Submenu

Warning!

This section applies to all Control Point series: the Control Point and Control Point VAV.

A basic function of the submenu is to provide access to some application functions from the device level. Submenus are preassigned to one of 6 groups:

  • temperature submenu;

  • fan submenu;

  • light submenu;

  • blind submenu;

  • alarm submenu;

  • occupancy submenu.

If a particular submenu is activated, its icon is visible on the bottom line of the panel’s display. Fan (if applicable) and occupancy icons, in addition to the activity status, show the current mode.

Each submenu can be set editable.

All submenu parameters are written to the EEPROM memory of the panel.

Editing Parameters

The following parameters allows to set the editing mode behavior:

ENTER_MENU_TIME: allows to set a long-press duration to enter the submenu;

  • Modbus register: 40223;

  • BACnet object: AO16, property: Present value;

EXIT_MENU_TIME: allows to set the time after which the panel exits the submenu:

  • Modbus register: 40225;

  • BACnet object: AO18.

Password Protection

Access to submenus can be password-protected.

SUBMENU_PROTECTION: allows to set a password preventing unauthorized access to submenu editing:

  • TEMPERATURE: allows to set a password for the temperature submenu;

    • Modbus register: 40228, bit 0;

    • BACnet object: BO36;

  • FAN: allows to set a password for the fan submenu;

    • Modbus register: 40228, bit 1;

    • BACnet object: BO37;

  • LIGHT: allows to set a password for the light submenu;

    • Modbus register: 40228, bit 2;

    • BACnet object: BO38;

  • BLIND: allows to set a password for the blind submenu;

    • Modbus register: 40228, bit 3;

    • BACnet object: BO39;

  • ALARMS: allows to set a password for the alarms submenu;

    • Modbus register: 40228, bit 4;

    • BACnet object: BO40;

  • SETTINGS: allows to set a password for the occupancy submenu;

    • Modbus register: 40228, bit 5;

    • BACnet object: BO41.

Icons Flashing

SUBMENU_ICON_FLASHING: allows to switch on or off blinking of submenu icons when normally displayed on the panel (not in the editing mode);

  • Modbus register: 40229;

  • BACnet objects: BO42-54;

SUBMENU_FLASHING_TIME: allows to set a time which constitutes a base for calculating a frequency of submenu icons flashing. This register has a min. value of 50 ms. The default value is 1000 ms (the icons are visible for 1000 ms and hidden for 1000/4=250 ms);

  • Modbus register: 40222;

  • BACnet object: AO15.

More details: Icons