Step 1: Installation
Supported Niagara Versions
nE2 Link is dedicated to Niagara 4 and supports Niagara 4.11 and higher.
Required Modules
In order to work properly, the nE2 Link requires the following modules:
nE2Link-rt.jar,
nE2Link-ux.jar,
nE2Link-wb.jar.
Contact the authorized iSMA CONTROLLI distributor to get the latest modules.
Installation
Niagara Workbench
nE2 Link can work directly on local Workbench stations. In order to use it correctly, follow the steps below:
Close the Workbench.
Copy the
nE2link-rt.jar
,nE2link-ux.jar
, andnE2link-wb.jar
files to the Niagara modules directory. Default Path:C:\Niagara\Niagara-4.x.x\modules
.Reopen the Workbench.
Connect to the local Platform using Workbench and restart the station.
Niagara Controller
It is possible to use the nE2 Link directly on a Niagara controller, such as MAC36 or JACE.
Note: Before proceeding, make sure the module is correctly installed in the local Workbench.
In Workbench, connect to the controller's Platform.
Open the Software Manager.
Locate the
nE2link-rt
andnE2link-ux
modules in the list and select them.Click the
Install
button at the bottom of the window.Click the
Commit
button at the bottom of the window.The modules will be installed on the station, and the list will reload when the process is complete.
Verify the
nE2link
modules are marked as “Up to Date”.Restart the Niagara station.
By following these steps, the nE2 Link modules will be successfully installed, enabling to leverage the full capabilities of the nano EDGE ENGINE devices within the Niagara 4 environment.