In the Control Point panel’s VAV submenu dedicated to the VAV application, it is possible to configure the following parameters:

DEVT: allows to choose a device type between VAV and VVT;

  • DeviceType:

    • Modbus register: 00107;

    • BACnet object: BV6, property: Present Value;

Register/object value

Value

0/false

VAV

1/true

VVT

REHT: allows to set a reheater type;

  • ReheaterType:

    • Modbus register: 40273;

    • BACnet object: MSV12, property: Present Value;

Register/object value

Value

1

None

2

Time proportional (PWM)

3

Staged

4

Float

PERT: allows to set a perimeter type;

  • PerimeterType:

    • Modbus register: 40274;

    • BACnet object: MSV13, property: Present Value;

Register/object value

Value

1

None

2

Time proportional (PWM)

3

Digital

FANT: allows to set a fan type;

  • FanType:

    • Modbus register: 40272;

    • BACnet object: MSV11, property: Present Value;

Register/object value

Value

1

None

2

Series

3

Parallel

SPCS: allows to set a source for temperature readings;

  • TemperatureInputSelector:

    • Modbus register: 40284;

    • BACnet object: MSV23, property: Present Value;

Register/object value

Value

1

Panel

2

Input

3

Network

SPCT: allows to set a space temperature type on the universal input 2;

  • U2SpaceTempType:

    • Modbus register: 40283;

    • BACnet object: MSV22, property: Present Value;

DIST: allows to set a discharge temperature type on the universal input 1;

  • U1DischargeTempType:

    • Modbus register: 40282;

    • BACnet object: MSV21, property: Present Value;

Register/object value

Value

1

Voltage measurement

2

Current

3

Resistance input

4

10K3A1 NTC

5

10K4A1 NTC

6

10K NTC Carel

7

20K6A1 NTC

8

2,2K3A1 NTC

9

3K3A1 NTC

10

30K6A1 NTC

11

SIE1

12

TAC1

13

SAT1

14

PT1000

15

NI1000

16

NI1000 21C

17

NI1000 LG F

18

10K Type2 NTC F

19

10K Type3 NTC F

20

20K NTC F

21

3K NTC F

22

PT1000 F

23

NI1000 32F

24

NI1000 70F

OFFS: allows to set a source for setpoint offset settings;

  • SetpointOffsetSelector:

    • Modbus register: 40285;

    • BACnet object: MSV24, property: Present Value;

CO2S: allows to set a source for CO2 readings;

  • CO2InputSelector:

    • Modbus register: 40286;

    • BACnet object: MSV25, property: Present Value;

Register/object value

Value

1

Panel

2

Input

3

Network

CO2R: allows to set a range for CO2 alarm settings;

  • CO2SensorRange:

    • Modbus register: 40239;

    • BACnet object: AV38, property: Present Value;

Register/object value

Value

Min.

0

Max.

10000

HPRI: allows to select a priority order for the heat source;

  • HeaterPriority:

    • Modbus register: 40275;

    • BACnet object: MSV14, property: Present Value;

Register/object value

Value

1

Reheater

2

Perimeter

3

Simultaneous

DUHT: allows to enable a possibility to use one or two heat sources;

  • DualHeat:

    • Modbus register: 00109;

    • BACnet object: BV8, property: Present Value;

Register/object value

Value

0/false

No

1/true

Yes

OCCT: allows to select an occupancy contact type;

  • PresenceSensorInvert:

    • Modbus register: 00105;

    • BACnet object: BV4, property: Present Value;

WNDT: allows to select a window contact type;

  • WindowContactInvert:

    • Modbus register: 00106;

    • BACnet object: BV5, property: Present Value;

DAMP: allows to set a damper actuator’s direction to open to clockwise or counterclockwise;

  • DamperDirection:

    • Modbus register: 00110;

    • BACnet object: BV9, property: Present Value.

Register/object value

Value

0/false

Clockwise

1/true

Counterclockwise