Breadcrumbs

AAC20 - Simulator - "Unlicensed" status in NV components

Issue

When using the simulator for the AAC20 controller, NV components have an ‘Unlicensed’ status.

image-20240205-115407.png
Figure 1. The “Unlicensed” status for NV components

Solution

The problem with the "Unlicensed" status for NV components from the iSMA_platAAC20 kit occurs because these components write data to the EEPROM memory, which is located exclusively inside the device. Using the simulator, the best solution would be to upload the control kit and use the WriteBool, WriteInt, WriteFloat components.

image-20240205-120056.png
Figure 2. The control kit palette