Skip to main content
Skip table of contents

Temperature Submenu Registers

Warning!

Please note that the following table contains registers for all series of the Control Point panels.

Modbus address

Decimal address

Hex address

Register name

Access

Description

40501

500

0x13F

TEMPERATURE_MENU_ACTIVE_POINTS

Read/write, memory

Number of active parameters in the submenu

40059

58

0x3A

TEMPERATURE_NUMERIC1_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40504

503

0x1F7

TEMPERATURE_NUMERIC1_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40506

505

0x1F9

TEMPERATURE_NUMERIC1_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40507

506

0x1FA

TEMPERATURE_NUMERIC1_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40508

507

0x1FB

TEMPERATURE_NUMERIC1_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40509

508

0x1FC

TEMPERATURE_NUMERIC1_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40510

509

0x1FD

TEMPERATURE_NUMERIC1_CONFIGURATION

Read/write, memory

Bit

Parameter

0

1

0

Active

Not active (default)

Active

2

First point active

No decimal place (default)

One decimal place active

3

Second point active

No decimal place (default)

Two decimal places active

4

Third point active

No decimal place (default)

Three decimal places active

6

C unit active

Not active (default)

Active

7

F unit active

Not active (default)

Active

8

Pa unit active

Not active (default)

Active

9

Lx unit active

Not active (default)

Active

10

ppm unit active

Not active (default)

Active

11

m3/h unit active

Not active (default)

Active

12

%Rh unit active

Not active (default)

Active

13

l/s unit active

Not active (default)

Active

14

% unit active

Not active (default)

Active

15

h unit active

Not active (default)

Active

40060

59

0x3B

TEMPERATURE_NUMERIC2_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40513

512

0x200

TEMPERATURE_NUMERIC2_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40515

514

0x202

TEMPERATURE_NUMERIC2_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40516

515

0x203

TEMPERATURE_NUMERIC2_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40517

516

0x204

TEMPERATURE_NUMERIC2_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40518

517

0x205

TEMPERATURE_NUMERIC2_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40519

518

0x1FD

TEMPERATURE_NUMERIC2_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40061

60

0x3C

TEMPERATURE_NUMERIC3_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40522

521

0x209

TEMPERATURE_NUMERIC3_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40524

523

0x20B

TEMPERATURE_NUMERIC3_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40525

524

0x20C

TEMPERATURE_NUMERIC3_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40526

525

0x20D

TEMPERATURE_NUMERIC3_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40527

526

0x20E

TEMPERATURE_NUMERIC3_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40528

527

0x20F

TEMPERATURE_NUMERIC3_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40062

61

0x3D

TEMPERATURE_NUMERIC4_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40531

530

0x212

TEMPERATURE_NUMERIC4_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40533

532

0x214

TEMPERATURE_NUMERIC4_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40534

533

0x215

TEMPERATURE_NUMERIC4_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40535

534

0x216

TEMPERATURE_NUMERIC4_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40536

535

0x217

TEMPERATURE_NUMERIC4_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40537

536

0x218

TEMPERATURE_NUMERIC4_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40063

62

0x3E

TEMPERATURE_NUMERIC5_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40540

539

0x21B

TEMPERATURE_NUMERIC5_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40542

541

0x21D

TEMPERATURE_NUMERIC5_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40543

542

0x21E

TEMPERATURE_NUMERIC5_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40544

543

0x21F

TEMPERATURE_NUMERIC5_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40545

544

0x220

TEMPERATURE_NUMERIC5_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40546

545

0x221

TEMPERATURE_NUMERIC5_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40064

63

0x3F

TEMPERATURE_NUMERIC6_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40549

548

0x224

TEMPERATURE_NUMERIC6_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40551

550

0x226

TEMPERATURE_NUMERIC6_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40552

551

0x227

TEMPERATURE_NUMERIC6_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40553

552

0x228

TEMPERATURE_NUMERIC6_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40554

553

0x229

TEMPERATURE_NUMERIC6_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40555

554

0x22A

TEMPERATURE_NUMERIC6_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40065

64

0x40

TEMPERATURE_NUMERIC7_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40558

557

0x22D

TEMPERATURE_NUMERIC7_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40560

559

0x22F

TEMPERATURE_NUMERIC7_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40561

560

0x230

TEMPERATURE_NUMERIC7_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40562

561

0x231

TEMPERATURE_NUMERIC7_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40563

562

0x232

TEMPERATURE_NUMERIC7_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40564

563

0x233

TEMPERATURE_NUMERIC7_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40066

65

0x41

TEMPERATURE_NUMERIC8_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40567

566

0x236

TEMPERATURE_NUMERIC8_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40569

568

0x238

TEMPERATURE_NUMERIC8_STEP

Read/write, memory

Step of the parameter value change. Default: 0.

40570

569

0x239

TEMPERATURE_NUMERIC8_LOW_LIMIT

Read/write, memory

Minimum value of the parameter. Default: 0.

40571

570

0x240

TEMPERATURE_NUMERIC8_HIGH_LIMIT

Read/write, memory

Maximum value of the parameter. Default: 0.

40572

571

0x241

TEMPERATURE_NUMERIC8_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the submenu

40573

572

0x242

TEMPERATURE_NUMERIC8_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_NUMERIC1_CONFIGURATION (40510)

40108

107

0x6B

TEMPERATURE_BOOLEAN_ALL_PRESENT_VALUE

Read/write, memory

Bit

Parameter

0

1

0

BOOLEAN1_PRESENT_VALUE

Not active (default)

Active

1

BOOLEAN2_PRESENT_VALUE

Not active (default)

Active

6

BOOLEAN7_PRESENT_VALUE

Not active (default)

Active

7

BOOLEAN8_PRESENT_VALUE

Not active (default)

Active

40122

121

0x79

TEMPERATURE_BOOLEAN1_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40576

575

0x23F

TEMPERATURE_BOOLEAN1_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40578

577

0x241

TEMPERATURE_BOOLEAN1_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40580

579

0x243

TEMPERATURE_BOOLEAN1_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40582

581

0x245

TEMPERATURE_BOOLEAN1_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40583

582

0x246

TEMPERATURE_BOOLEAN1_CONFIGURATION

Read/write, memory

Bit

Parameter

0

1

0

ACTIVE

Not active (default)

Active

1

EDITABLE

Not editable

Editable (default)

40123

122

0x7A

TEMPERATURE_BOOLEAN2_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40586

585

0x249

TEMPERATURE_BOOLEAN2_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40588

587

0x251

TEMPERATURE_BOOLEAN2_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40590

589

0x253

TEMPERATURE_BOOLEAN2_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40592

591

0x255

TEMPERATURE_BOOLEAN2_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40593

592

0x256

TEMPERATURE_BOOLEAN2_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40124

123

0x7B

TEMPERATURE_BOOLEAN3_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40596

595

0x253

TEMPERATURE_BOOLEAN3_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40598

597

0x255

TEMPERATURE_BOOLEAN3_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40600

599

0x257

TEMPERATURE_BOOLEAN3_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40602

601

0x259

TEMPERATURE_BOOLEAN3_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40603

602

0x25A

TEMPERATURE_BOOLEAN3_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40125

124

0x7C

TEMPERATURE_BOOLEAN4_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40606

605

0x25D

TEMPERATURE_BOOLEAN4_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40608

607

0x25F

TEMPERATURE_BOOLEAN4_TRUE_TEXT (32–bits)

Read/write, memory

Text for the parameter’s true value

40610

609

0x261

TEMPERATURE_BOOLEAN4_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40612

611

0x263

TEMPERATURE_BOOLEAN4_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40613

612

0x264

TEMPERATURE_BOOLEAN4_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40126

125

0x7D

TEMPERATURE_BOOLEAN5_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40616

615

0x267

TEMPERATURE_BOOLEAN5_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40618

617

0x269

TEMPERATURE_BOOLEAN5_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40620

619

0x271

TEMPERATURE_BOOLEAN5_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40622

621

0x273

TEMPERATURE_BOOLEAN5_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40623

622

0x274

TEMPERATURE_BOOLEAN5_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40127

126

0x7E

TEMPERATURE_BOOLEAN6 PRESENT_VALUE_

Read/write, memory

Current value of the parameter

40626

625

0x271

TEMPERATURE_BOOLEAN6_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40628

627

0x273

TEMPERATURE_BOOLEAN6_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40630

629

0x275

TEMPERATURE_BOOLEAN6_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40632

631

0x277

TEMPERATURE_BOOLEAN6_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40633

632

0x278

TEMPERATURE_BOOLEAN6_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40128

127

0x7F

TEMPERATURE_BOOLEAN7_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40636

635

0x27B

TEMPERATURE_BOOLEAN7_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40638

637

0x27D

TEMPERATURE_BOOLEAN7_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40640

639

0x27F

TEMPERATURE_BOOLEAN7_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40642

641

0x281

TEMPERATURE_BOOLEAN7_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40643

642

0x282

TEMPERATURE_BOOLEAN7_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

40129

128

0x80

TEMPERATURE_BOOLEAN8_PRESENT_VALUE

Read/write, memory

Current value of the parameter

40646

645

0x285

TEMPERATURE_BOOLEAN8_NAME (32-bit)

Read/write, memory

User-defined name of the parameter

40648

647

0x287

TEMPERATURE_BOOLEAN8_TRUE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s true value

40650

649

0x289

TEMPERATURE_BOOLEAN8_FALSE_TEXT (32-bit)

Read/write, memory

Text for the parameter’s false value

40652

651

0x28B

TEMPERATURE_BOOLEAN8_PRIORITY

Read/write, memory

Priority of the parameter for sequence of display in the main menu

40653

652

0x28C

TEMPERATURE_BOOLEAN8_CONFIGURATION

Read/write, memory

See the table in TEMPERATURE_BOOLEAN1_CONFIGURATION (40583)

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.