Breadcrumbs

MainMenuBoolean

Warning!

Component applicable for the LP and Control Point panels.

The MainMenuBoolean component is responsible for reading/writing and configuration of a single Boolean parameter, which is placed in the LP panel main menu.

88 MainMenuBoolean.png
MainMenuBoolean component

The MainMenuBoolean component has the following slots:

  • Status: shows the point’s status;

  • Fault Cause: shows the fault cause description;

  • Fault Status: shows the point error status (true: point read/write error);

  • Enable: enables or disables the point (true: enabled, false: disabled);

  • Poll Frequency: allows to set the reading poll frequency (fast, normal, slow);

  • Write Type: allows to set the writing mode (COV: only on the In slot change, COV_PollFrequency: on the In slot change and periodically, PollFrequency: only periodically, COV_LinkSet: only on the In slot change, using the "reverse following the link" function);

  • Trigger: allows to force sending values on rising edge;

  • Out: the main menu point output slot, the current value;

  • In: the main menu point input slot;

  • Point No: the panel’s main menu point number;

  • Point Display Name: allows to set the point display name on the LCD screen (up to 4, only ASCII characters);

  • Point Visibility: allows to activate or deactivate the point on the display;

  • Point True Text: allows to set the 4 characters LCD display text in the true state (only ASCII characters);

  • Point False Text: allows to set the 4 characters LCD display text in the false state (only ASCII characters);

  • Point Priority: allows to set the displaying priority on the LCD screen (starting from the lowest value);

  • Config Trigger: sends configuration parameters to the device components on rising edge.

The MainMenuBoolean component has the following right-click menu actions:

  • Set True: sets the true state in the In slot and sends it to the main menu point;

  • Set False: sets the false state in the In slot and sends it to the main menu point;

  • Write: sends the In slot state to the main menu point;

  • Read: reads the panel main menu point value and sets the Out slot;

  • Send Value: sends the point user value to the main menu without changing the In slot, from the pop-up window;

  • Read Config: reads the main menu point configuration parameters from the panel (Point Display Name, Point Visibility, Point True Text, Point False Text, Point Priority);

  • Write Config: writes the main menu point configuration parameters to the panel (Point Display Name, Point Visibility, Point True Text, Point False Text, Point Priority).