Occupancy Submenu Objects

Warning!

Please note that the following table contains objects for all series of the Control Point panels.

BACnet ID

Object property

Object name

Access

Description

AV48

Present value

SETTINGS_NUMERIC1:Present Value

Read/write, memory

Current value of the parameter

AV48

Description

SETTINGS_NUMERIC1:Name

Read/write, memory

User-defined name of the parameter

AV48

4206

SETTINGS_NUMERIC1:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV48

Low limit

SETTINGS_NUMERIC1:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV48

High limit

SETTINGS_NUMERIC1:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV48

4201

SETTINGS_NUMERIC1:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV48

Out of service

SETTINGS_NUMERIC1:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV48

4200

SETTINGS_NUMERIC1:Editability

Read/write, memory

Enabling editability of the parameter

AV48

4202

SETTINGS_NUMERIC1:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV48

Units

SETTINGS_NUMERIC1:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV49

Present value

SETTINGS_NUMERIC2:Present Value

Read/write, memory

Current value of the parameter

AV49

Description

SETTINGS_NUMERIC2:Name

Read/write, memory

User-defined name of the parameter

AV49

4206

SETTINGS_NUMERIC2:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV49

Low limit

SETTINGS_NUMERIC2:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV49

High limit

SETTINGS_NUMERIC2:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV49

4201

SETTINGS_NUMERIC2:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV49

Out of service

SETTINGS_NUMERIC2:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV49

4200

SETTINGS_NUMERIC2:Editability

Read/write, memory

Enabling editability of the parameter

AV49

4202

SETTINGS_NUMERIC2:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV49

Units

SETTINGS_NUMERIC2:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV50

Present value

SETTINGS_NUMERIC3:Present Value

Read/write, memory

Current value of the parameter

AV50

Description

SETTINGS_NUMERIC3:Name

Read/write, memory

User-defined name of the parameter

AV50

4206

SETTINGS_NUMERIC3:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV50

Low limit

SETTINGS_NUMERIC3:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV50

High limit

SETTINGS_NUMERIC3:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV50

4201

SETTINGS_NUMERIC3:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV50

Out of service

SETTINGS_NUMERIC3:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV50

4200

SETTINGS_NUMERIC3:Editability

Read/write, memory

Enabling editability of the parameter

AV50

4202

SETTINGS_NUMERIC3:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV50

Units

SETTINGS_NUMERIC3:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV51

Present value

SETTINGS_NUMERIC4:Present Value

Read/write, memory

Current value of the parameter

AV51

Description

SETTINGS_NUMERIC4:Name

Read/write, memory

User-defined name of the parameter

AV51

4206

SETTINGS_NUMERIC4:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV51

Low limit

SETTINGS_NUMERIC4:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV51

High limit

SETTINGS_NUMERIC4:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV51

4201

SETTINGS_NUMERIC4:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV51

Out of service

SETTINGS_NUMERIC4:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV51

4200

SETTINGS_NUMERIC4:Editability

Read/write, memory

Enabling editability of the parameter

AV51

4202

SETTINGS_NUMERIC4:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV51

Units

SETTINGS_NUMERIC4:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV52

Present value

SETTINGS_NUMERIC5:Present Value

Read/write, memory

Current value of the parameter

AV52

Description

SETTINGS_NUMERIC5:Name

Read/write, memory

User-defined name of the parameter

AV52

4206

SETTINGS_NUMERIC5:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV52

Low limit

SETTINGS_NUMERIC5:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV52

High limit

SETTINGS_NUMERIC5:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV52

4201

SETTINGS_NUMERIC5:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV52

Out of service

SETTINGS_NUMERIC5:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV52

4200

SETTINGS_NUMERIC5:Editability

Read/write, memory

Enabling editability of the parameter

AV52

4202

SETTINGS_NUMERIC5:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV52

Units

SETTINGS_NUMERIC5:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV53

Present value

SETTINGS_NUMERIC6:Present Value

Read/write, memory

Current value of the parameter

AV53

Description

SETTINGS_NUMERIC6:Name

Read/write, memory

User-defined name of the parameter

AV53

4206

SETTINGS_NUMERIC6:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV53

Low limit

SETTINGS_NUMERIC6:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV53

High limit

SETTINGS_NUMERIC6:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV53

4201

SETTINGS_NUMERIC6:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV53

Out of service

SETTINGS_NUMERIC6:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV53

4200

SETTINGS_NUMERIC6:Editability

Read/write, memory

Enabling editability of the parameter

AV53

4202

SETTINGS_NUMERIC6:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV53

Units

SETTINGS_NUMERIC6:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV54

Present value

SETTINGSNUMERIC7:Present Value

Read/write, memory

Current value of the parameter

AV54

Description

SETTINGS_NUMERIC7:Name

Read/write, memory

User-defined name of the parameter

AV54

4206

SETTINGS_NUMERIC7:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV54

Low limit

SETTINGS_NUMERIC7:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV54

High limit

SETTINGS_NUMERIC7:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV54

4201

SETTINGS_NUMERIC7:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV54

Out of service

SETTINGS_NUMERIC7:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV54

4200

SETTINGS_NUMERIC7:Editability

Read/write, memory

Enabling editability of the parameter

AV54

4202

SETTINGS_NUMERIC7:Decimal Places

Read/write, memory

Number of displayed decimal places from 0 to 3

AV54

Units

SETTINGS_NUMERIC7:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

AV55

Present value

SETTINGS_NUMERIC8:Present Value

Read/write, memory

Current value of the parameter

AV55

Description

SETTINGS_NUMERIC8:Name

Read/write, memory

User-defined name of the parameter

AV55

4206

SETTINGS_NUMERIC8:Step

Read/write, memory

Step of the parameter value change. Default: 0.

AV55

Low limit

SETTINGS_NUMERIC8:Low Limit

Read/write, memory

Minimum value of the parameter. Default: 0.

AV55

High limit

SETTINGS_NUMERIC8:High Limit

Read/write, memory

Maximum value of the parameter. Default: 0.

AV55

4201

SETTINGS_NUMERIC8:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

AV55

Out of service

SETTINGS_NUMERIC8:Visibility

Read/write, memory

Activating display of the parameter in the submenu

AV55

4200

SETTINGS_NUMERIC8:Editability

Read/write, memory

Enabling editability of the parameter

AV55

4202

SETTINGS_NUMERIC8_POINT ACTIV

Read/write, memory

Number of displayed decimal places from 0 to 3

AV55

Units

SETTINGS_NUMERIC8:Units

Read/write, memory

Supported units: ° C, ° F, Pa, Lx, ppm, m3/h, %RH, L/s, %, h

BV48

Present value

SETTINGS_BOOLEAN1:Present Value

Read/write, memory

Current value of the parameter

BV48

Description

SETTINGS_BOOLEAN1:Name

Read/write, memory

User-defined name of the parameter

BV48

4203

SETTINGS_BOOLEAN1:True Text

Read/write, memory

Text for the parameter’s true value

BV48

4204

SETTINGS_BOOLEAN1:False Text

Read/write, memory

Text for the parameter’s false value

BV48

4201

SETTINGS_BOOLEAN1:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV48

Out of

service

SETTINGS_BOOLEAN1:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV48

4200

SETTINGS_BOOLEAN1:Editability

Read/write, memory

Enabling editability of the parameter

BV49

Present value

SETTINGS_BOOLEAN2:Present Value

Read/write, memory

Current value of the parameter

BV49

Description

SETTINGS_BOOLEAN2:Name

Read/write, memory

User-defined name of the parameter

BV49

4203

SETTINGS_BOOLEAN2:True Text

Read/write, memory

Text for the parameter’s true value

BV49

4204

SETTINGS_BOOLEAN2:False Text

Read/write, memory

Text for the parameter’s false value

BV49

4201

SETTINGS_BOOLEAN2:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV49

Out of service

SETTINGS_BOOLEAN2:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV49

4200

SETTINGS_BOOLEAN2:Editability

Read/write, memory

Enabling editability of the parameter

BV50

Present value

SETTINGS_BOOLEAN3:Present Value

Read/write, memory

Current value of the parameter

BV50

Description

SETTINGS_BOOLEAN3:Name

Read/write, memory

User-defined name of the parameter

BV50

4203

SETTINGS_BOOLEAN3:True Text

Read/write, memory

Text for the parameter’s true value

BV50

4204

SETTINGS_BOOLEAN3:False Text

Read/write, memory

Text for the parameter’s false value

BV50

4201

SETTINGS_BOOLEAN3:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV50

Out of service

SETTINGS_BOOLEAN3:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV50

4200

SETTINGS_BOOLEAN3:Editability

Read/write, memory

Enabling editability of the parameter

BV51

Present value

SETTINGS_BOOLEAN4:Present Value

Read/write, memory

Current value of the parameter

BV51

Description

SETTINGS_BOOLEAN4:Name

Read/write, memory

User-defined name of the parameter

BV51

4203

SETTINGS_BOOLEAN4:True Text

Read/write, memory

Text for the parameter’s true value

BV51

4204

SETTINGS_BOOLEAN4:False Text

Read/write, memory

Text for the parameter’s false value

BV51

4201

SETTINGS_BOOLEAN4:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV51

Out of service

SETTINGS_BOOLEAN4:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV51

4200

SETTINGS_BOOLEAN4:Editability

Read/write, memory

Enabling editability of the parameter

BV52

Present value

SETTINGS_BOOLEAN5:Present Value

Read/write, memory

Current value of the parameter

BV52

Description

SETTINGS_BOOLEAN5:Name

Read/write, memory

User-defined name of the parameter

BV52

4203

SETTINGS_BOOLEAN5:True Text

Read/write, memory

Text for the parameter’s true value

BV52

4204

SETTINGS_BOOLEAN5:False Text

Read/write, memory

Text for the parameter’s false value

BV52

4201

SETTINGS_BOOLEAN5:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV52

Out of service

SETTINGS_BOOLEAN5:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV52

4200

SETTINGS_BOOLEAN5:Editability

Read/write, memory

Enabling editability of the parameter

BV53

Present value

SETTINGS_BOOLEAN6:Present Value

Read/write, memory

Current value of the parameter

BV53

Description

SETTINGS_BOOLEAN6:Name

Read/write, memory

User-defined name of the parameter

BV53

4203

SETTINGS_BOOLEAN6:True Text

Read/write, memory

Text for the parameter’s true value

BV53

4204

SETTINGS_BOOLEAN6:False Text

Read/write, memory

Text for the parameter’s false value

BV53

4201

SETTINGS_BOOLEAN6:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV53

Out of service

SETTINGS_BOOLEAN6:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV53

4200

SETTINGS_BOOLEAN6:Editability

Read/write, memory

Enabling editability of the parameter

BV54

Present value

SETTINGS_BOOLEAN7:Present Value

Read/write, memory

Current value of the parameter

BV54

Description

SETTINGS_BOOLEAN7:Name

Read/write, memory

User-defined name of the parameter

BV54

4203

SETTINGS_BOOLEAN7:True Text

Read/write, memory

Text for the parameter’s true value

BV54

4204

SETTINGS_BOOLEAN7:False Text

Read/write, memory

Text for the parameter’s false value

BV54

4201

SETTINGS_BOOLEAN7:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV54

Out of service

SETTINGS_BOOLEAN7:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV54

4200

SETTINGS_BOOLEAN7:Editability

Read/write, memory

Enabling editability of the parameter

BV55

Present value

SETTINGS_BOOLEAN8:Present Value

Read/write, memory

Current value of the parameter

BV55

Description

SETTINGS_BOOLEAN8:Name

Read/write, memory

User-defined name of the parameter

BV55

4203

SETTINGS_BOOLEAN8:True Text

Read/write, memory

Text for the parameter’s true value

BV55

4204

SETTINGS_BOOLEAN8:False Text

Read/write, memory

Text for the parameter’s false value

BV55

4201

SETTINGS_BOOLEAN8:Priority

Read/write, memory

Priority of the parameter for sequence of display in the submenu

BV55

Out of service

SETTINGS_BOOLEAN8:Visibility

Read/write, memory

Activating the display of the parameter in the submenu

BV55

4200

SETTINGS_BOOLEAN8:Editability

Read/write, memory

Enabling editability of the parameter