Skip to main content
Skip table of contents

List of Modbus Registers

Modbus Address

Decimal Address

Hex Address

Register Name

Access

Description

40001

0

0x0

VERSION TYPE

Read/Write Memory

First byte means a version and another one a type of device. Allows to enable 1 of 4 device actions.

30002

1

0x1

ADDRESS DIPSWITCH

Read-only

Address selected by address DIP switches

30003

2

0x2

CFG DIPSWITCH

Read-only

Configuration selected by CFG DIP switches

30004

3

0x3

RECEIVED FRAMES COUNTER

Read-only

Number of received frames

30006

5

0x5

ERROR FRAMES COUNTER

Read-only

Number of error frames

30008

7

0x7

TRANSMITTED FRAMES COUNTER

Read-only

Number of transmitted frames

30012

11

0xB

UP TIME

Read-only

Controller up time

40017

16

0x10

BAUD RATE

Read/Write Memory

The default value is 76800

30018

17

0x11

STOP BITS

Read-only

The constant value is 1

30019

18

0x12

DATA BITS

Read-only

The constant value is 8

30020

19

0x13

PARITY BITS

Read-only

The constant value is 0(none)

40021

20

0x14

REPLY DELAY

Read/Write Memory

The default value is 0

30041

40

0x28

DIGITAL INPUTS STATUS

Read-only

Bit0 – DI1 Status

Bit1 – DI2 Status

Bit2 – DI3 Status

Bit3 – DI4 Status

30042

41

0x29

DIGITAL OUTPUTS STATUS

Read-only

Bit0 – Light 1  Status O1

Bit1 – Light 2  Status O2

Bit2 – Blind UP Status O3

Bit3 – Blind DOWN Status O4

30043

42

0x2A

SPECIAL INPUTS STATUS

Read-only

Bit0 – SI1 Status

Bit1 – SI2 Status

40101

100

0x64

DIGITAL COMMANDS

Read/Write

Bit0 – DI1 Command

Bit1 – DI2 Command

Bit2 – DI3 Command

Bit3 – DI4 Command

40102

101

0x65

DIGITAL INPUT BLOCKING

Read/Write Memory

Value range from 0 to 1 (0 – no blocking; 1 – blocked)

Bit0 – DI1 Blocking

Bit1 – DI2 Blocking

Bit2 – DI3 Blocking

Bit3 – DI4 Blocking

40103

102

0x66

SPECIAL INPUT 1 PIR TYPE

Read/Write Memory

Value range from 5 to 6.

5 – time relay NO,

6 – time relay NC (default value)

40104

103

0x67

SPECIAL INPUT 2 PIR TYPE

Read/Write Memory

Value range from 5 to 6.

5 – time relay NO,

6 – time relay NC (default value)

40107

106

0x6A

SPECIAL INPUT 1 DELAY OFF TIME

Read/Write Memory

Value range from 0 to 65535 seconds.

The default value is 300s.

40108

107

0x6B

SPECIAL INPUT 2 DELAY OFF TIME

Read/Write Memory

Value range from 0 to 65535 seconds.

The default value is 300s.

30148

147

0x93

SPECIAL INPUTS PIR STATUS

Read-only

Bit0 – SI1 PIR Status

Bit1 – SI2 PIR Status

30156

155

0x9B

DIPSWITCH_CFG_REGISTER

Read-only

Value range 0-1.

Bit0 – DI1_DI2_SWITCH_TYPE

(0 – monostable; 1 – bistable)

Bit1 – DI1_CONTROL_MODE

(0 - DALI 1 only; 1 - DALI 1 + DALI2)

Bit2 – SI1_CONTROL_MODE

(0 - DALI 1 only; 1 - DALI 1 + DALI2)

Bit3 – DI2_CONTROL_MODE

(0 - DALI 2 only; 1 - DALI 1 + DALI2)

Bit4 – SI2_CONTROL_MODE

(0 - DALI 2 only; 1 - DALI 1 + DALI2)

Bit5 - LIGHT_CONTROL_MODE

(0 – DALI mode; 1 – ON/OFF mode)

Bit6 – DI3_DI4_SWITCH_TYPE

(0 – monostable; 1 – bistable)

Bit7 – BLIND_CONTROL_MODE

(0 -blind ; 1 - shutter)

30157

156

0x9C

DALI1 FAULT STATUS REGISTER

Read-only

Ballasts fault status storage (0 – no fault, 1 – fault)

Bit0 – Ballast 1 fault

Bit1 – Ballast 2 fault

Bit2 – Ballast 3 fault

Bit3 – Ballast 4 fault

Bit4 – Ballast 5 fault

Bit5 – Ballast 6 fault

Bit6 – Ballast 7 fault

Bit7 – Ballast 8 fault

Bit8 – Ballast 9 fault

Bit9 – Ballast 10 fault

Bit10 – Ballast 11 fault

Bit11 – Ballast 12 fault

Bit12 – Ballast 13 fault

Bit13 – Ballast 14 fault

Bit14 – Ballast 15 fault

Bit15 – Ballast 16 fault

30158

157

0x9D

DALI2 FAULT STATUS REGISTER

Read-only

Ballasts fault status storage (0 – no fault, 1 – fault)

Bit0 – Ballast 1 fault

Bit1 – Ballast 2 fault

Bit2 – Ballast 3 fault

Bit3 – Ballast 4 fault

Bit4 – Ballast 5 fault

Bit5 – Ballast 6 fault

Bit6 – Ballast 7 fault

Bit7 – Ballast 8 fault

Bit8 – Ballast 9 fault

Bit9 – Ballast 10 fault

Bit10 – Ballast 11 fault

Bit11 – Ballast 12 fault

Bit12 – Ballast 13 fault

Bit13 – Ballast 14 fault

Bit14 – Ballast 15 fault

Bit15 – Ballast 16 fault

30161

160

0xA0

DALI1 BALLAST 1 ACTUAL LEVEL

Read-only

Actual BALLAST1 state. Value range 0-255. (255 - fault)

30162

161

0xA1

DALI1 BALLAST 2 ACTUAL LEVEL

Read-only

Actual BALLAST2 state. Value range 0-255. (255 - fault)

30163

162

0xA2

DALI1 BALLAST 3 ACTUAL LEVEL

Read-only

Actual BALLAST3 state. Value range 0-255. (255 - fault)

30164

163

0xA3

DALI1 BALLAST 4 ACTUAL LEVEL

Read-only

Actual BALLAST4 state. Value range 0-255. (255 - fault)

30165

164

0xA4

DALI1 BALLAST 5 ACTUAL LEVEL

Read-only

Actual BALLAST5 state. Value range 0-255. (255 - fault)

30166

165

0xA5

DALI1 BALLAST 6 ACTUAL LEVEL

Read-only

Actual BALLAST6 state. Value range 0-255. (255 - fault)

30167

166

0xA6

DALI1 BALLAST 7 ACTUAL LEVEL

Read-only

Actual BALLAST7 state. Value range 0-255. (255 - fault)

30168

167

0xA7

DALI1 BALLAST 8 ACTUAL LEVEL

Read-only

Actual BALLAST8 state. Value range 0-255. (255 - fault)

30169

168

0xA8

DALI1 BALLAST 9 ACTUAL LEVEL

Read-only

Actual BALLAST9 state. Value range 0-255. (255 - fault)

30170

169

0xA9

DALI1 BALLAST 10 ACTUAL LEVEL

Read-only

Actual BALLAST10 state. Value range 0-255. (255 - fault)

30171

170

0xAA

DALI1 BALLAST 11 ACTUAL LEVEL

Read-only

Actual BALLAST11 state. Value range 0-255. (255 - fault)

30172

171

0xAB

DALI1 BALLAST 12 ACTUAL LEVEL

Read-only

Actual BALLAST12 state. Value range 0-255. (255 - fault)

30173

172

0xAC

DALI1 BALLAST 13 ACTUAL LEVEL

Read-only

Actual BALLAST13 state. Value range 0-255. (255 - fault)

30174

173

0xAD

DALI1 BALLAST 14 ACTUAL LEVEL

Read-only

Actual BALLAST14 state. Value range 0-255. (255 - fault)

30175

174

0xAE

DALI1 BALLAST 15 ACTUAL LEVEL

Read-only

Actual BALLAST15 state. Value range 0-255. (255 - fault)

30176

175

0xAF

DALI1 BALLAST 16 ACTUAL LEVEL

Read-only

Actual BALLAST16 state. Value range 0-255. (255 - fault)

30177

176

0xB0

DALI2 BALLAST 1 ACTUAL LEVEL

Read-only

Actual BALLAST1 state. Value range 0-255. (255 - fault)

30178

177

0xB1

DALI2 BALLAST 2 ACTUAL LEVEL

Read-only

Actual BALLAST2 state. Value range 0-255. (255 - fault)

30179

178

0xB2

DALI2 BALLAST 3 ACTUAL LEVEL

Read-only

Actual BALLAST3 state. Value range 0-255. (255 - fault)

30180

179

0xB3

DALI2 BALLAST 4 ACTUAL LEVEL

Read-only

Actual BALLAST4 state. Value range 0-255. (255 - fault)

30181

180

0xB4

DALI2 BALLAST 5 ACTUAL LEVEL

Read-only

Actual BALLAST5 state. Value range 0-255. (255 - fault)

30182

181

0xB5

DALI2 BALLAST 6 ACTUAL LEVEL

Read-only

Actual BALLAST6 state. Value range 0-255. (255 - fault)

30183

182

0xB6

DALI2 BALLAST 7 ACTUAL LEVEL

Read-only

Actual BALLAST7 state. Value range 0-255. (255 - fault)

30184

183

0xB7

DALI2 BALLAST 8 ACTUAL LEVEL

Read-only

Actual BALLAST8 state. Value range 0-255. (255 - fault)

30185

184

0xB8

DALI2 BALLAST 9 ACTUAL LEVEL

Read-only

Actual BALLAST9 state. Value range 0-255. (255 - fault)

30186

185

0xB9

DALI2 BALLAST 10 ACTUAL LEVEL

Read-only

Actual BALLAST10 state. Value range 0-255. (255 - fault)

30187

186

0xBA

DALI2 BALLAST 11 ACTUAL LEVEL

Read-only

Actual BALLAST11 state. Value range 0-255. (255 - fault)

30188

187

0xBB

DALI2 BALLAST 12 ACTUAL LEVEL

Read-only

Actual BALLAST12 state. Value range 0-255. (255 - fault)

30189

188

0xBC

DALI2 BALLAST 13 ACTUAL LEVEL

Read-only

Actual BALLAST13 state. Value range 0-255. (255 - fault)

30190

189

0xBD

DALI2 BALLAST 14 ACTUAL LEVEL

Read-only

Actual BALLAST14 state. Value range 0-255. (255 - fault)

30191

190

0xBE

DALI2 BALLAST 15 ACTUAL LEVEL

Read-only

Actual BALLAST15 state. Value range 0-255. (255 - fault)

30192

191

0xBF

DALI2 BALLAST 16 ACTUAL LEVEL

Read-only

Actual BALLAST16 state. Value range 0-255. (255 - fault)

30225

224

0xE0

DALI1 DISCOVERY PROGRESS

Read-only

Value range 0-100%.

30226

225

0xE1

DALI2 DISCOVERY PROGRESS

Read-only

Value range 0-100%.

30229

228

0xE4

DALI1 RECEIVED FRAMES COUNTER

Read-only

Number of correct answers from ballasts on DALI1 interface

30231

230

0xE6

DALI2 RECEIVED FRAMES COUNTER

Read-only

Number of correct answers from ballasts on DALI2 interface

30237

236

0xEC

DALI1 ERROR FRAMES COUNTER

Read-only

Number of incorrect answers from ballasts on DALI1 interface

30239

238

0xEE

DALI2 ERROR FRAMES COUNTER

Read-only

Number of incorrect answers from ballasts on DALI2 interface

30245

244

0xF4

DALI1 TRANSMITTED FRAMES COUNTER

Read-only

Number of send commands to ballasts on DALI1 interface

30247

246

0xF6

DALI2 TRANSMITTED FRAMES COUNTER

Read-only

Number of send commands to ballasts on DALI2 interface

40253

252

0xFC

DALI COMMAND REGISTER

Read/Write Memory

Value range 0-1. (0 – OFF (default); 1 – ON)

Bit0 – DALI1 ON/OFF state

Bit1 – DALI1 Broadcast Last Scene

Bit2 – DALI1 Broadcast OFF

Bit3 – DI1 Command

Bit4 – DALI2 ON/OFF state

Bit5 – DALI2 Broadcast Last Scene

Bit6 – DALI2 Broadcast OFF

Bit7 – DI2 Command

40254

253

0xFD

DALI1 CFG REGISTER

Read/Write Memory

Value range 0-1.

Bit0 – DALI1 ON/OFF state (0 – OFF (default); 1 – ON)

Bit1 – Broadcast Last Scene (0 – OFF (default); 1 – ON)

Bit2 – Broadcast OFF (0 – OFF (default); 1 – ON)

Bit3 – SI1 Blocking (0 – OFF; 1 – ON (default))

Bit4 – DI1 Dimming OFF (0 – Active (default); 1 – Inactive)

Bit11 –  All ballasts reset (0 – OFF (default); 1 – ON)

Bit12 –  Discover new initialization (0 – OFF (default); 1 – ON)

Bit13 –  Replace ballast (0 – OFF (default); 1 – ON)

Bit14 –  Add new ballast (0 – OFF (default); 1 – ON)

Bit15 –  Clear short addresses (0 – OFF (default); 1 – ON)

40255

254

0xFE

DALI2 CFG REGISTER

Read/Write Memory

Value range 0-1.

Bit0 – DALI1 ON/OFF state (0 – OFF (default); 1 – ON)

Bit1 – Broadcast Last Scene (0 – OFF (default); 1 – ON)

Bit2 – Broadcast OFF (0 – OFF (default); 1 – ON)

Bit3 – SI1 Blocking (0 – OFF; 1 – ON (default))

Bit4 – DI1 Dimming OFF (0 – Active (default); 1 – Inactive)

Bit11 –  All ballasts reset (0 – OFF (default); 1 – ON)

Bit12 –  Discover new initialization (0 – OFF (default); 1 – ON)

Bit13 –  Replace ballast (0 – OFF (default); 1 – ON)

Bit14 –  Add new ballast (0 – OFF (default); 1 – ON)

Bit15 –  Clear short addresses (0 – OFF (default); 1 – ON)

40258

257

0x101

DALI1 NUMBER OF BALLASTS

Read-only

Give the number of detected ballasts on DALI1 interface

40259

258

0x102

DALI2 NUMBER OF BALLASTS

Read-only

Give the number of detected ballasts on DALI2 interface

40262

261

0x105

DALI1 BLINK REGISTER

Read/Write Memory

Ballasts blinking procedure. Value 1 will turn ON blinking until value 0 would be send or device would be reset.

Bit0 – Ballast 1 blink

Bit1 – Ballast 2 blink

Bit2 – Ballast 3 blink

Bit3 – Ballast 4 blink

Bit4 – Ballast 5 blink

Bit5 – Ballast 6 blink

Bit6 – Ballast 7 blink

Bit7 – Ballast 8 blink

Bit8 – Ballast 9 blink

Bit9 – Ballast 10 blink

Bit10 – Ballast 11 blink

Bit11 – Ballast 12 blink

Bit12 – Ballast 13 blink

Bit13 – Ballast 14 blink

Bit14 – Ballast 15 blink

Bit15 – Ballast 16 blink

40263

262

0x106

DALI2 BLINK REGISTER

Read/Write Memory

Ballasts blinking procedure. Value 1 will turn ON blinking until value 0 would be send or device would be reset.

Bit0 – Ballast 1 blink

Bit1 – Ballast 2 blink

Bit2 – Ballast 3 blink

Bit3 – Ballast 4 blink

Bit4 – Ballast 5 blink

Bit5 – Ballast 6 blink

Bit6 – Ballast 7 blink

Bit7 – Ballast 8 blink

Bit8 – Ballast 9 blink

Bit9 – Ballast 10 blink

Bit10 – Ballast 11 blink

Bit11 – Ballast 12 blink

Bit12 – Ballast 13 blink

Bit13 – Ballast 14 blink

Bit14 – Ballast 15 blink

Bit15 – Ballast 16 blink

40266

265

0x109

DALI1 DIMMING STATE

Read/Write Memory

Value is set from BMS – send after every value change. 255 – will stop fade if it is in process and stops there. Value range 0 - 255. 

40267

266

0x10A

DALI2 DIMMING STATE

Read/Write Memory

Value is set from BMS – send after every value change. 255 – will stop fade if it is in process and stops there. Value range 0 - 255. 

40270

269

0x10D

DALI1 BALLAST1 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40271

270

0x10E

DALI1 BALLAST2 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40272

271

0x10F

DALI1 BALLAST3 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40273

272

0x110

DALI1 BALLAST4 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40274

273

0x111

DALI1 BALLAST5 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40275

274

0x112

DALI1 BALLAST6 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40276

275

0x113

DALI1 BALLAST7 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40277

276

0x114

DALI1 BALLAST8 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40278

277

0x115

DALI1 BALLAST9 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40279

278

0x116

DALI1 BALLAST10 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40280

279

0x117

DALI1 BALLAST11 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40281

280

0x118

DALI1 BALLAST12 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40282

281

0x119

DALI1 BALLAST13 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40283

282

0x11A

DALI1 BALLAST14 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40284

283

0x11B

DALI1 BALLAST15 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40285

284

0x11C

DALI1 BALLAST16 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40286

285

0x11D

DALI2 BALLAST1 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40287

286

0x11E

DALI2 BALLAST2 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40288

287

0x11F

DALI2 BALLAST3 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40289

288

0x120

DALI2 BALLAST4 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40290

289

0x121

DALI2 BALLAST5 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40291

290

0x122

DALI2 BALLAST6 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40292

291

0x123

DALI2 BALLAST7 SETPOINT

Read/Write Memory

Value range 1 – 254.  (254 – default)

40293

292

0x124

DALI2 BALLAST8 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40294

293

0x125

DALI2 BALLAST9 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40295

294

0x126

DALI2 BALLAST10 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40296

295

0x127

DALI2 BALLAST11 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40297

296

0x128

DALI2 BALLAST12 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40298

297

0x129

DALI2 BALLAST13 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40299

298

0x12A

DALI2 BALLAST14 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40300

299

0x12B

DALI2 BALLAST15 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40301

300

0x12C

DALI2 BALLAST16 SETPOINT

Read/Write Memory

Value range 1 – 254. (254 – default)

40334

333

0x14D

DALI1 BALLAST1 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40335

334

0x14E

DALI1 BALLAST2 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40336

335

0x14F

DALI1 BALLAST3 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40337

336

0x150

DALI1 BALLAST4 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40338

337

0x151

DALI1 BALLAST5 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40339

338

0x152

DALI1 BALLAST6 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40340

339

0x153

DALI1 BALLAST7 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40341

340

0x154

DALI1 BALLAST8 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40342

341

0x155

DALI1 BALLAST9 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40343

342

0x156

DALI1 BALLAST10 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40344

343

0x157

DALI1 BALLAST11 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40345

344

0x158

DALI1 BALLAST12 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40346

345

0x159

DALI1 BALLAST13 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40347

346

0x15A

DALI1 BALLAST14 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40348

347

0x15B

DALI1 BALLAST15 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40349

348

0x15C

DALI1 BALLAST16 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40350

349

0x15D

DALI2 BALLAST1 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40351

350

0x15E

DALI2 BALLAST2 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40352

351

0x15F

DALI2 BALLAST3 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40353

352

0x160

DALI2 BALLAST4 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40354

353

0x161

DALI2 BALLAST5 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40355

354

0x162

DALI2 BALLAST6 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40356

355

0x163

DALI2 BALLAST7 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40357

356

0x164

DALI2 BALLAST8 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40358

357

0x165

DALI2 BALLAST9 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40359

358

0x166

DALI2 BALLAST10 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40360

359

0x167

DALI2 BALLAST11 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40361

360

0x168

DALI2 BALLAST12 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40362

361

0x169

DALI2 BALLAST13 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40363

362

0x16A

DALI2 BALLAST14 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40364

363

0x16B

DALI2 BALLAST15 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40365

364

0x16C

DALI2 BALLAST16 MIN

Read/Write Memory

Minimum setpoint value. Value range 0 – 253. (0 – default)

40398

397

0x18D

DALI1 BALLAST1 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40399

398

0x18E

DALI1 BALLAST2 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40400

399

0x18F

DALI1 BALLAST3 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40401

400

0x190

DALI1 BALLAST4 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40402

401

0x191

DALI1 BALLAST5 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40403

402

0x192

DALI1 BALLAST6 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40404

403

0x193

DALI1 BALLAST7 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40405

404

0x194

DALI1 BALLAST8 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40406

405

0x195

DALI1 BALLAST9 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40407

406

0x196

DALI1 BALLAST10 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40408

407

0x197

DALI1 BALLAST11 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40409

408

0x198

DALI1 BALLAST12 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40410

409

0x199

DALI1 BALLAST13 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40411

410

0x19A

DALI1 BALLAST14 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40412

411

0x19B

DALI1 BALLAST15 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40413

412

0x19C

DALI1 BALLAST16 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40414

413

0x19D

DALI2 BALLAST1 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40415

414

0x19E

DALI2 BALLAST2 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40416

415

0x19F

DALI2 BALLAST3 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40417

416

0x1A0

DALI2 BALLAST4 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40418

417

0x1A1

DALI2 BALLAST5 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40419

418

0x1A2

DALI2 BALLAST6 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40420

419

0x1A3

DALI2 BALLAST7 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40421

420

0x1A4

DALI2 BALLAST8 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40422

421

0x1A5

DALI2 BALLAST9 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40423

422

0x1A6

DALI2 BALLAST10 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40424

423

0x1A7

DALI2 BALLAST11 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40425

424

0x1A8

DALI2 BALLAST12 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40426

425

0x1A9

DALI2 BALLAST13 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40427

426

0x1AA

DALI2 BALLAST14 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40428

427

0x1AB

DALI2 BALLAST15 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40429

428

0x1AC

DALI2 BALLAST16 MAX

Read/Write Memory

Maximum setpoint value. Value range 1 – 254. (254 – default)

40462

461

0x1CD

DALI1 FADE RATE

Read/Write Memory

Dimming speed. Value range 1 – 15. (1 – from MIN to MAX in 0.7 sec; 15 – from MIN to MAX in 90 sec)

40463

462

0x1CD

DALI2 FADE RATE

Read/Write Memory

Dimming speed. Value range 1 – 15. (1 – from MIN to MAX in 0.7 sec; 15 – from MIN to MAX in 90 sec)

40466

465

0x1D1

DALI1 FADE TIME

Read/Write Memory

Setpoint change speed. Value range 0 – 15. (0 – no transition; 15 – transition from one state to another state in 90 sec)

40467

466

0x1D2

DALI2 FADE TIME

Read/Write Memory

Setpoint change speed. Value range 0 – 15. (0 – no transition; 15 – transition from one state to another state in 90 sec)

40470

469

0x1D5

DALI1 POWER ON LEVEL

Read/Write Memory

Ballasts setpoint after power supply. Value range 0 – 254.

40471

470

0x1D6

DALI2 POWER ON LEVEL

Read/Write Memory

Ballasts setpoint after power supply. Value range 0 – 254.

40474

473

0x1D9

DALI1 SYSTEM FAILURE LEVEL

Read/Write Memory

Ballasts setpoint after DALI interface failure or disconnect from it. Value range 0 – 254.

40475

474

0x1DA

DALI2 SYSTEM FAILURE LEVEL

Read/Write Memory

Ballasts setpoint after DALI interface failure or disconnect from it. Value range 0 – 254.

40600

599

0x257

SLATS BLOCKING COIL REG

Read/Write Memory

Value range 0 – 1. (0 – short press control slats; 1 – short press is in middle press function mode)

Bit0 – SLATS 1 blocking local

40601

600

0x258

BLIND UP TIME

Read/Write Memory

Blind opening time – could be set from BMS. Default value – 0 ms.

40617

616

0x268

BLIND DOWN TIME

Read/Write Memory

Blind closing time – could be set from BMS. Default value – 0 ms.

40633

632

0x278

SLATS OPENING TIME

Read/Write Memory

Slats full opening time – could be set only from BMS. Default value – 1000 ms.

40649

648

0x288

BLIND STATE

Read/Write Memory

Value range 0-100%.


40657

656

0x290

SLATS STATE

Read/Write Memory

Value range 0-100%.


40665

664

0x298

BLIND_OFF_DELAY

Read/Write Memory

Blind\Shutter pull up time. Value range 0 – 100 (5 - default value)

40673

672

0x2A0

SLATS NUMBER OF STEPS

Read/Write Memory

Value range 1-10. (10 - default value)

List of Modbus registers