Flow Settings
In the Control Point panel’s VAV submenu dedicated to airflow settings, it is possible to configure the following parameters:
MAXC: allows to set a maximum airflow value for cooling;
MaxOccCoolAirflowSetpoint:
Modbus register: 40212;
BACnet object: AV11, property: Present Value;
MINC: allows to set a minimum airflow value for cooling;
MinOccCoolAirflowSetpoint:
Modbus register: 40213;
BACnet object: AV12, property: Present Value;
MAXH: allows to set a maximum airflow for heating;
MaxOccHeatAirflowSetpoint:
Modbus register: 40214;
BACnet object: AV13, property: Present Value;
MINH: allows to set a minimum airflow for heating;
MinOccHeatAirflowSetpoint:
Modbus register: 40215;
BACnet object: AV14, property: Present Value;
STBY: allows to set a minimum airflow in a standby state;
StandbyAirflowSetpoint:
Modbus register: 40216;
BACnet object: AV15, property: Present Value;
UNOC: allows to set a minimum airflow in an unoccupied state;
UnoccAirflowSetpoint:
Modbus register: 40217;
BACnet object: AV16, property: Present Value;
FANS: allows to set a minimum airflow value for a fan to start operating;
StartupFanAirflowSetpoint:
Modbus register: 40218;
BACnet object: AV17, property: Present Value;
KFAC: allows to set a K-factor value according to the type of device for use in the airflow calculations;
K-Factor:
Modbus register: 40289;
BACnet object: AV61, property: Present Value.