State of Analog Outputs Operating as Digital Outputs (40019)

Setting a true value of a particular bit of this 16-bit register causes setting the maximum output voltage (10 V) on the corresponding output and setting the corresponding register with analog output value (40121-40126) to 0.

Bits of the register correspond to the following analog outputs.

No. of Bit in the Register

No. of Analog Output

0

1

1

2

2

3

3

4

4

5

5

6

AO operating as DO for MIX38 and MIX38-IP

Value of 1-6 Analog Outputs (40121-40126)

These 16-bit registers contain the value of analog output voltage in mV.

Default State of the Analog Outputs (Digital) (40144)

Setting a true value of a particular bit of this 16-bits register sets the maximum voltage (10 V) on the corresponding analog output after turning the power on or resetting the watchdog.

Bits of the register correspond to the following analog outputs:

No. of Bit in the Register

No. of Analog Output

0

1

1

2

2

3

3

4

4

5

5

6

Default state of AO operating as DO form MIX38 and MIX38-IP

Default State of 1-6 Analog Outputs (40145-40150)

These 16-bit registers contain the values of voltage in mV, which appear on the analog outputs after turning the power on or resetting the watchdog.

Configuration Mode of 1-6 Analog Outputs (40168-40173)

These 16-bit registers contain information about the mode of the analog outputs according to the following table:

Register Value

Description

0 (default)

Voltage output 0-10 V

1

PWM 1Hz

2

PWM 10Hz

3

PWM 100Hz

4

PWM 0.1Hz

5

PWM 0.01Hz

AO type settings

Hand Control Status of Analog Outputs (30015)

This register is available only for modules with the manual control of analog outputs.

No. of Bit in Register

Description

0, 1

Hand status of outputs 1

2, 3

Hand status of outputs 2

4, 5

Hand status of outputs 3

6, 7

Hand status of outputs 4

AO hand status bits

Value of the Hand Status

Status Description

0

AUTO

1

HAND CONTROL

AO hand status value

The current value of the output in the hand mode determines registers from 30125 to 30128.

Hand Control Value of 1-4 Analog Outputs (30125-30128)

The registers contain a percentage value of the manual control for outputs from 1 to 4.