
292 |
0x124 |
COUNTER OF FREE MODBUS TCP SOCKETS |
Read-only |
Number of available Modbus TCP sockets |
List of Modbus registers