List of BACnet Objects

Warning!

Please note that the following table contains objects for all series of the Touch Point 2.0 panels.

The Touch Point VAV 2.0 series by default has no fan control and objects referring to fan control are inapplicable. If the fan control is activated on the Touch Point VAV 2.0 series panel, the objects become applicable too.

Objects referring to the fan control, occupancy, and setpoints control are inapplicable to the Touch Point Network Sensor 2.0 series or Touch Point ONE 2.0 and Touch Point L&B 2.0 that are quipped with generic buttons, which operation is dependent upon programming.

BACnet type & ID

BACnet property

Object name

Access

Default value

Value range

Description

Device

3030

VERSION_TYPE

Read/write



Shows version and type of the panel and enables 1 of 4 available actions

Device

Model name

DEVICE_MODEL_NAME

Read-only



Shows the device model

Device

5101

RECEIVED_FRAMES_COUNTER

Read-only

0


The number of received Modbus frames reset at the start of the panel and at the change of transmission parameters

Device

5103

ERROR_FRAMES_COUNTER

Read-only

0


The number of received error Modbus frames reset at the start of the panel and at the change of transmission parameters

Device

5104

TRANSMITTED_FRAME_COUNTER

Read-only

0


The number of transmitted Modbus frames reset at the start of the panel and at the change of transmission parameters

AI0

Present Value

LIVE_TIME

Read-only



Uptime of the panel in seconds

Device

Object Identifier

BACNET_DEVICE_ID

Read/write

0xFFFFFFFF


Device's BACnet ID

Device

3084

BAUD_RATE

Read/write

11520


Sets the baud rate

MSI1

Present Value

SENSORS

Read-only



Informs about built-in sensors

AI1

Present Value

BACKLIGHT_LCD

Read-only



Actual display illumination value

AI2

Present Value

BACKLIGHT_KEYPAD

Read-only



Actual keypad illumination value

MSV19

Present value

SCREEN_SELECT_MODE

Read/write



Screen mode in the Touch Point ONE 2.0 panel: standard display loop (1), fan 0 (2), fan 1 (3), fan 2 (4), fan 3 (5), fan auto (6), light 1 (7), light 2 (8), light 3 (9), light 4 (10), blind 1 (11), blind 2 (12), blind 3 (13), blind 4 (14), temperature setpoint (15)

MSV21-27

Present value

GEN_BTN_1_MODE-GEN_BTN_7_MODE

Read/write



Sets a mode of operation (disabled/blocked/bistable/monostable NO/monostable NC) to a generic button 1-7

BV56-62

Present value

GEN_BTN_1_STATE-GEN_BTN_7_STATE

Read/write



1-7 generic buttons state (on/off)

BV63-69

Present value

GEN_BTN_1_LED_LOCAL_MODE-GEN_BTN_7_LED_LOCAL_MODE

Read/write



Behavior of a generic button 1-7 additional LED

BV70-76

Present value

GEN_BTN_1_LED_BMS_STATE-GEN_BTN_7_LED_BMS_STATE

Read/write



LED BMS state set on the additional LED of a generic button 1-7 if LED mode is set to BMS mode



DEVICE_CONFIGURATION

Read/write




BO0

Present Value

BUZZER_ACTIVE


1


Activates (1) or deactivates (0) a buzzer

BO3

Present Value

LCD_BACKLIGHT_ACTIVE


1


Switches the LCD background illumination on (1)

BO4

Present Value

KEYPAD_BACKLIGHT_ACTIVE


1


Switches the keypad background illumination on (1)

BO5

Present Value

CO2_ALARM_LCD




Switches on the function of LCD background illumination flashing when CO2 alarm occurs

BO6

Present Value

CO2_ALARM_BUZZER




Switches on a buzzer when the CO2 alarm occurs

BO63

Present Value

CO2_ALARM_CONFIRM


1


Allows to enable confirmation of the CO2 alarm with any button of the panel

BO11

Present Value

PANEL_OFF


0


Switches the panel off (1)

BO12

Present Value

KEYPAD_OFF


0


Switches the panel keypad off (1)

AO3

Present Value

BACKLIGHT_LCD_ACTIVE

Read/write

60


Contains a value of the LCD display illumination in the active mode (expressed in %)

AO4

Present Value

BACKLIGHT_LCD_IDLE

Read/write

40


Contains a value of the LCD display illumination in the idle mode (expressed in %)

AO5

Present Value

BACKLIGHT_LCD_STANDBY

Read/write

0


Contains a value of the LCD display illumination in the standby mode (expressed in %)

AO6

Present Value

BACKLIGHT_LCD_TIME_TO_IDLE

Read/write

10


Sets the time after which the LCD display goes from the active mode to idle (expressed in seconds)

AO7

Present Value

BACKLIGHT_LCD_TIME_TO_STANDBY

Read/write

5


Sets the time after which the LCD display goes from the idle mode to standby (expressed in seconds)

AO8

Present Value

BACKLIGHT_KEYPAD_ACTIVE

Read/write

10


Contains a value of the keypad illumination in the active mode (expressed in %)

AO9

Present Value

BACKLIGHT_KEYPAD_IDLE

Read/write

40


Contains a value of the keypad illumination in the idle mode (expressed in %)

AO10

Present Value

BACKLIGHT_KEYPAD_STANDBY

Read/write

60


Contains a value of the keypad illumination in the standby mode (expressed in %)

AO11

Present Value

BACKLIGHT_KEYPAD_TIME_TO_IDLE

Read/write

10


Sets the time after which the keypad goes from the active mode to idle (expressed in seconds)

AO12

Present Value

BACKLIGHT_KEYPAD_TIME_TO_STANDBY

Read/write

5


Sets the time after which the keypad goes from the idle mode to standby (expressed in seconds)

AO13

Present Value

REFRESH_TIME


5

1-60

Sets the duration of the display time of particular parameters

BO74

Present value

USB_ON_OFF

Read/write



Switches on/off the USB port



ICON_DISPLAY

Read/write




BO22

Present Value

ECO




Switches on an ECO LED

AO17

Present Value

EXIT_EDIT_TIME

Read/write



Sets the time after which edition of any editable parameter is finished

AO19

Present Value

CO2_SETPOINT_FOR_ALARM

Read/write

1500


CO2 alarm setpoint

AO20

Present Value

CO2_HYSTERESIS_FOR_ALARM

Read/write

100


CO2 alarm hysteresis

BI0

Present Value

ALARM_STATUS

Read-only



CO2 current alarm status

MSV5

Present Value

NAVIGATIONAL_LED_MODE

Read/write

1

1-6

Sets a mode of the navigational LED

AO22

Present Value

NAVIGATIONAL_LED_BRIGHTNESS

Read/write

100

0-100

Navigational LED brightness

AO23

Present Value

NAVIGATIONAL_LED_RED

Read/write

100

0-100

Navigational LED color - red component intensity

AO24

Present Value

NAVIGATIONAL_LED_GREEN

Read/write

100

0-100

Navigational LED color - green component intensity

AO25

Present Value

NAVIGATIONAL_LED_BLUE

Read/write

100

0-100

Navigational LED color - blue component intensity

AI4

Present Value

TEMPERATURE_SENSOR

Read-only



Actual temperature sensor value with offset

AI5

Present Value

HUMIDITY_SENSOR

Read-only



Actual humidity sensor value with offset

AI6

Present Value

CO2_SENSOR

Read-only



Actual CO2 sensor value with offset

AI4

4205

TEMPERATURE_SENSOR_OFFSET

Read/write

0


Temperature sensor offset

AI5

4205

HUMIDITY_SENSOR_OFFSET

Read/write

0


Humidity sensor offset

AI6

4205

CO2_SENSOR_OFFSET

Read/write

0


CO2 sensor offset

AI4

4003

TEMPERATURE_FILTER

Read/write

60


Filtering time for the temperature sensor (seconds)

AI5

4003

HUMIDITY_FILTER

Read/write

60


Filtering time for the humidity sensor (seconds)

AI6

4003

CO2_FILTER

Read/write

60


Filtering time for the CO2 sensor (seconds)



TEMPERATURE_CONFIGURATION

Read/write




AI4

Out Of Service

ACTIVE


1


Activates/deactivates the sensor

AI4

4202

THIRD_POINT_ACTIVE




Sets decimal places



HUMIDITY_CONFIGURATION

Read/write




AI5

Out Of Service

ACTIVE


1


Activates/deactivates the sensor

AI5

4202

THIRD_POINT_ACTIVE




Sets decimal places



CO2_CONFIGURATION

Read/write




AI6

Out Of Service

ACTIVE


1


Activates/deactivates the sensor

AO27

Present Value

BUZZER_VOLUME

Read/write

50

0-100

Buzzer volume (%)

MSV20

Present Value

BUZZER_TONE

Read/write


1-4

Buzzer tone: discrete (1), loud (2), classic (3), retro (4)

Device

3020

FLASH_HW_VERSION

Read-only



HW version

AV56

Present Value

SETPOINT_VALUE

Read/write


0-500

Temperature setpoint value

AI3

Present Value

EFFECTIVE_SETPOINT

Read-only



Sum of setpoint and offset values

AV57

Present Value

DEFAULT_SETPOINT

Read/write

210

0-500

Default temperature setpoint

AV58

Present Value

OFFSET_SETPOINT

Read/write

0

0-500

Temperature offset for setpoint

AV56

Low Limit

SETPOINT_LOW_LIMIT

Read/write

180


Min. available setpoint value

AV56

High Limit

SETPOINT_HIGH_LIMIT

Read/write

240


Max. available setpoint value

AV59

Present Value

OFFSET_RANGE

Read/write

30

0-500

Limits offset value

AV56

4206

SETPOINT_STEP

Read/write

10


Setpoint step value



SETPOINT_CONFIGURATION

Read/write



Setpoint configuration of parameters: Visible, Editable, Operating mode, Setpoint display, ThirdPointActive

AV56

Out Of Service

VISIBLE




Enables or disables the temperature setpoint to be visible on the panel's display

AV56

4200

EDITABLE




Enables or disables editing of the temperature setpoint locally from the panel

BO55

Present Value

OPERATING_MODE




Sets the operating mode of the temperature setpoint configuration

BO56

Present Value

SETPOINT_DISPLAY




Configures the temperature setpoint display

AV56

4202

THIRD_POINT_ACTIVE




Enables or disables decimal values in the temperature setpoint

MSV0

Present Value

FAN_CURRENT_SPEED

Read/write

0


Not available for the Touch Point VAV series.

Fan speed

MSV1

Present Value

FAN_MODE

Read/write

1


Not available for the Touch Point VAV series.

Fan mode

MSV2

Present Value

FAN_TYPE

Read/write



Not available for the Touch Point VAV series.

Fan type



FAN_CONFIGURATION

Read/write

2


Not available for the Touch Point VAV series.

MSV1

Editable

EDITABLE




Not available for the Touch Point VAV series.

Activates or inactivated editing fan modes locally in the panel

BO58

Present Value

FAN_PART_EDITABLE




Not available for the Touch Point VAV series.

Configures editing of fan modes

BO60

Present Value

FAN_CONFIG_LOCAL_MODE 




Not available for the Touch Point VAV series.

Local/BMS mode

MSV3

Present Value

OCCUPANCY_CURRENT_STATUS

Read/write



Occupancy status

MSV4

Present Value

OCCUPANCY_MODE

Read/write



Occupancy mode



OCCUPANCY_CONFIGURATION

Read/write

2



MSV4

4200

EDITABLE




Activates or inactivated editing occupancy statutes locally in the panel

BO62

Present Value

OCCUPANCY_CONFIG_LOCAL_MODE




Local/BMS mode