Highlights
HVAC Mode Dependencies
The HVAC Mode settings in the AirflowSetpointControl folder affects a lot of factors in the VAV application. The below tables offers a basic summary.
HVAC Mode | Effective setpoint | Space temp. control loop | DAT | Airflow setpoint | Fan control | Reheater control | Perimeter control |
|---|---|---|---|---|---|---|---|
Auto | Heating demand active: effective setpoint equals the heating setpoint Cooling demand active: effective setpoint equals the cooling setpoint | Cooling CL active | Heating CL active:
Cooling CL active:
| Occupied and bypass:
Standby (StandbyAirFlowSetpoint) and unoccupied (UnoccAirFlowSetpoint): the same setpoint for heating and cooling | Parallel fan: working on heating demand Series fan: working if occupied or standby (if allowed) | According to the heating demand | According to the heating demand |
Heat | Occupied: OccHeatTempSetpoint Bypass: OccHeatTempSetpoint Standby: StandbyHeatTempSetpoint Unoccupied: UnoccHeatTempSetpoint | Heating CL active | Heating CL active | Occupied and bypass: linear function between the MaxOccHeatAirFlowSetpoint and MinOccHeatAirFlowSetpoint values Standby (StandbyAirFlowSetpoint): setpoint the same as the auto mode Unoccupied (UnoccAirFlowSetpoint) and | Parallel fan: working on heating demand Series fan: working only on heating demand if occupied or standby (if allowed) | According to the heating demand | According to the heating demand |
Cool | Occupied: OccCoolTempSetpoint Bypass: OccCoolTempSetpoint Standby: StandbyCoolTempSetpoint Unoccupied: UnoccCoolTempSetpoint | Cooling CL active | Cooling CL active | Occupied and bypass: linear function between the MaxOccCoolAirFlowSetpoint and MinOccCoolAirFlowSetpoint values Standby (StandbyAirFlowSetpoint): setpoint the same as the auto mode Unoccupied (UnoccAirFlowSetpoint): setpoint the same as the auto mode | Parallel fan: inactive Series fan: working only on cooling demand if occupied or standby (if allowed) | Off | Off |
MorningWarmUp | Occupied: OccHeatTempSetpoint Bypass: OccHeatTempSetpoint Standby: StandbyHeatTempSetpoint Unoccupied: UnoccHeatTempSetpoint | Heating CL active | Heating CL active | MaxOccHeatAirFlowSetpoint | Parallel fan: if the WarmUpParallelFan variable is set to true, the parallel fan is active in this mode Series fan: ventilator set to the maximum speed | According to the heating demand (if WarmUpHeater is true) | According to the heating demand (if WarmUpHeater is true) |
PreCool | Occupied: OccCoolTempSetpoint Bypass: OccCoolTempSetpoint Standby: StandbyCoolTempSetpoint Unoccupied: UnoccCoolTempSetpoint | Cooling CL active | Cooling CL active | MaxOccCoolAirFlowSetpoint | Parallel fan: inactive Series fan: ventilator set to the maximum speed | Off | Off |
Night | Occupied: OccCoolTempSetpoint Bypass: OccCoolTempSetpoint Standby: StandbyCoolTempSetpoint Unoccupied: UnoccCoolTempSetpoint | Cooling CL active | Cooling CL active | MaxOccCoolAirFlowSetpoint | Parallel fan: inactive Series fan: ventilator set to the maximum speed | Off | Off |
Fire | Occupied: OccCoolTempSetpoint Bypass: OccCoolTempSetpoint Standby: StandbyCoolTempSetpoint Unoccupied: UnoccCoolTempSetpoint | Disabled | Disabled | MaxOccCoolAirFlowSetpoint | Disabled | Off | Off |
Off | Occupied: OccCoolTempSetpoint Bypass: OccCoolTempSetpoint Standby: StandbyCoolTempSetpoint Unoccupied: UnoccCoolTempSetpoint | Disabled | Disabled | 0 | Off | Off | Off |