Other Parameters

Warning!

This section applies to all Touch Point 2.0 series: Touch Point 2.0, Touch Point ONE 2.0, Touch Point VAV 2.0, Touch Point L&B 2.0, and Touch Point Network Sensor 2.0 series.

Other parameters of the Touch Point 2.0 panels can be retrieved from the following registers and objects, or in the iSMA Configurator:

LIVE_TIME: shows uptime of the device since the last reset;

  • Modbus register: 30012;

  • BACnet object: AI0, property: Present Value;

VERSION_TYPE: allows to read version and type of the panel and enable 1 of 4 available actions. The first byte of the register indicates a version of the device, and the second one–type of the device;

  • Modbus register: 40001;

  • BACnet object: DEVICE, property: 3030;

Value

Bits 0-7

Bits 8-15

Type

Panel's version


11210(0x7016)

Panel in bootloader

23910(0xEF16)

Version

Firmware version multiplied by 10

1010(0x0A16) means 1.0 firmware version


The VERSION_TYPE register also allows to enable 1 of 4 available actions: reset panel, reload settings, reset settings, enter bootloader. If the register receives one of the following values, it invokes a relevant action and resumes its regular values afterwards (type and version):

Decimal value

Hex value

Action

511

0x01FF

Reset panel

767

0x02FF

Reload settings

1023

0x03FF

Reset settings

1279

0x04FF

Enter bootloader

FLASH_DEVICE_TYPE: indicates the panel's version and type;

  • Modbus register: 31301;

  • BACnet object: N/A;

Bit

Name

Description

0-7

VERSION_TYPE

Copy of the 40001 register's value

8-15

DEVICE_TYPE

0: TP, 1: not available

31

LCD_PRESENT

0: with display, 1: without display

FLASH_HW_VERSION: indicates the panel's hardware version;

  • Modbus register 31303;

  • BACnet object: DEVICE, property: 3020;

FLASH_BOOT_VERSION: indicates the panel's bootloader version;

  • Modbus register: 31304;

  • BACnet object: N/A;

FW_VERSION: indicates the panel's firmware version separated from the VERSION_TYPE register's value;

  • Modbus register: 31305;

  • BACnet object: N/A;

FLASH_SERIAL_NUMBER: indicates the panel's serial number;

  • Modbus registers 31306-31309;

  • BACnet object: N/A;

DEVICE_MODEL_NAME: shows a string value of the device model name;

  • Modbus registers: 31315-31330;

  • BACnet object: DEVICE, property: Model Name.