Skip to main content
Skip table of contents

Humidity Sensor (Optional)

Warning!

This section applies to all Control Point series: the Control Point and Control Point VAV.

A humidity sensor is an optional equipment in the Control Point panel. It is marked with a letter H in a product code, for example: CP-H (means the panel is equipped with a temperature sensor and humidity sensor). The humidity sensor's configuration data is available in the following parameters or in the iSMA Configurator:

HUMIDITY_SENSOR: indicates a current humidity value with offset;

  • Modbus register: 30302;

  • BACnet object: AI5, property: Present Value;

HUMIDITY_SENSOR_OFFSET: allows to set an offset value for the humidity sensor (correction to the humidity sensor's value). The default value is 0;

  • Modbus register: 40305;

  • BACnet object: AI5, property: 4205;

HUMIDITY_FILTER: allows to set a filtering value for the humidity sensor (expressed in seconds). The default value is 10 seconds.

  • Modbus register: 40308;

  • BACnet object: AI5, property: 4205;

HUMIDITY_NAME: allows to set a unique 4-letter name for a humidity sensor;

  • Modbus registers: 40312, 40313 (each for two letters of the name);

  • BACnet object: AI 5, property: Description Property.

Configuration of Humidity Sensor on Display

HUMIDITY_CONFIGURATION: allows to configure the humidity sensor with two bits:

  • ACTIVE: activates or deactivates the sensor;

    • Modbus register: 40317, bit 0;

    • BACnet object: AO5, property: 4200;

  • THIRD_POINT_ACTIVE: enables or disables decimal values in the sensor;

    • Modbus register: 40317, bit 4;

    • BACnet object: AO5, property: 4202;

Bit

Name

0

1

0

ACTIVE

Inactive

Active (default)

4

THIRD_POINT_ACTIVE

No decimal

Decimal (default)

Configuration of humidity sensor