BACnet Objects/Modbus Registers

Note

Please note that if the switch 1 on the S3 DIP switch is on, than configuration of the fan, reheater, and perimeter type from any other source is blocked (BACnet/Modbus), as well as any changes made to the referring parameters (for example, Heater Priority) will not be written to the device.

BACnet ID

Modbus address (dec)

Object/register name

Units

Access

Default value

Description

Configuration

AV37

40238 (237)

SetpointOffsetRange

N/a

Read/write

6

Sets the setpoint offset range to be changed by the user (e.g., a value of 5 means a range from -5 to +5), (min = 0, max = 10)

Connected to CP AV59

AV38

40239 (238)

CO2SensorRange

N/a

Read/write

2000

Sets the range of the CO2 sensor used (min = 0, max = 10000)

Connected to CP AO37

BV4

00105 (104)

PresenceSensorInvert

True/false

Read/write

False

Allows to invert the I1 input signal if required:

false (normal), true (invert)

Connected to CP BO66

BV5

00106 (105)

WindowContactInvert

True/false

Read/write

False

Allows to invert the I2 input signal if required:

false (normal), true (invert)

Connected to CP BO67

BV6

00107 (106)

DeviceType

True/false

Read/write

False

Allows to choose VAV device control type from airflow demand (VAV also known as pressure independent) or from cooling/heating demand (VVT also known as pressure dependent):

false (VAV), true (VVT)

Connected to CP BO68

BV8

00109 (108)

DualHeat

True/false

Read/write

False

Allows to enable dual heating mode with repeater/perimeter and damper (no effect without damper):

false (no), true (yes)

Connected to CP BO69

BO2

00123 (122)

Units

True/false

Read/write

False

Allows to change the unit in the application provided that the BACnet configuration is allowed in the Device Configuration Source variable:

false (metric), true (imperial)

Connected to CP BO2

MSV11

40272 (271)

FanType

N/a

Read/write

None

Allows to set the fan type:

1: none

2: series

3: parallel

Connected to CP MSV9

MSV12

40273 (272)

ReheaterType

N/a

Read/write

None

Allows to set the reheater type:

1: none

2: TimeProp

3: staged

4: float

Connected to CP MSV10

MSV13

40274 (273)

PerimeterType

N/a

Read/write

None

Allows to set the perimeter type:

1: none

2: TimeProp

3: digital

Connected to CP MSV11

MSV14

40275 (274)

HeaterPriority

N/a

Read/write

Reheater

Possibility to select heating priority for heating sources:

1: reheater

2: perimeter

3: simultaneous

Connected to CP MSV14

MSV21

40282 (281)

U1DischargeTempType

N/a

Read/write

Allows to select the discharge temperature type:

1: Voltage measurement

2: Current

3: Resistance input

4: 10K3A1 NTC

5: 10K4A1 NTC

6: 10K NTC Carel

7: 20K6A1 NTC

8: 2,2K3A1 NTC

9: 3K3A1 NTC

10: 30K6A1 NTC

11: SIE1

12: TAC1

13: SAT1

14: PT1000

15: NI1000

16: NI1000 21C

17: NI1000 LG F

18: 10K Type2 NTC F

19: 10K Type3 NTC F

20: 20K NTC F

21: 3K NTC F

22: PT1000 F

23: NI1000 32F

24: NI1000 70F

Connected to CP MSV12

MSV22

40283 (282)

U2SpaceTempType

N/a

Read/write

Allows to select the space temperature type:

1: Voltage measurement

2: Current

3: Resistance input

4: 10K3A1 NTC

5: 10K4A1 NTC

6: 10K NTC Carel

7: 20K6A1 NTC

8: 2,2K3A1 NTC

9: 3K3A1 NTC

10: 30K6A1 NTC

11: SIE1

12: TAC1

13: SAT1

14: PT1000

15: NI1000

16: NI1000 21C

17: NI1000 LG F

18: 10K Type2 NTC F

19: 10K Type3 NTC F

20: 20K NTC F

21: 3K NTC F

22: PT1000 F

23: NI1000 32F

24: NI1000 70F

Connected to CP MSV13

Flow Settings

AV11

40212 (211)

MaxOccCoolAirflowSetpoint

L/s / cfm

Read/write

400/800

Maximum airflow setpoint for cooling in the occupied state (min = 0)

Connected to CP AO29

AV12

40213 (212)

MinOccCoolAirflowSetpoint

L/s / cfm

Read/write

100/200

Minimum airflow setpoint for cooling in the occupied state (min = 0)

Connected to CP AO30

AV13

40214 (213)

MaxOccHeatAirflowSetpoint

L/s / cfm

Read/write

200/400

Maximum airflow setpoint for heating in the occupied state (min = 0)

Connected to CP AO31

AV14

40215 (214)

MinOccHeatAirflowSetpoint

L/s / cfm

Read/write

100/200

Minimum airflow setpoint for heating in the occupied state (min = 0)

Connected to CP AO32

AV15

40216 (215)

StandbyAirFlowSetpoint

L/s / cfm

Read/write

50/100

Airflow setpoint in the standby state (min = 0)

Connected to CP AO33

AV16

40217 (216)

UnoccAirFlowSetpoint

L/s / cfm

Read/write

25/50

Airflow setpoint in the unoccupied state (min = 0)

Connected to CP AO34

AV17

40218 (217)

StartupFanAirflowSetpoint

L/s / cfm

Read/write

35/75

Airflow setpoint for a fan startup only (min = 0)

Connected to CP AO35

BV9

00110 (109)

DamperDirection

True/false

Read/write

False

Sets the damper opening direction:

false (CW), true (CCW)

Connected to CP BO65

AV0

40201 (200)

OccCoolTempSetpoint

°C/°F

Read/write

23/74

Temperature setpoint for cooling in the occupied state

AV1

40202 (201)

OccHeatTempSetpoint

°C/°F

Read/write

21/70

Temperature setpoint for heating in the occupied state

AV2

40203 (202)

StandbyCoolTempSetpoint

°C/°F

Read/write

25/77

Temperature setpoint for cooling in the standby state

AV3

40204 (203)

StandbyHeatTempSetpoint

°C/°F

Read/write

19/67

Temperature setpoint for heating in the standby state

AV4

40205 (204)

UnoccCoolTempSetpoint

°C/°F

Read/write

28/80

Temperature setpoint for cooling in the unoccupied state

AV5

40206 (205)

UnoccHeatTempSetpoint

°C/°F

Read/write

16/64

Temperature setpoint for heating in the unoccupied state

AV6

40207 (206)

SpaceCO2Setpoint

ppm

Read/write

1000

CO2 setpoint for the room (regardless of the occupancy status)

AV9

40210 (209)

HotAirTempSetpoint

°C/°F

Read/write

26/78

Discharge temperature setpoint for detecting warm air to change the heating/cooling mode

Balancing

BV13

00114 (113)

PressureZeroing

True/false

Read/write

False

Allows to perform zeroing action on the built-in PI pressure transducer if there is a non-zero value in the absence of airflow.

Important: perform in the absence of airflow through the pressure transducer ports

False (no), true (zeroing)

Connected to CP BO64

AI11

30012 (11)

ActualAirFlow

L/s / cfm

Read-only

N/a

Actual calculated airflow based on the K-Factor value and differential pressure measure

Connected to CP AO25

AV61

40289 (288)

K-Factor

N/a

Read/write

1000

Sets the K-Factor (the flow rate at a differential pressure of 1 inWC/1 Pa on the measuring cross) for the given VAV model (min = 0)

Connected to CP AO23

AV64

40292 (291)

UserSetPosition

%

Read/write

0

User-set damper opening level (after selecting the User Position mode in the Damper Command variable) (min = 0, max = 100)

Connected to CP AO26

AV65

40293 (292)

UserSetAirflow

L/s / cfm

Read/write

0

User-set airflow setpoint (after selecting the User Position mode in the Damper Command variable) (min = 0)

Connected to CP AO27

AV66

40294 (293)

AirflowCalibration

L/s / cfm

Read/write

0

Allows to enter the airflow value measured by the hood for calibration

Connected to CP AO28

AO0

30251 (250)

DamperPosition

%

Read-only

N/a

Actual damper opening level coming from the Rotary Actuator component (Position Feedback signal)

Connected to CP AO24

MSV7

40268 (267)

DamperCommand

N/a

Read/write

None

Allows to set different damper command modes for calibration, balancing, or testing:

1: Auto/none (null)

2: Max flow

3: Min flow

4: User flow

5: User position

6: Full open

7: Full close

8: Calibrate

Connected to CP MSV5

Other

AI0

30001 (0)

UpTime

s

Read-only

N/a

Device’s up time

AI1

30005 (4)

SpaceTemperature

°C/°F

Read-only

N/a

Calculated space temperature

AI3

30004 (3)

U2SpaceTemperature

°C/°F

Read-only

N/a

Actual temperature sensor value from the local U2 input

AI4

30301 (300)

PanelTemperature

°C/°F

Read-only

N/a

Actual temperature sensor value from the room panel

AI5

30006 (5)

SpaceCO2

ppm

Read-only

N/a

Calculated space CO2

AI6

30303 (302)

PanelCO2

ppm

Read-only

N/a

Actual CO2 sensor value from the room panel

AI8

30009 (8)

U4CO2Sensor

ppm

Read-only

N/a

Actual CO2 sensor value from the local U4 input

AI9

30010 (9)

EffectiveTempSetpoint

°C/°F

Read-only

N/a

Calculated effective temperature setpoint based on occupancy status and heating or cooling temperature setpoints (depending on demand)

AI10

30011 (10)

CentralTempSetpoint

°C/°F

Read-only

N/a

Calculated Central Temperature Setpoint based on setpoints and occupancy status

AI12

30013 (12)

EffectiveAirFlowSetpoint

L/s / cfm

Read-only

N/a

Calculated effective airflow setpoint based on the occupancy status and heating or cooling airflow setpoints

AI13

30014 (13)

DischargeTemperature

°C/°F

Read-only

N/a

Calculated discharge temperature

AI14

30015 (14)

ActDischTempSetpoint

°C/°F

Read-only

N/a

Calculated discharge temperature setpoint based on the effective temperature setpoint and heating demand for high-limiting discharge temperature

AI15

30016 (15)

DifferentialPressure

Pa / “WC

Read-only

N/a

Actual differential pressure sensor-measured value from the built-in pressure input

AI16

30017 (16)

U1DischTemperature

°C/°F

Read-only

N/a

Actual discharge temperature sensor value comes from the U1 input

AI17

30018 (17)

U3SetpointOffset

°C/°F

Read-only

N/a

Actual setpoint offset value (calculated from resistance) from the U3 input

AI100

30103 (102)

AppVersion

N/a

Read-only

1.0

Current application version

AV7

40208 (207)

MaxDischTempSetpoint

°C/°F

Read/write

32/90

High limit of discharge temperature supplied to the room

AV8

40209 (208)

MinDischTempSetpoint

°C/°F

Read/write

13/55

Low limit of discharge temperature supplied to the room

AV10

40211 (210)

NetTemperature

°C/°F

Read/write

-327

Temperature sensor value from the network

AV18

40219 (218)

NetDuctInTemp

°C/°F

Read/write

-327

Discharge temperature sensor value from the network

AV19

40220 (219)

NetOutdoorTemp

°C/°F

Read/write

-327

Outside air temperature sensor value from the network

AV20

40221 (220)

LoadShedding

%

Read/write

0

Load-shedding level required from the network (min = 0, max = 100)

AV21

40222 (221)

MaxDamperPosition

%

Read/write

100

Maximum damper open position limit (min = 0, max = 100)

AV22

40223 (222)

MinDamperPosition

%

Read/write

0

Minimum damper open position limit (min = 0, max = 100)

AV23

40224 (223)

MaxFanSpeed

%

Read/write

100

Maximum fan speed level limit (min = 0, max = 100)

AV24

40225 (224)

MinFanSpeed

%

Read/write

20

Minimum fan speed level limit (min = 0, max = 100)

AV25

40226 (225)

DamperDriveTime

s

Read/write

90

Time required to reach full damper open position (from 0% to 100%) (min = 0)

AV26

40227 (226)

DamperResponse

%

Read/write

15

Sets the value of how much the control signal must change to perform the next damper movement

AV28

40229 (228)

MaxOatReheater

°C/°F

Read/write

32/90

Maximum outside air temperature limit that allows the use of a reheater

AV29

40230 (229)

MaxOatPerimeter

°C/°F

Read/write

18/65

Maximum outside air temperature limit that allows the use of a perimeter

AV30

40231 (230)

FloatReheaterValveDriveTime

s

Read/write

120

Time required to reach full reheater valve open (from 0% to 100%)

AV32

40233 (232)

TimePropReheaterPeriod

s

Read/write

60

Time required for a PWM valve for a full cycle time of a reheater

AV33

40234 (233)

TimePropPerimeterPeriod

s

Read/write

60

Time required for a PWM valve for a full cycle time of a perimeter

AV34

40235 (234)

BypassTimeOverride

min

Read/write

120

Time required to maintain the bypass occupancy status (after expiration it returns to the previous status)

AV35

40236 (235)

StandbyTimeOverride

min

Read/write

15

Time required to change the occupancy status to standby (after motion detection disappears)

AV36

40237 (236)

ChangeoverDelay

min

Read/write

2

Delay time for changing the heating/cooling operating mode

AV39

40240 (239)

FanDelayOff

s

Read/write

30

Delay time for switching off the fan

AV40

40241 (240)

NetCO2

ppm

Read/write

N/a

CO2 sensor value comes from the network

AV41

40242 (241)

NetOffset

°C/°F

Read/write

0

Offset temperature setpoint value from the network

AV56

40502 (501)

PanelTempSetpoint

°C/°F

Read/write

N/a

Temperature setpoint from the room panel

AV58

40504 (503)

OffsetTempSetpoint

°C/°F

Read/write

N/a

Temperature offset for setpoint from the room panel

AV62

40290 (289)

CalculatedK-Factor

N/a

Read/write

N/a

Calculated K-Factor value (meaning the flow rate at a differential pressure of 1 inWC/1 Pa on the measuring cross) based on the entered measured airflow (using the hood) and the measured differential pressure from the built-in PI input

AV67

40295 (294)

DamperControl

%

Read/write

0

Damper opening level control resulting from the application

AO1

40252 (251)

ReheaterControl

%

Read-only

N/a

Reheater valve opening level control resulting from the application

AO2

40253 (252)

FanSpeed

%

Read-only

N/a

Fan speed level control resulting from the application

AO3

40254 (253)

PerimeterControl

%

Read-only

N/a

Perimeter valve opening level control resulting from the application

AO4

40255 (254)

AHUOutdoorDamper

%

Read-only

N/a

Required opening level of the fresh air damper in the AHU resulting from the current CO2 level in the room (network signal to the AHU control)

BI0

10302 (301)

PresenceSensor

True/false

Read-only

N/a

Actual presence sensor state from the I1 input

BI1

10304 (303)

WindowContact

True/false

Read-only

N/a

Actual window contact state from the I2 input

BV0

00101 (100)

AutoOccMode

True/false

Read/write

False

Automatically changes occupancy to occupied when increased airflow is detected:

false (disabled), true (enabled)

BV1

00102 (101)

WarmUpHeater

True/false

Read/write

False

Allows to use the reheater also in the Morning WarmUp mode (in the HVAC Mode variable):

false (disabled), true (enabled)

BV2

00103 (102)

WarmUpParallelFan

True/false

Read/write

False

Allows to use the parallel fan also in the Morning WarmUp mode (in the HVAC Mode variable):

false (disabled), true (enabled)

BV3

00104 (103)

StandbySeriesFan

True/false

Read/write

False

Allows to use the series fan also in standby occupancy:

false (disabled), true (enabled)

BV10

00111 (110)

FanControlMode

True/false

Read/write

False

Allows to select the fan control mode:

false (digital), true (analog)

BV11

00112 (111)

HeatDamperPriority

True/false

Read/write

False

Allows to set the priority of the damper heating operation when working in the active DualHeat mode:

false (secondary), true (primary)

BV12

00113 (112)

DeviceConfigurationSource

True/false

Read/write

False

Allows to choose to set a source of the device application configuration:

false (BACcnet), true (DIP switch)

BO0

00121 (120)

PerimeterStatus

True/false

Read/write

False

Perimeter digital control status (if configured as digital) from the application:

false (off), true (on)

BO1

00122 (121)

FanStatus

True/false

Read/write

False

Fan digital control status (if configured as digital) from the application:

false (off), true (on)

BO16

00017 (116)

PanelHeating

True/false

Read/write

N/a

Heating mode status to be displayed as an icon on the Control Point room panel

false (no heating), true (heating)

Connected to CP BO16

BO17

00118 (117)

PanelCooling

True/false

Read/write

N/a

Cooling mode status to be displayed as an icon on the Control Point room panel

false (no cooling), true (cooling)

Connected to CP BO17

BO55

00156 (155)

PanelSetpointMode

True/false

Read/write

N/a

Sets the temperature setpoint mode in the Control Point room panel - directly or as an offset

false (offset), true (setpoint)

Connected to CP BO55

BO56

00157 (156)

PanelSetpointDisplay

True/false

Read/write

N/a

Allows to select which value to be displayed during the offset editing according to the set Panel Setpoint Mode

false (offset), true (setpoint)

Connected to CP BO56

MSI1

30022 (21)

HVACStatus

N/a

Read-only

Unoccupied Cooling

Current HVAC status:

1: Occupied cooling

2: Occupied heating

3: Standby cooling

4: Standby heating

5: Unoccupied cooling

6: Unoccupied heating

7: Off

8: Fire

MSI2

30023 (22)

OccupancyStatus

N/a

Read-only

Unoccupied

Current occupancy status:

1: occupied

2: unoccupied

3: bypass

4: standby

MSV0

40601 (600)

PanelFanStatus

N/a

Read/write

Off

Fan status to be displayed as an icon on the Control Point room panel:

1: off

5: speed 1 (auto)

6: speed 2 (auto)

7: speed 3 (auto)

MSV1

40262 (261)

HVACMode

N/a

Read/write

Auto

Allows to set the operating mode for the VAV device:

1: Auto

2: Heat

3: Morning WarmUp

4: Cool

5: Night Purge

6: PreCool

7: Off (depressurize)

8: Fire (pressurize)

MSV2

40263 (262)

OccupancyMode

N/a

Read/write

Unoccupied

Allows to set room the occupancy mode from the BMS system:

1: occupied

2: unoccupied

3: bypass

4: standby

MSV3

40701 (700)

PanelOccupancy Status

N/a

Read/write

Unoccupied

Current room occupancy status dedicated to Control Point room panel

1: unoccupied

2: occupied

3: standby

4: bypass

Connected to CP MSV3

MSV4

40702 (701)

PanelOccupancyMode

N/a

Read/write

Unoccupied

Status of set room occupancy mode from Control Point room panel

1: unoccupied

2: occupied

Connected to CP MSV4

MSV5

40703 (702)

PanelOccupancyReset

N/a

Read/write

Unoccupied

Resetting the room occupancy mode from occupied to unoccupied in the Control Point room panel

1: unoccupied

2: occupied

MSV8

40269 (268)

FanCommand

N/a

Read/write

None

Allows to set different fan command modes for testing

1: Auto/none (null)

2: Max speed

3: Min speed

4: Stop

Connected to CP MSV6

MSV9

40270 (269)

ReheaterCommand

N/a

Read/write

None

Allows to set different reheater command modes for testing

1: Auto/none (null)

2: Full open

3: Full close

Connected to CP MSV7

MSV10

40271 (270)

PerimeterCommand

N/a

Read/write

None

Allows to set different perimeter command modes for testing

1: Auto/none (null)

2: Full open

3: Full close

Connected to CP MSV8

MSV23

40284 (283)

TemperatureInputSelector

N/a

Read/write

Panel

Allows to choose the temperature source for control logic:

1: panel

2: input

3: network

Connected to CP MSV15

MSV24

40285 (284)

SetpointOffsetSelector

N/a

Read/write

Panel

Allows to choose the setpoint offset source for control logic:

1: panel

2: input

3: network

Connected to CP MSV16

MSV25

40286 (285)

CO2InputSelector

N/a

Read/write

Panel

Allows to select the CO2 source for control logic:

1: panel

2: input

3: network

Connected to CP MSV17

MSO0

40291 (290)

ReheaterStatus

N/a

Read/write

Off

Reheater staged control status (if configured as digital or staged) from application:

1: off

2: stage 1 on

3: stage 2 on