App Configuration
In the Control Point panel’s VAV submenu dedicated to the VAV application, it is possible to configure the following parameters:
DEVT: allows to choose a device type between VAV and VVT;
DeviceType:
Modbus register: 00107;
BACnet object: BV6, property: Present Value;
Register/object value | Value |
---|---|
0/false | VAV |
1/true | VVT |
REHT: allows to set a reheater type;
ReheaterType:
Modbus register: 40273;
BACnet object: MSV12, property: Present Value;
Register/object value | Value |
---|---|
1 | None |
2 | Time proportional (PWM) |
3 | Staged |
4 | Float |
PERT: allows to set a perimeter type;
PerimeterType:
Modbus register: 40274;
BACnet object: MSV13, property: Present Value;
Register/object value | Value |
---|---|
1 | None |
2 | Time proportional (PWM) |
3 | Digital |
FANT: allows to set a fan type;
FanType:
Modbus register: 40272;
BACnet object: MSV11, property: Present Value;
Register/object value | Value |
---|---|
1 | None |
2 | Series |
3 | Parallel |
SPCS: allows to set a source for temperature readings;
TemperatureInputSelector:
Modbus register: 40284;
BACnet object: MSV23, property: Present Value;
Register/object value | Value |
---|---|
1 | Panel |
2 | Input |
3 | Network |
SPCT: allows to set a space temperature type on the universal input 2;
U2SpaceTempType:
Modbus register: 40283;
BACnet object: MSV22, property: Present Value;
DIST: allows to set a discharge temperature type on the universal input 1;
U1DischargeTempType:
Modbus register: 40282;
BACnet object: MSV21, property: Present Value;
Register/object value | Value |
---|---|
1 | Voltage measurement |
2 | Current |
3 | Resistance input |
4 | 10K3A1 NTC |
5 | 10K4A1 NTC |
6 | 10K NTC Carel |
7 | 20K6A1 NTC |
8 | 2,2K3A1 NTC |
9 | 3K3A1 NTC |
10 | 30K6A1 NTC |
11 | SIE1 |
12 | TAC1 |
13 | SAT1 |
14 | PT1000 |
15 | NI1000 |
16 | NI1000 21C |
17 | NI1000 LG F |
18 | 10K Type2 NTC F |
19 | 10K Type3 NTC F |
20 | 20K NTC F |
21 | 3K NTC F |
22 | PT1000 F |
23 | NI1000 32F |
24 | NI1000 70F |
OFFS: allows to set a source for setpoint offset settings;
SetpointOffsetSelector:
Modbus register: 40285;
BACnet object: MSV24, property: Present Value;
CO2S: allows to set a source for CO2 readings;
CO2InputSelector:
Modbus register: 40286;
BACnet object: MSV25, property: Present Value;
Register/object value | Value |
---|---|
1 | Panel |
2 | Input |
3 | Network |
CO2R: allows to set a range for CO2 alarm settings;
CO2SensorRange:
Modbus register: 40239;
BACnet object: AV38, property: Present Value;
Register/object value | Value |
---|---|
Min. | 0 |
Max. | 10000 |
HPRI: allows to select a priority order for the heat source;
HeaterPriority:
Modbus register: 40275;
BACnet object: MSV14, property: Present Value;
Register/object value | Value |
---|---|
1 | Reheater |
2 | Perimeter |
3 | Simultaneous |
DUHT: allows to enable a possibility to use one or two heat sources;
DualHeat:
Modbus register: 00109;
BACnet object: BV8, property: Present Value;
Register/object value | Value |
---|---|
0/false | No |
1/true | Yes |
OCCT: allows to select an occupancy contact type;
PresenceSensorInvert:
Modbus register: 00105;
BACnet object: BV4, property: Present Value;
WNDT: allows to select a window contact type;
WindowContactInvert:
Modbus register: 00106;
BACnet object: BV5, property: Present Value;
DAMP: allows to set a damper actuator’s direction to open to clockwise or counterclockwise;
DamperDirection:
Modbus register: 00110;
BACnet object: BV9, property: Present Value.
Register/object value | Value |
---|---|
0/false | Clockwise |
1/true | Counterclockwise |