DIP Switches
Note
Please note that the default state of all DIP switches, S1, S2, and S3, is off (0).
S1 DIP Switch
6-position DIP switch (only the last switch is used for factory reset):
Number | Description | OFF (0) | ON (1) |
---|---|---|---|
1 | Units | Metric | Imperial |
6 | Factory Reset | Down - perform an action | Up - preparation for action |
Warning - Factory Default Deletes Application
The process of bringing back factory default settings erases the application from the controller. In such a case, it is required to restore the application from the available backup.
For detailed information on how to restore the backup, please see: Default Communication Settings and Credentials.
S2 DIP Switch
The S2 8-position DIP switch is reserved for future IP configuration.
S3 DIP Switch
8-position DIP switch configures the application settings:
Note
Please note that if the switch 1 on the S3 DIP switch is on, than configuration of the fan, reheater, and perimeter type from any other source is blocked, as well as any changes made to the referring parameters (for example, Heater Priority) will not be written to the device.
Number | Description | OFF (0) | ON (1) |
---|---|---|---|
1 | Configuration priority | Control Point VAV/Software (BACnet/Modbus/iC Configurator/iC Device Manager) | DIP switch |
2 | Reheater type | 2 - off, 3 - off: no reheater 2 - on, 3 - off: reheater PWM (time proportional) 2 - off, 3 - on: reheater digital/staged (up to 2 stages) 2 - on, 3 - on: reheater floating | |
3 | |||
4 | Fan type | 4 - off, 5 - off: no fan 4 - on, 5 - off: series fan 4 - off, 5 - on: parallel fan 4 - on, 5 - on: parallel fan | |
5 | |||
6 | Perimeter type | 6 - off, 7 - off: no perimeter 6 - on, 7 - off: perimeter PWM (time proportional) 6 - off, 7 - on: perimeter digital (on/off) 6 - on, 7 - on: no perimeter | |
7 |