Flow Settings

In the Control Point panel’s VAV submenu dedicated to airflow settings, it is possible to configure the following parameters:

MAXC: allows to set a maximum airflow value for cooling;

  • MaxOccCoolAirflowSetpoint:

    • Modbus register: 40212;

    • BACnet object: AV11, property: Present Value;

MINC: allows to set a minimum airflow value for cooling;

  • MinOccCoolAirflowSetpoint:

    • Modbus register: 40213;

    • BACnet object: AV12, property: Present Value;

MAXH: allows to set a maximum airflow for heating;

  • MaxOccHeatAirflowSetpoint:

    • Modbus register: 40214;

    • BACnet object: AV13, property: Present Value;

MINH: allows to set a minimum airflow for heating;

  • MinOccHeatAirflowSetpoint:

    • Modbus register: 40215;

    • BACnet object: AV14, property: Present Value;

STBY: allows to set a minimum airflow in a standby state;

  • StandbyAirflowSetpoint:

    • Modbus register: 40216;

    • BACnet object: AV15, property: Present Value;

UNOC: allows to set a minimum airflow in an unoccupied state;

  • UnoccAirflowSetpoint:

    • Modbus register: 40217;

    • BACnet object: AV16, property: Present Value;

FANS: allows to set a minimum airflow value for a fan to start operating;

  • StartupFanAirflowSetpoint:

    • Modbus register: 40218;

    • BACnet object: AV17, property: Present Value;

KFAC: allows to set a K-factor value according to the type of device for use in the airflow calculations;

  • K-Factor:

    • Modbus register: 40289;

    • BACnet object: AV61, property: Present Value.