Warning!
Please note that the following table contains registers for all series of the Touch Point 2.0 panels.
The Touch Point VAV 2.0 series by default has no fan control and registers referring to fan control are inapplicable. If the fan control is activated on the Touch Point VAV 2.0 series panel, the registers become applicable too.
Registers referring to the fan control, occupancy, and setpoints control are inapplicable to the Touch Point Network Sensor 2.0 series or Touch Point ONE 2.0 and Touch Point L&B 2.0 that are quipped with generic buttons, which operation is dependent upon programming.
|
Modbus address |
Decimal address |
Hex |
Register name |
Access |
Default value |
Value range |
Description |
|---|---|---|---|---|---|---|---|
|
40001 |
0 |
0x00 |
VERSION_TYPE |
Read/write |
|
|
Shows a firmware version and type of the panel and enables 1 of 4 available actions (reset device, reload settings, reset settings, enter bootloader) |
|
31315-31330 |
1314-1329 |
0x520-0x52F |
DEVICE_MODEL_NAME |
Read-only |
|
|
Shows the device model |
|
30002 |
1 |
0x01 |
ADDRESS_ROTARY_SWITCH |
Read-only |
|
0-9 |
Address set on a rotary switch |
|
30003 |
2 |
0x02 |
PROTOCOL_DIPSWITCH |
Read-only |
|
0-1 |
Protocol set on a DIP switch |
|
30004 |
3 |
0x03 |
RECEIVED_FRAMES_COUNTER |
Read-only |
0 |
|
The number of received Modbus frames reset at the start of the panel and at the change of transmission parameters |
|
30006 |
5 |
0x05 |
ERROR_FRAMES_COUNTER |
Read-only |
0 |
|
The number of received error Modbus frames reset at the start of the panel and at the change of transmission parameters |
|
30008 |
7 |
0x07 |
TRANSMITTED_FRAME_COUNTER |
Read-only |
0 |
|
The number of transmitted Modbus frames reset at the start of the panel and at the change of transmission parameters |
|
30012 |
11 |
0x0B |
LIVE_TIME |
Read-only |
|
|
Uptime of the panel in seconds |
|
40015 |
14 |
0x0E |
BACNET_DEVICE_ID |
Read/write |
0xFFFFFFFF |
|
Device's BACnet ID |
|
40017 |
16 |
0x10 |
BAUD_RATE |
Read/write |
11520 |
|
Sets the baud rate |
|
40018 |
17 |
0x11 |
STOP_BITS |
Read/write |
1 |
1-2 |
Sets the number of stop bits |
|
40019 |
18 |
0x12 |
DATA_BITS |
Read/write |
8 |
7-8 |
Sets the number of data bits (Modbus ASCII requires 7 bits) |
|
40020 |
19 |
0x13 |
PARITY_BIT |
Read/write |
0 |
0-2 |
Determines the parity bit |
|
40021 |
20 |
0x14 |
REPLY_DELAY |
Read/write |
0 |
|
Sets the delay time in ms before sending response |
|
40023 |
22 |
0x16 |
ADDRESS |
Read/write |
1 |
|
Modbus address of the device |
|
40024 |
23 |
0x17 |
PROTOCOL |
Read/write |
0 |
0-2 |
Sets the type of Modbus protocol (Modbus RTU (0), Modbus ASCII (1)) |
|
30029 |
28 |
0x1C |
SENSORS |
Read-only |
|
|
Informs about built-in sensors |
|
30201 |
200 |
0xC8 |
BACKLIGHT_LCD |
Read-only |
|
|
Actual display illumination value |
|
30202 |
201 |
0xC9 |
BACKLIGHT_KEYPAD |
Read-only |
|
|
Actual keypad illumination value |
|
40205 |
204 |
0xCC |
DEVICE_CONFIGURATION |
Read/write |
105 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
BUZZER |
Not active |
Active (def) |
Activates/inactivates a buzzer |
|||
|
3 |
BACKLIGHT_LCD |
Not active |
Active (def) |
Switches on/off display's backlight |
|||
|
4 |
BACKLIGHT_KEYPAD |
Not active |
Active (def) |
Switches on/off keypad's backlight |
|||
|
5 |
CO2_ALARM_LCD |
Not active |
Active |
Shows CO2 alarm on a display |
|||
|
6 |
CO2_ALARM_BUZZER |
Not active |
Active |
Switches on/off CO2 alarm's buzzer on alarm |
|||
|
8 |
CO2_ALARM_CONFIRM |
Not active |
Active (def) |
Switches on/off CO2 alarm confirmation by any button |
|||
|
11 |
PANEL_OFF |
Panel on (def) |
Panel off |
Switches on/off the panel |
|||
|
12 |
KEYPAD_OFF |
Keypad on (def) |
Keypad off |
Switches on/off the keypad |
|||
|
40206 |
205 |
0xCD |
DEVICE_CONFIGURATION_2 |
Read/write |
1 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
USB_ON_OFF |
USB off |
USB on |
Switches on/off the USB port |
|||
|
40207 |
206 |
0xCE |
BACKLIGHT_LCD_ACTIVE |
Read/write |
60 |
|
Contains a value of the LCD display illumination in the active mode (expressed in %) |
|
40208 |
207 |
0xCF |
BACKLIGHT_LCD_IDLE |
Read/write |
40 |
|
Contains a value of the LCD display illumination in the idle mode (expressed in %) |
|
40209 |
208 |
0xD0 |
BACKLIGHT_LCD_STANDBY |
Read/write |
0 |
|
Contains a value of the LCD display illumination in the standby mode (expressed in %) |
|
40210 |
209 |
0xD1 |
BACKLIGHT_LCD_TIME_TO_IDLE |
Read/write |
10 |
|
Sets the time, after which the LCD display goes from the active mode to idle (expressed in seconds) |
|
40211 |
210 |
0xD2 |
BACKLIGHT_LCD_TIME_TO_STANDBY |
Read/write |
5 |
|
Sets the time, after which the LCD display goes from the idle mode to standby (expressed in seconds) |
|
40212 |
211 |
0xD3 |
BACKLIGHT_KEYPAD_ACTIVE |
Read/write |
10 |
|
Contains a value of the keypad illumination in the active mode (expressed in %) |
|
40213 |
212 |
0xD4 |
BACKLIGHT_KEYPAD_IDLE |
Read/write |
40 |
|
Contains a value of the keypad illumination in the idle mode (expressed in %) |
|
40214 |
213 |
0xD5 |
BACKLIGHT_KEYPAD_STANDBY |
Read/write |
60 |
|
Contains a value of the keypad illumination in the standby mode (expressed in %) |
|
40215 |
214 |
0xD6 |
BACKLIGHT_KEYPAD_TIME_TO_IDLE |
Read/write |
10 |
|
Sets the time, after which the keypad goes from the active mode to idle (expressed in seconds) |
|
40216 |
215 |
0xD7 |
BACKLIGHT_KEYPAD_TIME_TO_STANDBY |
Read/write |
5 |
|
Sets the time, after which the keypad goes from the idle mode to standby (expressed in seconds) |
|
40217 |
216 |
0xD8 |
REFRESH_TIME |
|
5 |
1-60 |
Sets the duration of the display time of particular parameters |
|
40219 |
218 |
0xDA |
ICON_DISPLAY |
Read/write |
|
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
8 |
ECO |
Not active |
Active |
Switches on/off an ECO LED |
|||
|
40226 |
225 |
0xE1 |
CO2_SETPOINT_FOR_ALARM |
Read/write |
1500 |
|
CO2 alarm setpoint |
|
40227 |
226 |
0xE2 |
CO2_HYSTERESIS_FOR_ALARM |
Read/write |
100 |
|
CO2 alarm hysteresis |
|
30230 |
229 |
0xE5 |
ALARM_STATUS |
Read-only |
|
|
CO2 current alarm status |
|
30231 |
230 |
0xE6 |
NAVIGATIONAL_LED_MODE |
Read/write |
1 |
0-5 |
Sets a mode of the navigational LED |
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
OFF |
Not active |
Active |
|
|||
|
1 |
ON (default) |
Not active |
Active |
|
|||
|
2 |
Active on IDLE and STANDBY |
Not active |
Active |
|
|||
|
3 |
Active on IDLE only |
Not active |
Active |
|
|||
|
4 |
Active on STANDBY only |
Not active |
Active |
|
|||
|
5 |
BMS mode |
Not active |
Active |
|
|||
|
30232 |
231 |
0xE7 |
NAVIGATIONAL_LED_BRIGHTNESS |
Read/write |
100 |
0-100 |
Navigational LED brightness |
|
30233 |
232 |
0xE8 |
NAVIGATIONAL_LED_RED |
Read/write |
100 |
0-100 |
Navigational LED color - red component intensity |
|
30234 |
233 |
0xE9 |
NAVIGATIONAL_LED_GREEN |
Read/write |
100 |
0-100 |
Navigational LED color - green component intensity |
|
30235 |
234 |
0xE10 |
NAVIGATIONAL_LED_BLUE |
Read/write |
100 |
0-100 |
Navigational LED color - blue component intensity |
|
30301 |
300 |
0x12C |
TEMPERATURE_SENSOR |
Read-only |
|
|
Actual temperature sensor value with offset |
|
30302 |
301 |
0x12D |
HUMIDITY_SENSOR |
Read-only |
|
|
Actual humidity sensor value with offset |
|
30303 |
302 |
0x12E |
CO2_SENSOR |
Read-only |
|
|
Actual CO2 sensor value with offset |
|
40304 |
303 |
0x12F |
TEMPERATURE_SENSOR_OFFSET |
Read/write |
0 |
|
Temperature sensor offset |
|
40305 |
304 |
0x130 |
HUMIDITY_SENSOR_OFFSET |
Read/write |
0 |
|
Humidity sensor offset |
|
40306 |
305 |
0x131 |
CO2_SENSOR_OFFSET |
Read/write |
0 |
|
CO2 sensor offset |
|
40307 |
306 |
0x132 |
TEMPERATURE_FILTER |
Read/write |
60 |
|
Filtering time for the temperature sensor (seconds) |
|
40308 |
307 |
0x133 |
HUMIDITY_FILTER |
Read/write |
60 |
|
Filtering time for the humidity sensor (seconds) |
|
40309 |
308 |
0x134 |
CO2_FILTER |
Read/write |
60 |
|
Filtering time for the CO2 sensor (seconds) |
|
40316 |
315 |
0x13B |
TEMPERATURE_CONFIGURATION |
Read/write |
17 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
ACTIVE |
Not active |
Active (def) |
Activates/deactivates the sensor |
|||
|
4 |
THIRD_POINT-ACTIVE |
No decimal |
Decimal (def) |
Sets decimal places |
|||
|
40317 |
316 |
0x13C |
HUMIDITY_CONFIGURATION |
Read/write |
17 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
ACTIVE |
Not active |
Active (def) |
Activates/deactivates the sensor |
|||
|
4 |
THIRD_POINT-ACTIVE |
No decimal |
Decimal (def) |
Sets decimal places |
|||
|
40318 |
317 |
0x13D |
CO2_CONFIGURATION |
Read/write |
1 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
ACTIVE |
Not active |
Active |
Activates/deactivates the sensor |
|||
|
40323 |
322 |
0x142 |
BUZZER_VOLUME |
Read/write |
50 |
0-100 |
Buzzer volume (%) |
|
40324 |
323 |
0x143 |
BUZZER_TONE |
Read/write |
|
1-4 |
Buzzer tone: discrete (1), loud (2), classic (3), retro (4) |
|
40325 |
324 |
0x144 |
SCREEN_SELECT_MODE |
Read/write |
|
|
Screen mode in the Touch Point ONE 2.0 panel: standard display loop (1), fan 0 (2), fan 1 (3), fan 2 (4), fan 3 (5), fan auto (6), light 1 (7), light 2 (8), light 3 (9), light 4 (10), blind 1 (11), blind 2 (12), blind 3 (13), blind 4 (14), temperature setpoint (15) |
|
31301 |
1300 |
0x514 |
FLASH_DEVICE_TYPE |
Read-only |
|
|
Version and type of device |
|
31302 |
1301 |
0x515 |
FLASH_HW_VERSION |
Read-only |
|
|
HW version |
|
31303 |
1302 |
0x516 |
FLASH_BOOT_VERSION |
Read-only |
|
|
Bootloader version |
|
31304 |
1303 |
0x517 |
FW_VERSION |
Read-only |
|
|
FW version separated from the VERSION_TYPE register |
|
31305 |
1304 |
0x518 |
FLASH_SERIAL_NUMBER_1 |
Read-only |
|
|
Serial number |
|
31306 |
1305 |
0x519 |
FLASH_SERIAL_NUMBER_2 |
Read-only |
|
|
Serial number |
|
31307 |
1306 |
0x51A |
FLASH_SERIAL_NUMBER_3 |
Read-only |
|
|
Serial number |
|
31308 |
1307 |
0x51B |
FLASH_SERIAL_NUMBER_4 |
Read-only |
|
|
Serial number |
|
41342 |
1341 |
0x53D |
GENERIC_BUTTON_1_MODE |
Read/write |
|
|
Sets a mode of operation (1 - disabled/2 - blocked/3 - bistable/4 - monostable NO/5 - monostable NC) to a generic button 1 |
|
41343 |
1342 |
0x53E |
GENERIC_BUTTON_2_MODE |
Read/write |
|
|
Sets a mode of operation (1 - disabled/2 - blocked/3 - bistable/4 - monostable NO/5 - monostable NC) to a generic button 2 |
|
41344 |
1343 |
0x53F |
GENERIC_BUTTON_3_MODE |
Read/write |
|
|
Sets a mode of operation (1 - disabled/2 - blocked/3 - bistable/4 - monostable NO/5 - monostable NC) to a generic button 3 |
|
41345 |
1344 |
0x540 |
GENERIC_BUTTON_4_MODE |
Read/write |
|
|
Sets a mode of operation (1 - disabled/2 - blocked/3 - bistable/4 - monostable NO/5 - monostable NC) to a generic button 4 |
|
41346 |
1345 |
0x541 |
GENERIC_BUTTON_5_MODE |
Read/write |
|
|
Sets a mode of operation (1 - disabled/2 - blocked/3 - bistable/4 - monostable NO/5 - monostable NC) to a generic button 5 |
|
41347 |
1346 |
0x542 |
GENERIC_BUTTON_6_MODE |
Read/write |
|
|
Sets a mode of operation (1 - disabled/2 - blocked/3 - bistable/4 - monostable NO/5 - monostable NC) to a generic button 6 |
|
41348 |
1347 |
0x543 |
GENERIC_BUTTON_7_MODE |
Read/write |
|
|
Sets a mode of operation (1 - disabled/2 - blocked/3 - bistable/4 - monostable NO/5 - monostable NC) to a generic button 7 |
|
41349 |
1348 |
0x544 |
GENERIC_BUTTONS_STATES |
Read/write |
|
|
1-7 generic buttons state (on/off) |
|
Bit |
0 |
1 |
|
||||
|
0 |
Off |
On |
State of generic button 1 |
||||
|
1 |
Off |
On |
State of generic button 2 |
||||
|
2 |
Off |
On |
State of generic button 3 |
||||
|
3 |
Off |
On |
State of generic button 4 |
||||
|
4 |
Off |
On |
State of generic button 5 |
||||
|
5 |
Off |
On |
State of generic button 6 |
||||
|
6 |
Off |
On |
State of generic button 7 |
||||
|
41350 |
1349 |
0x545 |
GENERIC_BUTTONS_LED_MODES |
Read/write |
|
|
Behavior of a generic button additional LED (0- BMS, 1 - local) |
|
41352 |
1351 |
0x547 |
GENERIC_BUTTON_LED_BMS_STATES |
Read/write |
|
|
LED BMS state set on the additional LED if LED mode is set to BMS mode |
|
41501 |
1500 |
0x5DC |
SETPOINT_VALUE |
Read/write |
|
0-500 |
Temperature setpoint value |
|
41502 |
1501 |
0x5DD |
EFFECTIVE_SETPOINT |
Read-only |
|
|
Sum of setpoint and offset values |
|
41503 |
1502 |
0x5DE |
DEFAULT_SETPOINT |
Read/write |
210 |
0-500 |
Default temperature setpoint |
|
41504 |
1503 |
0x5DF |
OFFSET_SETPOINT |
Read/write |
0 |
-OFFSET_RANGE value/OFFSET_RANGE value |
Temperature offset for setpoint |
|
41505 |
1504 |
0x5E0 |
SETPOINT_LOW_LIMIT |
Read/write |
180 |
|
Min. available setpoint value |
|
41506 |
1505 |
0x5E1 |
SETPOINT_HIGH_LIMIT |
Read/write |
240 |
|
Max. available setpoint value |
|
41507 |
1506 |
0x5E2 |
OFFSET_RANGE |
Read/write |
30 |
0-100 |
Limit offset value |
|
41508 |
1507 |
0x5E3 |
SETPOINT_STEP |
Read/write |
50 |
1-100 |
Setpoint step value (default value: 0.5°C) |
|
41509 |
1508 |
0x5E4 |
SETPOINT_LED_BAR_MODE |
Read/write |
|
|
LED bar operation mode |
|
41510 |
1509 |
0x5E5 |
SETPOINT_LED_BAR_USER_VALUE |
Read/write |
|
-500-500 |
Value represented on the LED bar if the LED bar mode is set to BMS |
|
41513 |
1512 |
0x5E8 |
SETPOINT_CONFIGURATION |
Read/write |
31 |
|
Setpoint configuration of parameters: Visible, Editable, Operating mode, Setpoint display, ThirdPointActive |
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
VISIBLE |
Not visible |
Visible (def) |
Switches on/off a temperature setpoint visibility on a display |
|||
|
1 |
EDITABLE |
Not editable |
Editable (def) |
Activates/inactivates editing of a temperature setpoint locally on the panel |
|||
|
2 |
OPERATING_MODE |
Changing offset |
Changing setpoint (def) |
Switches between changing offset or setpoint |
|||
|
3 |
SETPOINT_DISPLAY |
Show/change offset |
Show/change effective setpoint (def) |
Switches between changing offset or setpoint |
|||
|
4 |
THIRD_POINT_ACTIVE |
No decimal |
Decimal (def) |
Activates/inactivates decimal points |
|||
|
41601 |
1600 |
0x640 |
FAN_CURRENT_SPEED |
Read/write |
0 |
|
Not available for the Touch Point VAV series. Fan speed |
|
41602 |
1601 |
0x641 |
FAN_MODE |
Read/write |
1 |
|
Not available for the Touch Point VAV series. Fan mode |
|
41603 |
1602 |
0x642 |
FAN_TYPE |
Read/write |
|
|
Not available for the Touch Point VAV series. Fan type |
|
41614 |
1613 |
0x64D |
FAN_CONFIGURATION |
Read/write |
2 |
|
Not available for the Touch Point VAV series. |
|
Bit |
Name |
0 |
1 |
|
|||
|
1 |
EDITABLE |
Not editable |
Editable (def) |
Switches on/off editing fan modes locally |
|||
|
2 |
PART_EDITABLE |
Fully editable |
Auto_Off_Mode |
Switches editability of fan modes |
|||
|
6 |
FAN_CONFIG_LOCAL_MODE |
BMS (def) |
Local |
Switches between BMS/local modes |
|||
|
41701 |
1700 |
0x6A4 |
OCCUPANCY_CURRENT_STATUS |
Read/write |
|
|
Occupancy status |
|
41702 |
1701 |
0x6A5 |
OCCUPANCY_MODE |
Read/write |
|
|
Occupancy mode |
|
41707 |
1706 |
0x6AA |
OCCUPANCY_CONFIGURATION |
Read/write |
2 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
1 |
EDITABLE |
Not editable |
Editable (def) |
Switches on/off editing occupancy statues locally |
|||
|
6 |
OCCUPIED_CONFIG_LOCAL_MODE |
BMS (def) |
Local |
Switches between BMS/local modes |
|||