Note

Please note that the default state of all DIP switches, S1, S2, and S3, is off (0).

S1 DIP Switch

6-position DIP switch (only the last switch is used for factory reset):

Number

Description

OFF (0)

ON (1)

1

Units

Metric

Imperial

6

Factory Reset

Down - perform an action

Up - preparation for action

S2 DIP Switch

The S2 8-position DIP switch is reserved for future IP configuration.

S3 DIP Switch

8-position DIP switch configures the application settings:

Note

Please note that if the switch 1 on the S3 DIP switch is on, than configuration of the fan, reheater, and perimeter type from any other source is blocked, as well as any changes made to the referring parameters (for example, Heater Priority) will not be written to the device.

Number

Description

OFF (0)

ON (1)

1

Configuration priority

Control Point VAV/Software (BACnet/Modbus/iC Configurator/iC Device Manager)

DIP switch

2

Reheater type

2 - off, 3 - off: no reheater

2 - on, 3 - off: reheater PWM (time proportional)

2 - off, 3 - on: reheater digital/staged (up to 2 stages)

2 - on, 3 - on: reheater floating

3

4

Fan type

4 - off, 5 - off: no fan

4 - on, 5 - off: series fan

4 - off, 5 - on: parallel fan

4 - on, 5 - on: parallel fan

5

6

Perimeter type

6 - off, 7 - off: no perimeter

6 - on, 7 - off: perimeter PWM (time proportional)

6 - off, 7 - on: perimeter digital (on/off)

6 - on, 7 - on: no perimeter

7