Skip to main content
Skip table of contents

Sensors Parameters

Warning!

This section applies to all Touch Point series: the Control Point and Control Point VAV series.

The Control Point panel supports 3 types of sensors, all of which are equipped with configurable software filter and user offset. Values measured by sensors can be shown on the device’s display or read through communication protocols.

Information about available sensors can be read from the following register or in the iSMA Configurator:

SENSORS: contains an information about the sensors built-in the panel according to the table below (if the bit is active, it means the sensor is built-in in the panel):

Bit

Built-in Sensors

0

Humidity sensor

1

CO2 sensor

2

Temperature sensor

Sensors built-in in the panel
  • Modbus register: 30029;

  • BACnet object: MSI1, property: Present Value.