Skip to main content
Skip table of contents

Module Registers


Registered Access

Modbus Address

Decimal Address

Hex Address

Register Name

Access

Description

30001

0

0x00

Version/Type

Read

Version and type of the device

30002

1

0x01

Address

Read

Module address

40003

2

0x02

Baud Rate

Read/write

RS485 baud rate

40004

3

0x03

Stop Bits & Data Bits

Read/write

No of stop bits & data bits

40005

4

0x04

Parity

Read/write

Parity bit

40006

5

0x05

Response Delay

Read/write

Response delay in ms

40007

6

0x06

Modbus Mode

Read/write

Modbus mode (ASCII or RTU)

40009

8

0x08

Watchdog

Read/write

Watchdog

40013

12

0x0C

Default Output State

Read/write

Default output state (after power on or watchdog reset)

40033

32

0x20

Received Packets LSR (Least Significant Register)

Read/write

No. of received packets

40034

33

0x21

Received Packets MSR (Most Significant Register)

Read/write

40035

34

0x22

Incorrect Packets LSR

Read/write

No. of received packets with error

40036

35

0x23

Incorrect Packets MSR

Read/write

40037

36

0x24

Sent Packets LSR

Read/write

No. of sent packets

40038

37

0x25

Sent Packets MSR

Read/write

30051

50

0x32

Inputs

Read

Inputs state

40052

51

0x33

Outputs

Read/write

Output state

40053

52

0x34

Counter 1 LSR

Read/write

32-bit counter 1

40054

53

0x35

Counter 1 MSR

Read/write

40055

54

0x36

Counter 2 LSR

Read/write

32-bit counter 2

40056

55

0x37

Counter 2 MSR

Read/write

40061

60

0x3C

CCounter 1 LSR

Read/write

32-bit value of captured counter 1

40062

61

0x3D

CCounter 1 MSR

Read/write

40063

62

0x3E

CCounter 2 LSR

Read/write

32-bit value of captured counter 2

40064

63

0x3F

CCounter 2 MSR

Read/write

40069

68

0x44

Counter Config 1

Read/write

Counter configuration

+1 – time measurement (if 0 counting impulses)
+2 – autocatch counter every 1 sec
+4 – catch value when input low
+8 – reset counter after catch
+16 – reset counter if input low
+32 – encoder

40070

69

0x45

Counter Config 2

Read/write

40073

72

0x48

Catch

Read/write

Catch counter

40074

73

0x49

Status

Read/write

Captured counter

Registered access

Bit Access

Modbus Address

Dec Address

Hex
Address

Register Name

Access

Description

193

192

0x0C0

Default State of Output 1

Read/write

Default state of output 1

194

193

0x0C1

Default State of Output 2

Read/write

Default state of output 2

10801

800

0x320

Input 1

Read

Input 1 state

10802

801

0x321

Input 2

Read

Input 2 state

817

816

0x330

Output 1

Read/write

Output 1 state

818

817

0x331

Output 2

Read/write

Output 2 state

1153

1152

0x480

Capture 1

Read/write

Capture counter 1

1154

1153

0x481

Capture 2

Read/write

Capture counter 2

1169

1168

0x490

Captured 1

Read/write

Captured value of counter 1

1170

1169

0x491

Captured 2

Read/write

Captured value of counter 2

Bit access