Skip to main content
Skip table of contents

Technical Specification

Power Supply

Voltage

24 V AC/DC ± 20%

Power Consumption

iSMA-B-LP(-1): 0.5 W (24 V DC), 0.75 VA (24 V AC)

iSMA-B-LP-H(-1): 0.5 W (24 V DC), 0.75 VA (24 V AC)

iSMA-B-LP-C(-1): 0.7 W (24 V DC), 1 VA (24 V AC)

iSMA-B-LP-HC(-1): 0.7 W (24 V DC), 1 VA (24 V AC)

Built-in Sensors

Temperature Sensor

10k NTC type

Accuracy: ±0.5˚C

Range: 0-50˚C

Resolution: ±0.1˚C

Humidity Sensor

Range: 0-100% RH

Accuracy: ±2% RH in range 20-80% RH

Resolution: ±1% RH

CO2 Sensor

Method Non Dispersive Infrared (NDIR), gold plated optics, diffusion sampling (with Telaire’s Patented ABC Logic Self Calibrated Algorithm)

Range: 400-2000 ppm

Accuracy: ±30 ppm OR ±3% of reading

Stability: < 2% of FS over life of sensor (15 years typical)

Warm-up Time : < 2 minutes (operational);

10 minutes (maximum accuracy)

Calibration: ABC Logic Algorithm

Manual Calibration Interval: Not required

RS485 Interface

Communication Protocols

Modbus RTU, Modbus ASCII, BACnet MS/TP

Baud rate

From 4800 to 115200 bps

USB

USB

Mini USB, type B

Environment

Ingress Protection

IP40

Temperature

Storage

-40˚C to +85˚C

Operating

0˚C to +50˚C

Humidity

Relative

5% to 95%

Platform


ARM Cortex - M0+

Housing


Construction: plastic, self-extinguishing (PC/ABS)

Wall mounting (standard electric box)

Cooling: internal air circulation  

Dimensions

Width

100 mm

Length

27 mm

Height

123 mm

Technical specification

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.