Warning!

This section applies to all Control Point series: the Control Point and Control Point VAV.

Clock-related parameters allow to configure the clock display on the panel.

TIME_CONFIGURATION: allows to activate the clock’s display on the panel. If true, the clock is visible on the main menu (it is first displayed when the panel receives a first message with a correct time value after powering up or a restart). By default, the clock is visible;

  • Modbus register: 40218, bit 0;

  • BACnet object: BO13;

HOURS: allows to set an hour value in a time displaying mode. 12-hour/24-hour mode is determined by the TIME_FORMAT in DEVICE_CONFIGURATION (the default mode is 24-hour). If the clock is set to a 12-hour format, icons AM and PM are displayed automatically. A semicolon, which separates hours and minutes sections, flashes with 1 Hz frequency;

  • Modbus register: 40203;

  • BACnet object: AO1;

MINUTES: allows to set a minute value in a time displaying mode;

  • Modbus register: 40204;

  • BACnet object: AO2.

Note

In order to display clock on the panel, it is required to set a null value in the following parameters:

TEMPERATURE_NAME

  • Modbus registers: 40310, 40311 (each for two letters of the name);

  • BACnet object: AI 4, property: Description Property;

HUMIDITY_NAME

  • Modbus registers: 40312, 40313 (each for two letters of the name);

  • BACnet object: AI 5, property: Description Property;

CO2_NAME

  • Modbus registers: 40314, 40315 (each for two letters of the name);

  • BACnet object: AI 6, property: Description Property.