List of Variables in Application
The below table lists all Data Points used in the VAV application as variables.
The application employs 116 licensed Data Points.
Name | DP | Def. | Units | Exposed | BACnet | Modbus dec. addr. | Conf. | Description |
|---|---|---|---|---|---|---|---|---|
OccupancyCalculator | ||||||||
OccupancyStatus | MDP | Unocc. | N/a | True | MSI2 | 22 | No | Current occupancy status: 1: occupied 2: unoccupied 3: bypass 4: standby |
OccupancyMode | MDP | Unocc. | N/a | True | MSV2 | 262 | No | Allows to set room the occupancy mode from the BMS system: 1: occupied 2: unoccupied 3: bypass 4: standby |
PanelOccupancyStatus | MDP | Unocc. | N/a | True | MSV3 | 700 | No | Current room occupancy status dedicated to Control Point room panel 1: unoccupied 2: occupied 3: standby 4: bypass |
PanelOccupancyMode | MDP | Unocc. | N/a | True | MSV4 | 701 | No | Status of set room occupancy mode from Control Point room panel 1: unoccupied 2: occupied |
PresenceSensor | BDP | N/a | True/ | True | BI0 | 301 | No | Actual presence sensor state from the I1 input |
WindowContact | BDP | N/a | True/ | True | BI1 | 303 | No | Actual window contact state from the I2 input |
BypassTimeOverride | ADP | 120 | s | True | AV34 | 234 | Yes | Time required to maintain the bypass occupancy status (after expiration it returns to the previous status) |
StandbyTimeOverride | ADP | 15 | s | True | AV35 | 235 | Yes | Time required to change the occupancy status to standby (after motion detection disappears) |
AutoOccMode | BDP | Disabled | True/ | True | BV0 | 100 | Yes | Automatically changes occupancy to occupied when increased airflow is detected: false (disabled), true (enabled) |
PanelOccupancyReset | MDP | Unocc. | N/a | True | MSV5 | 702 | No | Resetting the room occupancy mode from occupied to unoccupied in the Control Point room panel 1: unoccupied 2: occupied |
PresenceSensorInvert | BDP | Invert | True/ | True | BV4 | 104 | Yes | Allows to invert the I1 input signal if required: false (normal), true (invert) |
WindowContactInvert | BDP | Normal | True/ | True | BV5 | 105 | Yes | Allows to invert the I2 input signal if required: false (normal), true (invert) |
TemperatureSelector | ||||||||
SpaceTemperature | ADP | N/a | °C/°F | True | AI1 | 4 | No | Calculated space temperature |
NetTemperature | ADP | -327 | °C/°F | True | AV10 | 210 | No | Temperature sensor value from the network |
U2SpaceTemperature | ADP | N/a | °C/°F | True | AI3 | 3 | No | Actual temperature sensor value from the local U2 input |
PanelTemperature | ADP | N/a | °C/°F | True | AI4 | 300 | No | Actual temperature sensor value from the room panel |
DischargeTemperature | ADP | N/a | °C/°F | True | AI13 | 13 | No | Calculated discharge temperature |
NetDuctInTemp | ADP | -327 | °C/°F | True | AV18 | 218 | No | Discharge temperature sensor value from the network |
U1DischTemperature | ADP | N/a | °C/°F | True | AI16 | 16 | No | Actual discharge temperature sensor value comes from the U1 input |
U2SpaceTempType | MDP | 10K3A1 NTC | °C/°F | True | MSV22 | 282 | Yes | Allows to select the space temperature type: 1: Voltage measurement 2: Current 3: Resistance input 4: 10K3A1 NTC 5: 10K4A1 NTC 6: 10K NTC Carel 7: 20K6A1 NTC 8: 2,2K3A1 NTC 9: 3K3A1 NTC 10: 30K6A1 NTC 11: SIE1 12: TAC1 13: SAT1 14: PT1000 15: NI1000 16: NI1000 21C 17: NI1000 LG F 18: 10K Type2 NTC F 19: 10K Type3 NTC F 20: 20K NTC F 21: 3K NTC F 22: PT1000 F 23: NI1000 32F 24: NI1000 70F |
U1DischargeTempType | MDP | 10K3A1 NTC | °C/°F | True | MSV21 | 281 | Yes | Allows to select the discharge temperature type: 1: Voltage measurement 2: Current 3: Resistance input 4: 10K3A1 NTC 5: 10K4A1 NTC 6: 10K NTC Carel 7: 20K6A1 NTC 8: 2,2K3A1 NTC 9: 3K3A1 NTC 10: 30K6A1 NTC 11: SIE1 12: TAC1 13: SAT1 14: PT1000 15: NI1000 16: NI1000 21C 17: NI1000 LG F 18: 10K Type2 NTC F 19: 10K Type3 NTC F 20: 20K NTC F 21: 3K NTC F 22: PT1000 F 23: NI1000 32F 24: NI1000 70F Connected to CP MSV12 |
TemperatureInputSelector | MDP | Panel | N/a | True | MSV23 | 283 | Yes | Allows to choose the temperature source for control logic: 1: panel 2: input 3: network |
OffsetCalculator | ||||||||
OffsetTempSetpoint | ADP | N/a | °C/°F | True | AV58 | 503 | No | Temperature offset for setpoint from the room panel |
SetpointOffsetRange | ADP | 6 | N/a | True | AV37 | 237 | Yes | Sets the setpoint offset range to be changed by the user (e.g., a value of 5 means a range from -5 to +5), (min = 0, max = 10) |
U3SetpointOffset | ADP | N/a | °C/°F | True | AI17 | 17 | No | Actual setpoint offset value (calculated from resistance) from the U3 input |
PanelSetpointDisplay | BDP | N/a | True/ | True | BO56 | 156 | Yes | Allows to select which value to be displayed during the offset editing according to the set Panel Setpoint Mode false (offset), true (setpoint) |
NetOffsetSetpoint | ADP | 0 | °C/°F | AV41 | 241 | No | Offset temperature setpoint value from the network | |
SetpointOffsetSelector | MDP | Panel | N/a | MSV24 | 284 | Yes | Allows to choose the setpoint offset source for control logic: 1: panel 2: input 3: network | |
TemperatureSetpointSelector | ||||||||
PanelSetpointMode | BDP | N/a | True/ | True | BO55 | 155 | Yes | Sets the temperature setpoint mode in the Control Point room panel - directly or as an offset false (offset), true (setpoint) |
OccCoolTempSetpoint | ADP | 23°C/74°F | °C/°F | True | AV0 | 200 | Yes | Temperature setpoint for cooling in the occupied state |
OccHeatTempSetpoint | ADP | 21°C/70°F | °C/°F | True | AV1 | 201 | Yes | Temperature setpoint for heating in the occupied state |
StandbyCoolTempSetpoint | ADP | 25°C/77°F | °C/°F | True | AV2 | 202 | Yes | Temperature setpoint for cooling in the standby state |
StandbyHeatTempSetpoint | ADP | 19°C/67°F | °C/°F | True | AV3 | 203 | Yes | Temperature setpoint for heating in the standby state |
UnoccCoolTempSetpoint | ADP | 28°C/80°F | °C/°F | True | AV4 | 204 | Yes | Temperature setpoint for cooling in the unoccupied state |
UnoccHeatTempSetpoint | ADP | 16°C/64°F | °C/°F | True | AV5 | 205 | Yes | Temperature setpoint for heating in the unoccupied state |
EffectiveTempSetpoint | ADP | N/a | °C/°F | True | AI9 | 9 | No | Calculated effective temperature setpoint based on occupancy status and heating or cooling temperature setpoints (depending on demand) |
CentralTempSetpoint | ADP | N/a | °C/°F | True | AI10 | 10 | No | Calculated Central Temperature Setpoint based on setpoints and occupancy status |
PanelTempSetpoint | ADP | N/a | °C/°F | True | AV56 | 501 | No | Temperature setpoint from the room panel |
MaxDischTempSetpoint | ADP | 32°C/90°F | °C/°F | True | AV7 | 207 | Yes | High limit of discharge temperature supplied to the room |
ActDischTempSetpoint | ADP | N/a | °C/°F | True | AI14 | 14 | No | Calculated discharge temperature setpoint based on the effective temperature setpoint and heating demand for high-limiting discharge temperature |
MinDischTempSetpoint | ADP | 13°C/55°F | °C/°F | True | AV8 | 208 | Yes | Low limit of discharge temperature supplied to the room |
CO2Selector | ||||||||
PanelCO2 | ADP | N/a | ppm | True | AI6 | 302 | No | Actual CO2 sensor value from the room panel |
NetCO2 | ADP | N/a | ppm | True | AV40 | 240 | No | CO2 sensor value comes from the network |
U4CO2Sensor | ADP | N/a | ppm | True | AI8 | 8 | No | Actual CO2 sensor value from the local U4 input |
SpaceCO2 | ADP | N/a | ppm | True | AI5 | 5 | Yes | Calculated space CO2 |
U4CO2SensorRange | ADP | 2000 | N/a | True | AV38 | 238 | Yes | Sets the range of the CO2 sensor used (min = 0, max = 10000) |
CO2InputSelector | MDP | Panel | N/a | MSV25 | 285 | Yes | Allows to select the CO2 source for control logic: 1: panel 2: input 3: network | |
AirflowCalculator | ||||||||
K-Factor | ADP | 1000 | N/a | True | AV61 | 288 | Yes | Sets the K-Factor (the flow rate at a differential pressure of 1inWC/1Pa on the measuring cross) for the given VAV model (min = 0) |
DifferentialPressure | ADP | N/a | Pa/WC | True | AI15 | 15 | No | Actual differential pressure sensor-measured value from the built-in pressure input |
ActualAirFlow | ADP | N/a | L/s/cfm | True | AI11 | 11 | No | Actual calculated airflow based on the K-Factor value and differential pressure measure |
AirflowCalibration | ADP | 0 | L/s/cfm | True | AV66 | 293 | No | Allows to enter the airflow value measured by the hood for calibration |
CalculatedKFactor | ADP | N/a | N/a | False | AV62 | 289 | No | Calculated K-Factor value (meaning the flow rate at a differential pressure of 1 inWC/1 Pa on the measuring cross) based on the entered measured airflow (using the hood) and the measured differential pressure from the built-in PI input |
PressureZeroing | BDP | No | True/ | True | BV13 | 113 | No | Allows to perform zeroing action on the built-in PI pressure transducer if there is a non-zero value in the absence of airflow. Important: perform in the absence of airflow through the pressure transducer ports False (no), true (zeroing) |
AirflowSetpointCalculator | ||||||||
EffectiveAirFlowSetpoint | ADP | N/a | L/s/cfm | True | AI12 | 12 | No | Calculated effective airflow setpoint based on the occupancy status and heating or cooling airflow setpoints |
HVACMode | MDP | Auto | N/a | True | MSV1 | 261 | No | Allows to set the operating mode for the VAV device: 1: Auto 2: Heat 3: Morning WarmUp 4: Cool 5: Night Purge 6: PreCool 7: Off (depressurize) 8: Fire (pressurize) |
MaxOccCoolAirflowSetpoint | ADP | 400 | L/s/cfm | True | AV11 | 211 | Yes | Maximum airflow setpoint for cooling in the occupied state (min = 0) |
MaxOccHeatAirflowSetpoint | ADP | 200 | L/s/cfm | True | AV13 | 213 | Yes | Minimum airflow setpoint for cooling in the occupied state (min = 0) |
MinOccCoolAirflowSetpoint | ADP | 100 | L/s/cfm | True | AV12 | 212 | Yes | Maximum airflow setpoint for heating in the occupied state (min = 0) |
MinOccHeatAirflowSetpoint | ADP | 100 | L/s/cfm | True | AV14 | 214 | Yes | Minimum airflow setpoint for heating in the occupied state (min = 0) |
StandbyAirflowSetpoint | ADP | 50 | L/s/cfm | True | AV15 | 215 | Yes | Airflow setpoint in the standby state (min = 0) |
UnoccAirflowSetpoint | ADP | 25 | L/s/cfm | True | AV16 | 216 | Yes | Airflow setpoint in the unoccupied state (min = 0) |
StartupFanAirflowSetpoint | ADP | 35 | L/s/cfm | True | AV17 | 217 | Yes | Airflow setpoint for a fan startup only (min = 0) |
UserSetAirflow | ADP | 0 | L/s/cfm | True | AV65 | 292 | No | User-set airflow setpoint (after selecting the User Position mode in the Damper Command variable) (min = 0) |
Heat&CoolLoops | ||||||||
HotAirTempSetpoint | ADP | 26°C/78°F | °C/°F | True | AV9 | 209 | Yes | Discharge temperature setpoint for detecting warm air to change the heating/cooling mode |
PanelHeating | BDP | N/a | True/ | True | BO16 | 116 | No | Heating mode status to be displayed as an icon on the Control Point room panel false (no heating), true (heating) |
PanelCooling | BDP | N/a | True/ | True | BO17 | 117 | No | Cooling mode status to be displayed as an icon on the Control Point room panel false (no cooling), true (cooling) |
ChangeoverDelay | ADP | 2 | min | True | AV36 | 236 | No | Delay time for changing the heating/cooling operating mode |
Airflow/DAT/CO2Loops | ||||||||
SpaceCO2Setpoint | ADP | 1000 | ppm | True | AV6 | 206 | Yes | CO2 setpoint for the room (regardless of the occupancy status) |
AHUOutdoorDamper | ADP | N/a | % | True | AO4 | 254 | No | Required opening level of the fresh air damper in the AHU resulting from the current CO2 level in the room (network signal to the AHU control) |
DamperControl | ||||||||
DeviceType | BDP | VAV | True/ | True | BV6 | 106 | Yes | Allows to choose VAV device control type from airflow demand (VAV also known as pressure independent) or from cooling/heating demand (VVT also known as pressure dependent): false (VAV), true (VVT) |
MaxDamperPosition | ADP | 100 | % | True | AV21 | 221 | Yes | Maximum damper open position limit (min = 0, max = 100) |
MinDamperPosition | ADP | 0 | % | True | AV22 | 222 | Yes | Minimum damper open position limit (min = 0, max = 100) |
UserSetPosition | ADP | 0 | % | True | AV64 | 291 | No | User-set damper opening level (after selecting the User Position mode in the Damper Command variable) (min = 0, max = 100) |
DualHeat | BDP | No | True/ | True | BV8 | 108 | Yes | Allows to enable dual heating mode with repeater/perimeter and damper (no effect without damper): false (no), true (yes) |
HeatDamperPriority | BDP | Secondary | True/ | True | BV11 | 111 | Yes | Allows to set the priority of the damper heating operation when working in the active DualHeat mode: false (secondary), true (primary) |
DamperPosition | ADP | N/a | % | True | AO0 | 250 | No | Actual damper opening level coming from the Rotary Actuator component (Position Feedback signal) |
DamperResponse | ADP | 2 | % | True | AV26 | 226 | Yes | Sets the value of how much the control signal must change to perform the next damper movement |
DamperDriveTime | ADP | 90 | s | True | AV25 | 225 | Yes | Time required to reach full damper open position (from 0% to 100%) (min = 0) |
DirectionActuator | BDP | Clockwise | True/ | True | BV9 | 109 | Yes | Sets the damper opening direction: false (CW), true (CCW) |
DamperControl | ADP | 0 | % | True | AV67 | 294 | No | Damper opening level control resulting from the application |
DamperCommand | MDP | None | N/a | True | MSV7 | 267 | No | Allows to set different damper command modes for calibration, balancing, or testing: 1: Auto/none (null) 2: Max flow 3: Min flow 4: User flow 5: User position 6: Full open 7: Full close 8: Calibrate |
FanControl | ||||||||
FanCommand | MDP | Auto | N/a | True | MSV8 | 268 | No | Allows to set different fan command modes for testing 1: Auto/none (null) 2: Max speed 3: Min speed 4: Stop |
FanControlMode | BDP | Digital | True/ | True | BV10 | 110 | Yes | Allows to select the fan control mode: false (digital), true (analog) |
MaxFanSpeed | ADP | 100 | % | True | AV23 | 223 | Yes | Maximum fan speed level limit (min = 0, max = 100) |
MinFanSpeed | ADP | 20 | % | True | AV24 | 224 | Yes | Minimum fan speed level limit (min = 0, max = 100) |
WarmUpParallelFan | BDP | Disabled | True/ | True | BV2 | 102 | Yes | Allows to use the parallel fan also in the Morning WarmUp mode (in the HVAC Mode variable): false (disabled), true (enabled) |
StandbySeriesFan | BDP | Disabled | True/ | True | BV3 | 103 | Yes | Allows to use the series fan also in standby occupancy: false (disabled), true (enabled) |
FanDelayOff | ADP | 30 | s | True | AV39 | 239 | Yes | Delay time for switching off the fan |
PanelFanStatus | MDP | Off | N/a | True | MSV0 | 600 | No | Fan status to be displayed as an icon on the Control Point room panel: 1: off 5: speed 1 (auto) 6: speed 2 (auto) 7: speed 3 (auto) |
FanStatus | BDP | Off | True/ | True | BO1 | 121 | No | Fan digital control status (if configured as digital) from the application: false (off), true (on) |
FanSpeed | ADP | N/a | % | True | AO2 | 252 | No | Fan speed level control resulting from the application |
ReheaterControl | ||||||||
LoadShedding | ADP | 0 | % | True | AV20 | 220 | No | Load-shedding level required from the network (min = 0, max = 100) |
ReheaterCommand | MDP | Auto | N/a | True | MSV9 | 269 | No | Allows to set different reheater command modes for testing 1: Auto/none (null) 2: Full open 3: Full close |
HeaterPriority | MDP | Reheater | N/a | True | MSV14 | 274 | Yes | Possibility to select heating priority for heating sources: 1: reheater 2: perimeter 3: simultaneous |
WarmUpHeater | BDP | Disabled | True/ | True | BV1 | 101 | Yes | Allows to use the reheater also in the Morning WarmUp mode (in the HVAC Mode variable): false (disabled), true (enabled) |
ReheaterControl | ADP | N/a | % | True | AO1 | 251 | No | Reheater valve opening level control resulting from the application |
TimePropReheaterPeriod | ADP | 60 | s | True | AV32 | 232 | Yes | Time required for a PWM valve for a full cycle time of a reheater |
FloatReheaterValveDriveTime | ADP | 120 | s | True | AV30 | 230 | Yes | Time required for a PWM valve for a full cycle time of a perimeter |
ReheaterStatus | MDP | Off | N/a | True | MSO0 | 290 | No | Reheater staged control status (if configured as digital or staged) from application: 1: off 2: stage 1 on 3: stage 2 on |
PerimeterControl | ||||||||
PerimeterCommand | MDP | Auto | N/a | True | MSV10 | 270 | No | Allows to set different perimeter command modes for testing 1: Auto/none (null) 2: Full open 3: Full close |
PerimeterControl | ADP | N/a | % | True | AO3 | 253 | No | Perimeter valve opening level control resulting from the application |
PerimeterStatus | BDP | Off | True/ | True | BO0 | 120 | No | Perimeter digital control status (if configured as digital) from the application: false (off), true (on) |
TimePropPerimeterPeriod | ADP | 60 | s | True | AV33 | 233 | Yes | Time required for a PWM valve for a full cycle time of a perimeter |
OutsideTemperatureControl | ||||||||
MaxOatReheater | ADP | 32°C/90°F | °C/°F | True | AV28 | 228 | Yes | Maximum outside air temperature limit that allows the use of a reheater |
MaxOatPerimeter | ADP | 18°C/65°F | °C/°F | True | AV29 | 229 | Yes | Maximum outside air temperature limit that allows the use of a perimeter |
NetOutdoorTemp | ADP | -327 | °C/°F | True | AV19 | 219 | No | Outside air temperature sensor value from the network |
DeviceConfiguration | ||||||||
DeviceConfigurationSource | BDP | BACnet | True/ | True | BV12 | 112 | Yes | Allows to choose to set a source of the device application configuration: false (BACcnet), true (DIP switch) |
PerimeterType | MDP | None | N/a | True | MSV13 | 273 | Yes | Allows to set the perimeter type: 1: none 2: TimeProp 3: digital |
ReheaterType | MDP | None | N/a | True | MSV12 | 272 | Yes | Allows to set the reheater type: 1: none 2: TimeProp 3: staged 4: float |
FanType | MDP | None | N/a | True | MSV11 | 271 | Yes | Allows to set the fan type: 1: none 2: series 3: parallel |
Units | BDP | Metric | True/ | True | BO2 | 122 | Yes | Allows to change the unit in the application provided that the BACnet configuration is allowed in the Device Configuration Source variable: false (metric), true (imperial) |
UpTime | ADP | N/a | s | True | AI0 | 0 | No | Device’s up time |
AppVersion | ADP | 1.0 | N/a | True | AI100 | 102 | No | Current application version |
TriacOutputsConfig | ||||||||
TO4 | ADP | 0 | False | 996 | 996 | No | ||
TO3 | ADP | 0 | False | 997 | 997 | No | ||
TO2 | ADP | 0 | False | 998 | 998 | No | ||
TO1 | ADP | 0 | False | 999 | 999 | No | ||