HVAC Mode Dependencies

The HVAC Mode settings in the AirflowSetpointControl folder affects a lot of factors in the VAV application. The below tables offers a basic summary.

HVAC Mode

Effective setpoint

Space temp. control loop

DAT
control loop

Airflow setpoint

Fan control

Reheater control

Perimeter control

Auto

Heating demand active: effective setpoint equals the heating setpoint

Cooling demand active: effective setpoint equals the cooling setpoint

Cooling CL active

Heating CL active:

  • DAT > HotAirTempSetpoint

  • the above temp. is maintained > ChangeoverDelay

Cooling CL active:

  • DAT < HotAirTempSetpoint

  • the above temp. is maintained > ChangeoverDelay

Occupied and bypass:

  • heating: linear function between the MaxOccHeatAirFlowSetpoint and MinOccHeatAirFlowSetpoint

  • cooling: linear function between theMaxOccCoolAirFlowSetpoint and MinOccCoolAirFlowSetpoint

Standby (StandbyAirFlowSetpoint) and unoccupied (UnoccAirFlowSetpoint): the same setpoint for heating and cooling

Parallel fan: working on heating demand

Series fan: working if occupied or standby (if allowed)

According to the heating demand

According to the heating demand

Heat

Occupied: OccHeatTempSetpoint

Bypass: OccHeatTempSetpoint

Standby: StandbyHeatTempSetpoint

Unoccupied: UnoccHeatTempSetpoint

Heating CL active

Heating CL active

Occupied and bypass: linear function between the MaxOccHeatAirFlowSetpoint and MinOccHeatAirFlowSetpoint values

Standby (StandbyAirFlowSetpoint): setpoint the same as the auto mode

Unoccupied (UnoccAirFlowSetpoint) and

Parallel fan: working on heating demand

Series fan: working only on heating demand if occupied or standby (if allowed)

According to the heating demand

According to the heating demand

Cool

Occupied: OccCoolTempSetpoint

Bypass: OccCoolTempSetpoint

Standby: StandbyCoolTempSetpoint

Unoccupied: UnoccCoolTempSetpoint

Cooling CL active

Cooling CL active

Occupied and bypass: linear function between the MaxOccCoolAirFlowSetpoint and MinOccCoolAirFlowSetpoint values

Standby (StandbyAirFlowSetpoint): setpoint the same as the auto mode

Unoccupied (UnoccAirFlowSetpoint): setpoint the same as the auto mode

Parallel fan: inactive

Series fan: working only on cooling demand if occupied or standby (if allowed)

Off

Off

MorningWarmUp

Occupied: OccHeatTempSetpoint

Bypass: OccHeatTempSetpoint

Standby: StandbyHeatTempSetpoint

Unoccupied: UnoccHeatTempSetpoint

Heating CL active

Heating CL active

MaxOccHeatAirFlowSetpoint

Parallel fan: if the WarmUpParallelFan variable is set to true, the parallel fan is active in this mode

Series fan: ventilator set to the maximum speed

According to the heating demand (if WarmUpHeater is true)

According to the heating demand (if WarmUpHeater is true)

PreCool

Occupied: OccCoolTempSetpoint

Bypass: OccCoolTempSetpoint

Standby: StandbyCoolTempSetpoint

Unoccupied: UnoccCoolTempSetpoint

Cooling CL active

Cooling CL active

MaxOccCoolAirFlowSetpoint

Parallel fan: inactive

Series fan: ventilator set to the maximum speed

Off

Off

Night
Purge

Occupied: OccCoolTempSetpoint

Bypass: OccCoolTempSetpoint

Standby: StandbyCoolTempSetpoint

Unoccupied: UnoccCoolTempSetpoint

Cooling CL active

Cooling CL active

MaxOccCoolAirFlowSetpoint

Parallel fan: inactive

Series fan: ventilator set to the maximum speed

Off

Off

Fire

Occupied: OccCoolTempSetpoint

Bypass: OccCoolTempSetpoint

Standby: StandbyCoolTempSetpoint

Unoccupied: UnoccCoolTempSetpoint

Disabled

Disabled

MaxOccCoolAirFlowSetpoint

Disabled

Off

Off

Off

Occupied: OccCoolTempSetpoint

Bypass: OccCoolTempSetpoint

Standby: StandbyCoolTempSetpoint

Unoccupied: UnoccCoolTempSetpoint

Disabled

Disabled

0

Off

Off

Off