Registered Access
|
Modbus Address |
Decimal Address |
Hex Address |
Register Name |
Access |
Description |
|---|---|---|---|---|---|
|
30001 |
0 |
0x00 |
Version/Type |
Read |
Version and type of the device |
|
30002 |
1 |
0x01 |
Address |
Read |
Module address |
|
40003 |
2 |
0x02 |
Baud Rate |
Read/write |
RS485 baud rate |
|
40004 |
3 |
0x03 |
Stop Bits & Data Bits |
Read/write |
No of stop bits & data bits |
|
40005 |
4 |
0x04 |
Parity |
Read/write |
Parity bit |
|
40006 |
5 |
0x05 |
Response Delay |
Read/write |
Response delay in ms |
|
40007 |
6 |
0x06 |
Modbus Mode |
Read/write |
Modbus mode (ASCII or RTU) |
|
40009 |
8 |
0x08 |
Watchdog |
Read/write |
Watchdog |
|
40013 |
12 |
0x0C |
Default Output State |
Read/write |
Default output state (after power on or watchdog reset) |
|
40033 |
32 |
0x20 |
Received Packets LSR (Least Significant Register) |
Read/write |
No. of received packets |
|
40034 |
33 |
0x21 |
Received Packets MSR (Most Significant Register) |
Read/write |
|
|
40035 |
34 |
0x22 |
Incorrect Packets LSR |
Read/write |
No. of received packets with error |
|
40036 |
35 |
0x23 |
Incorrect Packets MSR |
Read/write |
|
|
40037 |
36 |
0x24 |
Sent Packets LSR |
Read/write |
No. of sent packets |
|
40038 |
37 |
0x25 |
Sent Packets MSR |
Read/write |
|
|
30051 |
50 |
0x32 |
Inputs |
Read |
Inputs state |
|
40052 |
51 |
0x33 |
Outputs |
Read/write |
Output state |
|
40053 |
52 |
0x34 |
Counter 1 LSR |
Read/write |
32-bit counter 1 |
|
40054 |
53 |
0x35 |
Counter 1 MSR |
Read/write |
|
|
40055 |
54 |
0x36 |
Counter 2 LSR |
Read/write |
32-bit counter 2 |
|
40056 |
55 |
0x37 |
Counter 2 MSR |
Read/write |
|
|
40061 |
60 |
0x3C |
CCounter 1 LSR |
Read/write |
32-bit value of captured counter 1 |
|
40062 |
61 |
0x3D |
CCounter 1 MSR |
Read/write |
|
|
40063 |
62 |
0x3E |
CCounter 2 LSR |
Read/write |
32-bit value of captured counter 2 |
|
40064 |
63 |
0x3F |
CCounter 2 MSR |
Read/write |
|
|
40069 |
68 |
0x44 |
Counter Config 1 |
Read/write |
Counter configuration
|
|
40070 |
69 |
0x45 |
Counter Config 2 |
Read/write |
|
|
40073 |
72 |
0x48 |
Catch |
Read/write |
Catch counter |
|
40074 |
73 |
0x49 |
Status |
Read/write |
Captured counter |
Registered access
Bit Access
|
Modbus Address |
Dec Address |
Hex
|
Register Name |
Access |
Description |
|---|---|---|---|---|---|
|
193 |
192 |
0x0C0 |
Default State of Output 1 |
Read/write |
Default state of output 1 |
|
194 |
193 |
0x0C1 |
Default State of Output 2 |
Read/write |
Default state of output 2 |
|
10801 |
800 |
0x320 |
Input 1 |
Read |
Input 1 state |
|
10802 |
801 |
0x321 |
Input 2 |
Read |
Input 2 state |
|
817 |
816 |
0x330 |
Output 1 |
Read/write |
Output 1 state |
|
818 |
817 |
0x331 |
Output 2 |
Read/write |
Output 2 state |
|
1153 |
1152 |
0x480 |
Capture 1 |
Read/write |
Capture counter 1 |
|
1154 |
1153 |
0x481 |
Capture 2 |
Read/write |
Capture counter 2 |
|
1169 |
1168 |
0x490 |
Captured 1 |
Read/write |
Captured value of counter 1 |
|
1170 |
1169 |
0x491 |
Captured 2 |
Read/write |
Captured value of counter 2 |
Bit access