Default Settings
Register Name | Default Value |
---|---|
COUNTER | 0 |
USER BAUD RATE | 7680 (76800 bps) |
STOP BITS | 1 |
DATA BITS | 8 |
PARITY BITS | 0 |
RESPONSE DELAY | 0 |
WATCHDOG TIME | 0 (disabled) |
STATE OF THE DIGITAL OUTPUTS AFTER START | 0 |
STATE OF THE ANALOG OUTPUTS (DIGITAL) AFTER START | 0 |
STATE OF THE ANALOG OUTPUTS AFTER START | 0 |
UNIVERSAL INPUT CONFIGURATION | 1 |
INPUT FILTER TIME CONSTANT | 2 |
UNIVERSAL INPUT RESOLUTION | 0 |
ANALOG OUTPUT CONFIGURATION | 0 |
Only for IP modules | |
USERNAME | platform |
PASSWORD | 1000 |
IP ADDRESS | 192.168.1.123 |
MASK | 255.255.255.0 |
GATEWAY | 192.168.1.1 |
HTTP PORT | 80 |
MODBUS TCP PORT | 502 |
MODBUS TCP TIMEOUT | 60s |
RS485 TIMEOUT | 1000ms |
RS485 BIASING RESISTORS (MINI only) | DISABLED |
SEND MODBUS ERRORS | ENABLED |
BACNET ID | 826001 |
BACNET UDP PORT | 47808 (0xBAC0) |
Restoring Default Settings
To restore the default configuration of all registers, follow the steps below:
- turn off the power supply;
- set section 6 of the S3 switch to on;
- turn on the power supply, the power LED will start blinking;
- switch section 6 of the S3 switch to off to restore the default settings. To cancel the reset, turn off the power, and switch section 6 of the S3 switch to the off position.