List of Variables in Application

The below table lists all Data Points used in the VAV application as variables.

The application employs 116 licensed Data Points.

Name

DP
type

Def.
Out
value

Units

Exposed
on
BACnet/
Modbus

BACnet
ID

Modbus dec. addr.

Conf.
data
ext.

Description

OccupancyCalculator

OccupancyStatus

MDP

Unocc.

N/a

True

MSI2

22

No

Current occupancy status:

1: occupied

2: unoccupied

3: bypass

4: standby

OccupancyMode

MDP

Unocc.

N/a

True

MSV2

262

No

Allows to set room the occupancy mode from the BMS system:

1: occupied

2: unoccupied

3: bypass

4: standby

PanelOccupancyStatus

MDP

Unocc.

N/a

True

MSV3

700

No

Current room occupancy status dedicated to Control Point room panel

1: unoccupied

2: occupied

3: standby

4: bypass

PanelOccupancyMode

MDP

Unocc.

N/a

True

MSV4

701

No

Status of set room occupancy mode from Control Point room panel

1: unoccupied

2: occupied

PresenceSensor

BDP

N/a
(derived from the app)

True/
false

True

BI0

301

No

Actual presence sensor state from the I1 input

WindowContact

BDP

N/a
(derived from the app)

True/
false

True

BI1

303

No

Actual window contact state from the I2 input

BypassTimeOverride

ADP

120

s

True

AV34

234

Yes

Time required to maintain the bypass occupancy status (after expiration it returns to the previous status)

StandbyTimeOverride

ADP

15

s

True

AV35

235

Yes

Time required to change the occupancy status to standby (after motion detection disappears)

AutoOccMode

BDP

Disabled

True/
false

True

BV0

100

Yes

Automatically changes occupancy to occupied when increased airflow is detected:

false (disabled), true (enabled)

PanelOccupancyReset

MDP

Unocc.

N/a

True

MSV5

702

No

Resetting the room occupancy mode from occupied to unoccupied in the Control Point room panel

1: unoccupied

2: occupied

PresenceSensorInvert

BDP

Invert

True/
false

True

BV4

104

Yes

Allows to invert the I1 input signal if required:

false (normal), true (invert)

WindowContactInvert

BDP

Normal

True/
false

True

BV5

105

Yes

Allows to invert the I2 input signal if required:

false (normal), true (invert)

TemperatureSelector

SpaceTemperature

ADP

N/a
(derived from the app)

°C/°F

True

AI1

4

No

Calculated space temperature

NetTemperature

ADP

-327

°C/°F

True

AV10

210

No

Temperature sensor value from the network

U2SpaceTemperature

ADP

N/a
(derived from the app)

°C/°F

True

AI3

3

No

Actual temperature sensor value from the local U2 input

PanelTemperature

ADP

N/a
(derived from the app)

°C/°F

True

AI4

300

No

Actual temperature sensor value from the room panel

DischargeTemperature

ADP

N/a
(derived from the app)

°C/°F

True

AI13

13

No

Calculated discharge temperature

NetDuctInTemp

ADP

-327

°C/°F

True

AV18

218

No

Discharge temperature sensor value from the network

U1DischTemperature

ADP

N/a
(derived from the app)

°C/°F

True

AI16

16

No

Actual discharge temperature sensor value comes from the U1 input

U2SpaceTempType

MDP

10K3A1 NTC

°C/°F

True

MSV22

282

Yes

Allows to select the space temperature type:

1: Voltage measurement

2: Current

3: Resistance input

4: 10K3A1 NTC

5: 10K4A1 NTC

6: 10K NTC Carel

7: 20K6A1 NTC

8: 2,2K3A1 NTC

9: 3K3A1 NTC

10: 30K6A1 NTC

11: SIE1

12: TAC1

13: SAT1

14: PT1000

15: NI1000

16: NI1000 21C

17: NI1000 LG F

18: 10K Type2 NTC F

19: 10K Type3 NTC F

20: 20K NTC F

21: 3K NTC F

22: PT1000 F

23: NI1000 32F

24: NI1000 70F

U1DischargeTempType

MDP

10K3A1 NTC

°C/°F

True

MSV21

281

Yes

Allows to select the discharge temperature type:

1: Voltage measurement

2: Current

3: Resistance input

4: 10K3A1 NTC

5: 10K4A1 NTC

6: 10K NTC Carel

7: 20K6A1 NTC

8: 2,2K3A1 NTC

9: 3K3A1 NTC

10: 30K6A1 NTC

11: SIE1

12: TAC1

13: SAT1

14: PT1000

15: NI1000

16: NI1000 21C

17: NI1000 LG F

18: 10K Type2 NTC F

19: 10K Type3 NTC F

20: 20K NTC F

21: 3K NTC F

22: PT1000 F

23: NI1000 32F

24: NI1000 70F

Connected to CP MSV12

TemperatureInputSelector

MDP

Panel

N/a

True

MSV23

283

Yes

Allows to choose the temperature source for control logic:

1: panel

2: input

3: network

OffsetCalculator

OffsetTempSetpoint

ADP

N/a
(derived from the app)

°C/°F

True

AV58

503

No

Temperature offset for setpoint from the room panel

SetpointOffsetRange

ADP

6

N/a

True

AV37

237

Yes

Sets the setpoint offset range to be changed by the user (e.g., a value of 5 means a range from -5 to +5), (min = 0, max = 10)

U3SetpointOffset

ADP

N/a
(derived from the app)

°C/°F

True

AI17

17

No

Actual setpoint offset value (calculated from resistance) from the U3 input

PanelSetpointDisplay

BDP

N/a
(derived from the app)

True/
false

True

BO56

156

Yes

Allows to select which value to be displayed during the offset editing according to the set Panel Setpoint Mode

false (offset), true (setpoint)

NetOffsetSetpoint

ADP

0

°C/°F

AV41

241

No

Offset temperature setpoint value from the network

SetpointOffsetSelector

MDP

Panel

N/a

MSV24

284

Yes

Allows to choose the setpoint offset source for control logic:

1: panel

2: input

3: network

TemperatureSetpointSelector

PanelSetpointMode

BDP

N/a
(derived from the app)

True/
false

True

BO55

155

Yes

Sets the temperature setpoint mode in the Control Point room panel - directly or as an offset

false (offset), true (setpoint)

OccCoolTempSetpoint

ADP

23°C/74°F

°C/°F

True

AV0

200

Yes

Temperature setpoint for cooling in the occupied state

OccHeatTempSetpoint

ADP

21°C/70°F

°C/°F

True

AV1

201

Yes

Temperature setpoint for heating in the occupied state

StandbyCoolTempSetpoint

ADP

25°C/77°F

°C/°F

True

AV2

202

Yes

Temperature setpoint for cooling in the standby state

StandbyHeatTempSetpoint

ADP

19°C/67°F

°C/°F

True

AV3

203

Yes

Temperature setpoint for heating in the standby state

UnoccCoolTempSetpoint

ADP

28°C/80°F

°C/°F

True

AV4

204

Yes

Temperature setpoint for cooling in the unoccupied state

UnoccHeatTempSetpoint

ADP

16°C/64°F

°C/°F

True

AV5

205

Yes

Temperature setpoint for heating in the unoccupied state

EffectiveTempSetpoint

ADP

N/a
(derived from the app)

°C/°F

True

AI9

9

No

Calculated effective temperature setpoint based on occupancy status and heating or cooling temperature setpoints (depending on demand)

CentralTempSetpoint

ADP

N/a
(derived from the app)

°C/°F

True

AI10

10

No

Calculated Central Temperature Setpoint based on setpoints and occupancy status

PanelTempSetpoint

ADP

N/a
(derived from the app)

°C/°F

True

AV56

501

No

Temperature setpoint from the room panel

MaxDischTempSetpoint

ADP

32°C/90°F

°C/°F

True

AV7

207

Yes

High limit of discharge temperature supplied to the room

ActDischTempSetpoint

ADP

N/a
(derived from the app)

°C/°F

True

AI14

14

No

Calculated discharge temperature setpoint based on the effective temperature setpoint and heating demand for high-limiting discharge temperature

MinDischTempSetpoint

ADP

13°C/55°F

°C/°F

True

AV8

208

Yes

Low limit of discharge temperature supplied to the room

CO2Selector

PanelCO2

ADP

N/a
(derived from the app)

ppm

True

AI6

302

No

Actual CO2 sensor value from the room panel

NetCO2

ADP

N/a
(derived from the app)

ppm

True

AV40

240

No

CO2 sensor value comes from the network

U4CO2Sensor

ADP

N/a
(derived from the app)

ppm

True

AI8

8

No

Actual CO2 sensor value from the local U4 input

SpaceCO2

ADP

N/a
(derived from the app)

ppm

True

AI5

5

Yes

Calculated space CO2

U4CO2SensorRange

ADP

2000

N/a

True

AV38

238

Yes

Sets the range of the CO2 sensor used (min = 0, max = 10000)

CO2InputSelector

MDP

Panel

N/a

MSV25

285

Yes

Allows to select the CO2 source for control logic:

1: panel

2: input

3: network

AirflowCalculator

K-Factor

ADP

1000

N/a

True

AV61

288

Yes

Sets the K-Factor (the flow rate at a differential pressure of 1inWC/1Pa on the measuring cross) for the given VAV model (min = 0)

DifferentialPressure

ADP

N/a
(derived from the app)

Pa/WC

True

AI15

15

No

Actual differential pressure sensor-measured value from the built-in pressure input

ActualAirFlow

ADP

N/a
(derived from the app)

L/s/cfm

True

AI11

11

No

Actual calculated airflow based on the K-Factor value and differential pressure measure

AirflowCalibration

ADP

0

L/s/cfm

True

AV66

293

No

Allows to enter the airflow value measured by the hood for calibration

CalculatedKFactor

ADP

N/a
(derived from the app)

N/a

False

AV62

289

No

Calculated K-Factor value (meaning the flow rate at a differential pressure of 1 inWC/1 Pa on the measuring cross) based on the entered measured airflow (using the hood) and the measured differential pressure from the built-in PI input

PressureZeroing

BDP

No

True/
false

True

BV13

113

No

Allows to perform zeroing action on the built-in PI pressure transducer if there is a non-zero value in the absence of airflow.

Important: perform in the absence of airflow through the pressure transducer ports

False (no), true (zeroing)

AirflowSetpointCalculator

EffectiveAirFlowSetpoint

ADP

N/a
(derived from the app)

L/s/cfm

True

AI12

12

No

Calculated effective airflow setpoint based on the occupancy status and heating or cooling airflow setpoints

HVACMode

MDP

Auto

N/a

True

MSV1

261

No

Allows to set the operating mode for the VAV device:

1: Auto

2: Heat

3: Morning WarmUp

4: Cool

5: Night Purge

6: PreCool

7: Off (depressurize)

8: Fire (pressurize)

MaxOccCoolAirflowSetpoint

ADP

400

L/s/cfm

True

AV11

211

Yes

Maximum airflow setpoint for cooling in the occupied state (min = 0)

MaxOccHeatAirflowSetpoint

ADP

200

L/s/cfm

True

AV13

213

Yes

Minimum airflow setpoint for cooling in the occupied state (min = 0)

MinOccCoolAirflowSetpoint

ADP

100

L/s/cfm

True

AV12

212

Yes

Maximum airflow setpoint for heating in the occupied state (min = 0)

MinOccHeatAirflowSetpoint

ADP

100

L/s/cfm

True

AV14

214

Yes

Minimum airflow setpoint for heating in the occupied state (min = 0)

StandbyAirflowSetpoint

ADP

50

L/s/cfm

True

AV15

215

Yes

Airflow setpoint in the standby state (min = 0)

UnoccAirflowSetpoint

ADP

25

L/s/cfm

True

AV16

216

Yes

Airflow setpoint in the unoccupied state (min = 0)

StartupFanAirflowSetpoint

ADP

35

L/s/cfm

True

AV17

217

Yes

Airflow setpoint for a fan startup only (min = 0)

UserSetAirflow

ADP

0

L/s/cfm

True

AV65

292

No

User-set airflow setpoint (after selecting the User Position mode in the Damper Command variable) (min = 0)

Heat&CoolLoops

HotAirTempSetpoint

ADP

26°C/78°F

°C/°F

True

AV9

209

Yes

Discharge temperature setpoint for detecting warm air to change the heating/cooling mode

PanelHeating

BDP

N/a
(derived from the app)

True/
false

True

BO16

116

No

Heating mode status to be displayed as an icon on the Control Point room panel

false (no heating), true (heating)

PanelCooling

BDP

N/a
(derived from the app)

True/
false

True

BO17

117

No

Cooling mode status to be displayed as an icon on the Control Point room panel

false (no cooling), true (cooling)

ChangeoverDelay

ADP

2

min

True

AV36

236

No

Delay time for changing the heating/cooling operating mode

Airflow/DAT/CO2Loops

SpaceCO2Setpoint

ADP

1000

ppm

True

AV6

206

Yes

CO2 setpoint for the room (regardless of the occupancy status)

AHUOutdoorDamper

ADP

N/a
(derived from the app)

%

True

AO4

254

No

Required opening level of the fresh air damper in the AHU resulting from the current CO2 level in the room (network signal to the AHU control)

DamperControl

DeviceType

BDP

VAV

True/
false

True

BV6

106

Yes

Allows to choose VAV device control type from airflow demand (VAV also known as pressure independent) or from cooling/heating demand (VVT also known as pressure dependent):

false (VAV), true (VVT)

MaxDamperPosition

ADP

100

%

True

AV21

221

Yes

Maximum damper open position limit (min = 0, max = 100)

MinDamperPosition

ADP

0

%

True

AV22

222

Yes

Minimum damper open position limit (min = 0, max = 100)

UserSetPosition

ADP

0

%

True

AV64

291

No

User-set damper opening level (after selecting the User Position mode in the Damper Command variable) (min = 0, max = 100)

DualHeat

BDP

No

True/
false

True

BV8

108

Yes

Allows to enable dual heating mode with repeater/perimeter and damper (no effect without damper):

false (no), true (yes)

HeatDamperPriority

BDP

Secondary

True/
false

True

BV11

111

Yes

Allows to set the priority of the damper heating operation when working in the active DualHeat mode:

false (secondary), true (primary)

DamperPosition

ADP

N/a
(derived from the app)

%

True

AO0

250

No

Actual damper opening level coming from the Rotary Actuator component (Position Feedback signal)

DamperResponse

ADP

2

%

True

AV26

226

Yes

Sets the value of how much the control signal must change to perform the next damper movement

DamperDriveTime

ADP

90

s

True

AV25

225

Yes

Time required to reach full damper open position (from 0% to 100%) (min = 0)

DirectionActuator

BDP

Clockwise

True/
false

True

BV9

109

Yes

Sets the damper opening direction:

false (CW), true (CCW)

DamperControl

ADP

0

%

True

AV67

294

No

Damper opening level control resulting from the application

DamperCommand

MDP

None

N/a

True

MSV7

267

No

Allows to set different damper command modes for calibration, balancing, or testing:

1: Auto/none (null)

2: Max flow

3: Min flow

4: User flow

5: User position

6: Full open

7: Full close

8: Calibrate

FanControl

FanCommand

MDP

Auto

N/a

True

MSV8

268

No

Allows to set different fan command modes for testing

1: Auto/none (null)

2: Max speed

3: Min speed

4: Stop

FanControlMode

BDP

Digital

True/
false

True

BV10

110

Yes

Allows to select the fan control mode:

false (digital), true (analog)

MaxFanSpeed

ADP

100

%

True

AV23

223

Yes

Maximum fan speed level limit (min = 0, max = 100)

MinFanSpeed

ADP

20

%

True

AV24

224

Yes

Minimum fan speed level limit (min = 0, max = 100)

WarmUpParallelFan

BDP

Disabled

True/
false

True

BV2

102

Yes

Allows to use the parallel fan also in the Morning WarmUp mode (in the HVAC Mode variable):

false (disabled), true (enabled)

StandbySeriesFan

BDP

Disabled

True/
false

True

BV3

103

Yes

Allows to use the series fan also in standby occupancy:

false (disabled), true (enabled)

FanDelayOff

ADP

30

s

True

AV39

239

Yes

Delay time for switching off the fan

PanelFanStatus

MDP

Off

N/a

True

MSV0

600

No

Fan status to be displayed as an icon on the Control Point room panel:

1: off

5: speed 1 (auto)

6: speed 2 (auto)

7: speed 3 (auto)

FanStatus

BDP

Off

True/
false

True

BO1

121

No

Fan digital control status (if configured as digital) from the application:

false (off), true (on)

FanSpeed

ADP

N/a
(derived from the app)

%

True

AO2

252

No

Fan speed level control resulting from the application

ReheaterControl

LoadShedding

ADP

0

%

True

AV20

220

No

Load-shedding level required from the network (min = 0, max = 100)

ReheaterCommand

MDP

Auto

N/a

True

MSV9

269

No

Allows to set different reheater command modes for testing

1: Auto/none (null)

2: Full open

3: Full close

HeaterPriority

MDP

Reheater

N/a

True

MSV14

274

Yes

Possibility to select heating priority for heating sources:

1: reheater

2: perimeter

3: simultaneous

WarmUpHeater

BDP

Disabled

True/
false

True

BV1

101

Yes

Allows to use the reheater also in the Morning WarmUp mode (in the HVAC Mode variable):

false (disabled), true (enabled)

ReheaterControl

ADP

N/a
(derived from the app)

%

True

AO1

251

No

Reheater valve opening level control resulting from the application

TimePropReheaterPeriod

ADP

60

s

True

AV32

232

Yes

Time required for a PWM valve for a full cycle time of a reheater

FloatReheaterValveDriveTime

ADP

120

s

True

AV30

230

Yes

Time required for a PWM valve for a full cycle time of a perimeter

ReheaterStatus

MDP

Off

N/a

True

MSO0

290

No

Reheater staged control status (if configured as digital or staged) from application:

1: off

2: stage 1 on

3: stage 2 on

PerimeterControl

PerimeterCommand

MDP

Auto

N/a

True

MSV10

270

No

Allows to set different perimeter command modes for testing

1: Auto/none (null)

2: Full open

3: Full close

PerimeterControl

ADP

N/a
(derived from the app)

%

True

AO3

253

No

Perimeter valve opening level control resulting from the application

PerimeterStatus

BDP

Off

True/
false

True

BO0

120

No

Perimeter digital control status (if configured as digital) from the application:

false (off), true (on)

TimePropPerimeterPeriod

ADP

60

s

True

AV33

233

Yes

Time required for a PWM valve for a full cycle time of a perimeter

OutsideTemperatureControl

MaxOatReheater

ADP

32°C/90°F

°C/°F

True

AV28

228

Yes

Maximum outside air temperature limit that allows the use of a reheater

MaxOatPerimeter

ADP

18°C/65°F

°C/°F

True

AV29

229

Yes

Maximum outside air temperature limit that allows the use of a perimeter

NetOutdoorTemp

ADP

-327

°C/°F

True

AV19

219

No

Outside air temperature sensor value from the network

DeviceConfiguration

DeviceConfigurationSource

BDP

BACnet

True/
false

True

BV12

112

Yes

Allows to choose to set a source of the device application configuration:

false (BACcnet), true (DIP switch)

PerimeterType

MDP

None

N/a

True

MSV13

273

Yes

Allows to set the perimeter type:

1: none

2: TimeProp

3: digital

ReheaterType

MDP

None

N/a

True

MSV12

272

Yes

Allows to set the reheater type:

1: none

2: TimeProp

3: staged

4: float

FanType

MDP

None

N/a

True

MSV11

271

Yes

Allows to set the fan type:

1: none

2: series

3: parallel

Units

BDP

Metric

True/
false

True

BO2

122

Yes

Allows to change the unit in the application provided that the BACnet configuration is allowed in the Device Configuration Source variable:

false (metric), true (imperial)

UpTime

ADP

N/a
(derived from the app)

s

True

AI0

0

No

Device’s up time

AppVersion

ADP

1.0

N/a

True

AI100

102

No

Current application version

TriacOutputsConfig

TO4

ADP

0

False

996

996

No

TO3

ADP

0

False

997

997

No

TO2

ADP

0

False

998

998

No

TO1

ADP

0

False

999

999

No