CO2 Sensor (Optional)
Warning!
This section applies to all Control Point series: the Control Point and Control Point VAV.
A CO2 sensor is an optional equipment in the Control Point panel. It is marked with a letter C in a product code, for example: CP-HC (means the panel is equipped with a temperature, humidity, and CO2 sensors). The CO2 sensor's configuration data is available in the following parameters or in the iSMA Configurator:
CO2_SENSOR: indicates a current CO2 value with offset;
Modbus register: 30303;
BACnet object: AI6, property: Present Value;
CO2_OFFSET: allows to set an offset value for the CO2 sensor (correction to the CO2 sensor's value). The default value is 0;
Modbus register: 40306;
BACnet object: AI6, property: 4205;
CO2_FILTER: allows to set a filtering value for the CO2 sensor (expressed in seconds). The default value is 10 seconds;
Modbus register: 40309;
BACnet object: AI6, property: 4003;
CO2_NAME: allows to set a unique 4-letter name for a CO2 sensor;
Modbus registers: 40314, 40315 (each for two letters of the name);
BACnet object: AI 6, property: Description Property.
Configuration of CO2 Sensor on Display
CO2_CONFIGURATION: allows to activate or deactivate the CO2 sensor:
ACTIVE: activates or deactivates the sensor;
Modbus register: 40318, bit 0;
BACnet object: AO6, property: 4200;
Bit | Name | 0 | 1 |
---|---|---|---|
0 | ACTIVE | Inactive | Active (default) |