Triac Output Registers
State of Triac Outputs (40018)
This 16-bit register contains the state of triac outputs in digital mode. Setting a particular bit in the register activates the corresponding triac output according to the following table:
No. of Bit in the Register | No. of Triac Output |
---|---|
0 | 1 |
1 | 2 |
2 | 3 |
3 | 4 |
Default State of Triac Outputs (40143)
This 16-bit register contains the default state of the triac output device after the start or after resetting the watchdog.
The register bits correspond with triac outputs according to the following table:
No. of Bit in the Register | No. of Digital Output |
---|---|
0 | 1 |
1 | 2 |
2 | 3 |
3 | 4 |
Value of 1-4 Triac PWM Outputs (40121-40124)
These 16-bit registers contain the value of the duty that appears on the PWM output (expressed in percents). Output working mode is defined by the CONFIGURATION mode of the triac output.
Default State of 1-4 Triac PWM Outputs (40145-40148)
These 16-bit registers contain the value of the duty that appears on the analog output (expressed in percents) after turning the power on or resetting the watchdog.
Configuration Mode of 1-4 Triac Outputs (40168-40171)
These 16-bit registers contain information about the mode of triac outputs according to the following table:
Register Value | Description |
---|---|
0 (default) | Digital Output |
1 | PWM 1Hz |
2 | PWM 10Hz |
3 | Not supported |
4 | PWM 0.1 HZ |
5 | PWM 0.01Hz |
Hand Control Status of the Triac Outputs (30015)
This register is available only for modules with the manual control of outputs.
No. of Bit in the Register | Description |
---|---|
0,1 | Hand status of outputs 1 |
2,3 | Hand status of outputs 2 |
4,5 | Hand status of outputs 3 |
6,7 | Hand status of outputs 4 |
Value of Hand Status | Status Description |
---|---|
0 | AUTO |
2 | HAND OUT = 0 |
3 | HAND OUT = 1 |