Skip to main content
Skip table of contents

List of Modbus Registers

Warning!

Please note that the following table contains registers for all series of the Control Point panels.

The Control Point VAV series by default has no fan control and registers referring to fan control are inapplicable. If the fan control is activated on the Control Point VAV series panel, the registers become applicable too.

Modbus address

Decimal address

Hex address

Register name

Access

Description

40001

0

0x00

VERSION_TYPE

Read/write

Version and type of device. Additionally, allows to enable 1 of 4 device operations (reset panel, reload settings, reset settings, enter bootloader).

30004-30005

3-4

0x03

RECEIVED_FRAMES (32-bit)

Read-only

Number of received frames. Resets at the unit start and change of transmission parameters.

30006-30007

5-6

0x05

ERROR_FRAMES (32-bit)

Read-only

Number of error frames. Resets at the unit start and change of transmission parameters.

30008-30009

7-8

0x07

TRANSMITTED_FRAMES _(32-bit)

Read-only

Number of transmitted frames. Resets at the unit start and change of transmission parameters.

30012-30013

11-12

0x0C

LIVE_TIME (32-bit)

Read-only

Device uptime in seconds

30014

13

0x0D

RESET_SOURCE

Read-only

Source of a last device restart

40015-40016

14-15

0x0E

BACNET_DEVICE_ID (32-bit)

Read/write, memory

Default: 0xFFFFFFFF

40017

16

0x10

BAUD_RATE

Read/write, memory

Default: 11520 (115200 bps).

40018

17

0x11

STOP_BITS

Read/write, memory

Supported values are 1 and 2. Default: 1.

40019

18

0x12

DATA_BITS

Read/write, memory

Supported values are 7 and 8. Default: 8.

40020

19

0x13

PARITY_BITS

Read/write, memory

The default value is 0 (no parity).

Value

Description

0 (default)

None

1

Odd

2

Even

40021

20

0x14

REPLAY_DELAY

Read/write, memory

Delay in ms before sending a response. Default: 0.

40023

22

0x16

ADDRESS

Read/write, memory

Modbus address of the device. Default: 1.

40024

23

0x17

PROTOCOL

Read/write, memory

Protocol set in the panel. To set the BACnet MS/TP protocol, use the DIP switch.

Bit

Value

0

Modbus RTU (default)

1

Modbus ASCII

2

BACnet MS/TP (read-only)

40028

27

0x1B

PANEL_PASSWORD

Read/write, memory

Password for the panel settings. Default: 1000.

30029

28

0x1C

SENSORS

Read-only

Sensors built-in in the panel:

Bit

Value

0

Temperature sensor

1

CO2 sensor

2

Humidity sensor

30030

29

0x1D

BOOTLOADER_VERSION

Read-only

Bootloader version

30031

30

0x1E

HW_VERSION

Read-only

Hardware version

30035

34

0x22

SERIAL_NUMBER

Read-only

Device’s serial number (64-bit)

30050

49

0x31

SUBTYPE

Read-only

Device’s subtype: Control Point, Control Point VAV

30201

200

0xC8

BACKGROUND_LCD_CURRENT_VALUE

Read-only

Current display illumination value

30202

201

0xC9

BACKGROUND_KEY_PAD_CURRENT_VALUE

Read-only

Current keypad illumination value

40203

202

0xCA

HOURS

Read/write

Hours part of time display

40204

203

0xCB

MINUTES

Read/write

Minutes part of time display

40205

204

0xCC

DEVICE_CONFIGURATION

Read/write, memory

Bit

Name

0

1

0

BUZZER

Not active

Active (default)

1

TIME_FORMAT

24-hour (default)

12-hour

2

DEFAULT_TEMPERATURE_UNIT

Celsius (default)

Fahrenheit

3

BACKGROUND_ILLUMINATION_ LCD_ACTIVE

Not active

Active (default)

4

BACKGROUND_ILLUMINATION_KEY_PAD_ACTIVE

Not active (default)

Active

5

CO2_IN_ALARM_FLASHING_LCD

Not active

Active

6

CO2_IN_ALARM_BUZZER

Not active

Active

7

CO2_IN_ALARM_SHOW_HIGH

Not active

Active

8

CO2_ALARM_CONFIRM_ENABLE

Not active

Active

10

SUBMENU_ICON_DISPLAY_OFF

Not active

Active

11

PANEL_OFF

Panel off

Panel on (default)

12

KEY_PAD_OFF

Keypad off

Keypad on (default)

13

LCD_FLASHING

Not active (default)

Active

14

KEY_PAD_FLASHING

Not active (default)

Active

40207

206

0xCE

BACKGROUND_LCD_FOR_ACTIVE_MODE

Read/write, memory

Default: 60%

40208

207

0xCF

BACKGROUND_LCD_FOR_IDLE_MODE

Read/write, memory

Default: 40%

40209

208

0xD0

BACKGROUND_LCD_FOR_STANDBY_MODE

Read/write, memory

Default: 5%

40210

209

0xD1

BACKGROUND_LCD_TIME_TO_IDLE_

Read/write, memory

Default: 10 sec

40211

210

0xD2

BACKGROUND_LCD_TIME_TO_STANDBY

Read/write, memory

Default: 5 sec

40212

211

0xD3

BACKGROUND_KEY_PAD_ACTIVE_MODE

Read/write, memory

Default: 10%

40213

212

0xD4

BACKGROUND_KEY_PAD_IDLE_MODE

Read/write, memory

Default: 40%

40214

213

0xD5

BACKGROUND_KEY_PAD_STANDBY_MODE

Read/write, memory

Default: 60%

40215

214

0xD6

BACKGROUND_KEY_PAD_TIME_TO_IDLE

Read/write, memory

Default: 10 sec

40216

215

0xD7

BACKGROUND_KEY_PAD_TIME_TO_STANDBY

Read/write, memory

Default: 5 sec

40217

216

0xD8

REFRESH_TIME

Read/write, memory

Default: 2 sec

40218

217

0xD9

TIME_CONFIGURATION

Read/write, memory

Bit

Value

0

Clock displayed (default)

1

Clock not displayed

40219

218

0xDA

LCD_ICON_DISPLAY

Read/write, memory

Each bit of the register shows or hides assigned icon

Bit

Icon

0

icon_sun.jpg

1

icon_moon.jpg

2

icon_heat.jpg

3

icon_cool.jpg

4

icon_hum.jpg

5

icon_no_hum.jpg

6

icon_wifi.jpg

7

icon_settings.jpg

8

icon_eco.jpg

9

icon_rewind.jpg

10

icon_comp.jpg

40220

219

0xDB

LCD_ICON_FLASHING

Read/write, memory

Blinking of icons (bits 0-10 assigned analogically as in the LCD_ICON_DISPLAY register)

40221

220

0xDC

LCD_ICON_FLASHING_TIME

Read/write, memory

Icons blinking frequency. Default: 500 ms.

40222

221

0xDD

SUBMENU_ICON_FLASHING_TIME

Read/write, memory

Submenu icons flashing time. Default: 1000 ms.

40223

222

0xDE

ENTER_MENU_TIME

Read/write, memory

Default: 2 s

40224

223

0xDF

EXIT_EDIT_TIME

Read/write, memory

Default: 5 s

40225

224

0xE0

EXIT_MENU_TIME

Read/write, memory

Default: 10 s

40226

225

0xE1

CO2_SETPOINT_FOR_ALARM

Read/write, memory

CO2 alarm setpoint. Default: 1500 ppm.

40227

226

0xE2

CO2_HYSTERESIS_FOR_ALARM

Read/write, memory

CO2 alarm hysteresis. Default: 100 ppm.

40228

227

0xE3

SUBMENU_PROTECTION

Read/write, memory

Password protection from editing of submenus. Default: inactive.

40229

228

0xE4

SUBMENU_ICONS_FLASHING

Read/write, memory

Switching on icons blinking

30230

229

0xE5

CO2_ALARM_STATUS

Read/write, memory

CO2 current alarm status

Bit

Name

0

1

0

Alarm status

Not active

Active

1

Alarm confirmed

Not confirmed

Confirmed

30301

300

0x12C

TEMPERATURE_SENSOR

Read-only

Current temperature sensor value with offset.

30302

301

0x12D

HUMIDITY_SENSOR

Read-only

Current humidity sensor value with offset.

30303

302

0x12E

CO2_SENSOR

Read-only

Current CO2 sensor value with offset.

40304

303

0x12F

TEMPERATURE_SENSOR_OFFSET

Read/write, memory

Temperature sensor offset. Default: 0.

40305

304

0x130

HUMIDITY_SENSOR_OFFSET

Read/write, memory

Humidity sensor offset. Default: 0.

40306

305

0x131

CO2_SENSOR_OFFSET

Read/write, memory

CO2 sensor offset. Default: 0.

40307

306

0x132

TEMPERATURE_FILTER

Read/write, memory

Default: 10 s

40308

307

0x133

HUMIDITY_FILTER

Read/write, memory

Default: 10 s

40309

308

0x134

CO2_FILTER

Read/write, memory

Default: 10 s

40310-40311

309-310

0x135

TEMPERATURE_NAME (32-bit)

Read/write, memory

Displayed temperature sensor name. Default: TEMP.

40312-40313

311-312

0x137

HUMIDITY_NAME (32-bit)

Read/write, memory

Displayed humidity sensor name. Default: HUMI.

40314-40315

313-314

0x139

CO2_NAME (32-bit)

Read/write, memory

Displayed CO2 sensor name. Default: CO2.

40316

315

0x13B

TEMPERATURE_CONFIGURATION

Read/write, memory

Bit

Name

0

1

0

Active

Not active

Active (default)

4

ThirdPointActive

No decimal

Decimal (default)

40317

316

0x13C

HUMIDITY_CONFIGURATION

Read/write, memory

Bit

Name

0

1

0

Active

Not active

Active (default)

4

ThirdPointActive

No decimal

Decimal (default)

40318

317

0x13D

CO2_CONFIGURATION

Read/write, memory

Bit

Name

0

1

0

Active

Not active

Active (default)

4

ThirdPointActive

No decimal

Decimal (default)

41501

1500

0x5DC

SETPOINT

Read/write

Actual setpoint value. After reset, the DEFAULT_SETPOINT is set to the setpoint value.

41502

1501

0x5DD

EFFECTIVE_SETPOINT

Read-only

Sum of the temperature actual setpoint value and offset.

41503

1502

0x5DE

DEFAULT_SETPOINT

Read/write, memory

Default: 21oC

41504

1503

0x5DF

OFFSET_SETPOINT

Read/write, memory

Default: 0oC

41505

1504

0x5E0

SETPOINT_LOW_LIMIT

Read/write, memory

Min. available setpoint value. Default: 18oC.

41506

1505

0x5E1

SETPOINT_HIGH_LIMIT

Read/write, memory

Max. available setpoint value. Default: 24oC.

41507

1506

0x5E2

OFFSET_RANGE

Read/write, memory

Offset value limit. Default: 3oC.

41508

1507

0x5E3

SETPOINT_STEP

Read/write, memory

Setpoint step value. Default: 1oC.

41509-41510

1508=1509

0x5E4

OFFSET_NAME (32-bit)

Read/write, memory

Displayed offset name. Default: OFFS.

41511-41512

1510-1511

0x5E6

SETPOINT_NAME (32-bit)

Read/write, memory

Displayed setpoint name. Default: SETP.

41513

1512

0x5E8

SETPOINT_CONFIGURATION

Read/write, memory

Bit

Name

0

1

0

Visible

Not visible

Visible (default)

1

Editable

Not editable

Editable (default)

2

Operating mode

Changing offset

Changing setpoint (default)

3

Setpoint display

Show/change offset

Show/change Effective setpoint

4

Third point active

Not active

Active (default)

5

Fast edit mode

Not active (default)

Active

41601

1600

0x640

FAN_CURRENT_SPEED

Read/write

Value

Fan mode

Comment

0

Off (default)

Fan is off

1

Manual speed 1

Fan works in speed 1 manual mode

2

Manual speed 2

Fan works in speed 2 manual mode

3

Manual speed 3

Fan works in speed 3 manual mode

4

Auto speed 1

Fan works in speed 1 auto mode

5

Auto speed 2

Fan works in speed 2 auto mode

6

Auto speed 3

Fan works in speed 3 auto mode

41602

1601

0x641

FAN_MODE

Read/write

Value

Fan mode

0

Off

1

Manual speed 1 (default)

2

Manual speed 2

3

Manual speed 3

4

Auto

41603

1602

0x642

FAN_TYPE

Read/write, memory

Value

Fan type

Comment

0

0-10 V (default)

Fan is controlled by analog value 0-10 V

1

1-speed

1-speed fan

2

2-speed

2-speed fan

3

3-speed

3-speed fan

41604-41605

1603-1604

0x643

FAN_MODE_0_NAME (32-bit)

Read/write, memory

Displayed fan mode 0 name. Default: OFF

41606-41607

1605-1606

0x645

FAN_MODE_1_NAME (32-bit)

Read/write, memory

Displayed fan mode 1 name. Default: AUTO

41608-41609

1607-1608

0x647

FAN_MODE_2_NAME (32-bit)

Read/write, memory

Displayed fan mode 2 name. Default: _ _ _1

41610-41611

1609-1610

0x649

FAN_MODE_3_NAME (32-bit)

Read/write, memory

Displayed fan mode 3 name. Default: _ _11

41612-41613

1611-1612

0x64B

FAN_MODE_4_NAME (32-bit)

Read/write, memory

Displayed fan mode 4 name. Default: _111

41614

1613

0x64D

FAN_CONFIGURATION

Read/write, memory

Bit

Name

0

1

0

Visible

Not visible

Visible (default)

1

Editable

Not editable

Editable (default)

2

Part editable

Fully editable (default)

Auto_off_mode

5

Fast edit mode

Not active (default)

Active

6

Local mode

Not active

Active

BMS mode

Active (default)

Not active

41615

1614

0x64E

FAN_ICON_FLASHING_TIME

Read/write, memory

Time base for calculating the frequency of the fan icon rotation. Default: 500 ms.

41701

1700

0x6A4

CURRENT_OCCUPIED_STATUS

Read/write

Value (set remotely)

Occupancy status

0

Unoccupied

1

Occupied

2

Standby

3

Forced occupied

41702

1701

0x6A5

OCCUPANCY_MODE

Read/write, memory

Value

Occupancy mode

0

Unoccupied

1

Occupied

41703-41704

1702-1703

0x6A6

OCCUPANCY_MODE_0_NAME (32-bit)

Read/write, memory

Displayed unoccupied mode name. Default: UNOC

41705-41706

1704-1705

0x6A8

OCCUPANCY_MODE_1_NAME (32-bit)

Read/write, memory

Displayed occupied mode name. Default: OCC

41707

1706

0x6AA

OCCUPIED_CONFIGURATION

Read/write, memory

Bit

Name

0

1

0

Visible

Not visible

Visible (default)

1

Editable

Not editable

Editable (default)

5

Fast edit mode

Not active (default)

Active

6

Local mode

Not active

Active

BMS mode

Active (default)

Not active

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.