Registers Adjustable Locally from the Room Panel
Room Panel Settings
Accessing the settings from the main menu level is possible in the active mode.
In order to enter the settings locally, press the OK button and the Menu button together, for the time longer than the time value stored in the ENTER_MENU_TIME register. Access to the settings menu is protected by a password stored in the PANEL_PASSWORD register (default password: 1000).
The settings menu name blinks on the 14-segment display block.
Particular settings are selected by pressing the up and down arrow buttons.
Press the OK button to enter a selected setting.
Upon entering a particular setting, the parameters are displayed in ascending order (by a parameter number) on the 14-segment display block.
Available parameters are selected by pressing the up or down arrow buttons.
All parameters are described in detail in further sections of this User Manual.
Configuration (CONF)
The configuration menu contains registers responsible for the device configuration. Most of the registers available in the configuration menu are the communication registers: baud rate, Modbus address, stop bits, parity bits and protocol selection. The user can also change the panel’s password and check the firmware version in the configuration menu. All available parameters are presented in the table below:
Parameter Number | Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|---|
1.1 | 40017 | 16 | 0x10 | BAUD_RATE | Read/write | 48-1152 (*100kbs) |
1.2 | 40023 | 22 | 0x16 | ADDRESS | Read/write | Default: 1 |
1.3 | 40018 | 17 | 0x11 | STOP_BITS | Read/write | 1: one stop bit 2: two stop bits |
1.4 | 40020 | 19 | 0x13 | PARITY_BITS | Read/write | 0: disabled 1: odd 2: even |
1.5 | 40024 | 23 | 0x17 | PROTOCOL | Read/write | 0: Modbus RTU 1: Modbus ASCII 2: BACnet MS/TP |
1.6 | 40028 | 27 | 0x1B | PANEL_PASSWORD | Read/write | Default: 1000 |
1.7 | - | - | - | FIRMWARE_VERSION | Read-only | Software Version |
Device (DEV)
The Device settings menu contains registers responsible for global settings. Changing any of parameter in the Device menu impacts modes and functions of the room panel. The Device menu contains parameters for time settings, such as time format, menu enter or exit time, or refresh time. In the Device menu, the user can also switch the beeper off or disable the background illumination of the LCD display or keypad. All available parameters are presented in the table below:
Parameter Number | Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|---|
2.1 | 40205 | 204 | 0xCC | DEVICE CONFIGURATION bit 0 BEEPER | Read/write | 0: inactive 1: active(def) |
2.2 | 40205 | 204 | 0xCC | DEVICE CONFIGURATION bit 1 TIME_FORMAT | Read/write | 0-24h(def) 1-12h |
2.3 | 40205 | 204 | 0xCC | DEVICE CONFIGURATION bit 2 TEMPERATURE_UNIT | Read/write | Not supported |
2.4 | 40205 | 204 | 0xCC | DEVICE CONFIGURATION bit 3 BACKGROUND_ILLUMINATION_LCD_ACTIVE | Read/write | 0: inactive 1: active(def) |
2.5 | 40205 | 204 | 0xDE | DEVICE CONFIGURATION bit 4 BACKGROUND_ILLUMINATION_KEYPAD_ACTIVE | Read/write | 0: inactive(def) 1: active |
2.6 | 40223 | 222 | 0x1B | ENTER_MENU_TIME | Read/write | Default: 2 sec |
2.7 | 40224 | 223 | 0xDF | EXIT_EDIT_TIME | Read/write | Default: 5 sec |
2.8 | 40225 | 224 | 0xE0 | EXIT_MENU_TIME | Read/write | Default: 10 sec |
2.9 | 40217 | 216 | 0xD8 | REFRESH_TIME | Read/write | Default: 2 sec |
Temperature (TEMP)
The Temperature settings menu contains registers referring to the temperature sensor display and temperature control settings. The user is able to switch on/off the temperature sensor value display, set the temperature sensor filter, or change the temperature sensor offset. All available parameters are presented in the table below:
Parameter Number | Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|---|
3.1 | 40316 | 315 | 0x13B | TEMPERATURE_ CONFIGURATION bit 0 ACTIVE | Read/write | 0: inactive 1-active(def) |
3.2 | 40316 | 315 | 0x13B | TEMPERATURE_CONFIGURATION bit 4 THIRD_POINT_ACTIVE | Read/write | 0: inactive 1: active(def) |
3.3 | 40307 | 306 | 0x132 | TEMPERATURE_FILTER | Read/write | Default: 60 sec |
3.4 | 40304 | 303 | 0x12F | TEMPERATURE_OFFSET | Read/write | Default: 0 |
Humidity (HUM)
The Humidity settings menu contains registers referring to the humidity sensor display and the humidity control settings. The user is able to switch on/off the humidity sensor value display, set the humidity sensor filter, or change the humidity sensor offset. All available parameters are presented in the table below:
Parameter Number | Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|---|
4.1 | 40317 | 316 | 0x13C | HUMIDITY_CONFIGURATION bit 0 ACTIVE | Read/write | 0: inactive 1: active(def) |
4.2 | 40317 | 316 | 0x13C | HUMIDITY_CONFIGURATION bit 4 THIRD_POINT_ACTIVE | Read/write | 0: inactive 1: active(def) |
4.3 | 40308 | 307 | 0x133 | HUMIDITY_FILTER | Read/write | Default: 60 sec |
4.4 | 40305 | 304 | 0x130 | HUMIDITY_OFFSET | Read/write | Default: 0 |
CO2 (CO2)
The CO2 settings menu contains registers referring to the CO2 sensor display and CO2 control settings. The user is able to switch on/off the CO2 sensor value display, set the CO2 sensor filter, or change the CO2 sensor offset. All available parameters are presented in the table below:
Parameter Number | Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|---|
5.1 | 40318 | 317 | 0x13D | CO2 CONFIGURATION bit 0 ACTIVE | Read/write | 0: inactive 1: active(def) |
5.2 | 40309 | 308 | 0x134 | CO2_FILTER | Read/write | Default: 60 sec |
5.3 | 40307 | 306 | 0x132 | CO2_OFFSET | Read/write | Default: 0 |
5.4 | 40226 | 225 | 0xE1 | CO2_SETPOINT | Read/write | Default: 1500 ppm |
Setpoint (SETP)
In the Setpoint settings menu, the user has access to the main setpoint registers. It is possible to change most useful setpoint parameters locally from the room panel, such as a default setpoint, low and high setpoint limits, setpoint step, or offset range. The user can also decide if the setpoint value should be displayed in the main menu, or if the setpoint or offset should be changed during a setpoint edition. All available parameters are presented in the table below:
Parameter Number | Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|---|
6.1 | 41513 | 1512 | 0x5E8 | SETPOINT_CONFIGURATION bit 0 ACTIVE | Read/write | 0-inactive 1-active(def) |
6.2 | 41513 | 1512 | 0x5E8 | SETPOINT_CONFIGURATION bit 1 EDITABLE | Read/write | 0-inactive 1-active(def) |
6.3 | 41513 | 1512 | 0x5E8 | SETPOINT_CONFIGURATION bit 2 OPPERATING_MODE | Read/write | 0-changing offset 1-changing setpoint(def) |
6.4 | 41513 | 1512 | 0x5E8 | SETPOINT_CONFIGURATION bit 3 SETPOINT_DISPLAY | Read/write | 0-changing offset 1-changing effective setpoint(def) |
6.5 | 41513 | 1512 | 0x5E8 | SETPOINT_CONFIGURATION bit 4 THIRD_POINT_ACTIVE | Read/write | 0-inactive 1-active(def) |
6.6 | 41513 | 1512 | 0x5E8 | SETPOINT_CONFIGURATION bit 5 FAST_EDIT_MODE | Read/write | 0-inactive(def) 1-active |
6.7 | 41503 | 1502 | 0x5DE | DEFAULT_SETPOINT | Read/write | By default 210 |
6.8 | 41505 | 1504 | 0x5E0 | SETPOINT_LOW_LIMIT | Read/write | By default 180 |
6.9 | 41506 | 1505 | 0x5E1 | SETPOINT_HIGH_LIMIT | Read/write | By default 240 |
6.10 | 41507 | 1506 | 0x5E2 | OFFSET_RANGE | Read/write | By default 30 |
6.11 | 41508 | 1507 | 0x5E3 | SETPOINT_STEP | Read/write | By default 10 |
Fan (FAN)
The Fan settings menu contains the registers of fan configuration settings. The user can change the fan type or decide if the fan status is displayed in the main menu. Editable parameters determine if the user can change particular fan modes. All available parameters are presented in the table below:
Parameter Number | Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|---|
7.1 | 41614 | 1613 | 0x64D | FAN_CONFIGURATION bit 0 VISABLE_FAN_CURRENT_SPEED | Read/write | 0: inactive 1: active(def) |
7.2 | 41614 | 1613 | 0x64D | FAN_CONFIGURATION bit 1 EDITABLE | Read/write | 0: inactive 1: active(def) |
7.3 | 41614 | 1613 | 0x64D | FAN_CONFIGURATION bit 2 PART_EDITABLE | Read/write | 0: inactive(def) 1: active |
7.4 | 41614 | 1613 | 0x64D | FAN_CONFIGURATION bit 5 FAST_EDIT_MODE | Read/write | 0: inactive(def) 1: active |
7.5 | 41615 | 1614 | 0x64E | FAN_ICON_FLASHING_TIME | Read/write | Default: 500 ms |
7.6 | 41603 | 1602 | 0x642 | FAN_TYPE | Read/write | 0: 0-10 V(def) 1: 1-Speed 2: 2-Speed 3: 3-Speed |
Occupancy (OCCU)
The Occupancy settings menu contains registers referring to the occupancy configuration. The user can decide if the current occupancy status is displayed in the main menu. Editable parameters determine if the user can change the occupancy mode. All available parameters are presented in the table below:
Parameter Number | Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|---|
8.1 | 41707 | 1706 | 0x6AA | OCCUPANCY_CONFIGURATION bit 0 VISABLE_OCCUPANCY_CURRENT_STATUS | Read/write | 0: inactive 1: active(def) |
8.2 | 41707 | 1706 | 0x6AA | OCCUPANCY_CONFIGURATION bit 1 EDITABLE | Read/write | 0: inactive 1: active(def) |
8.3 | 41707 | 1706 | 0x6AA | OCCUPANCY_CONFIGURATION bit 5 FAST_EDIT_MODE | Read/write | 0: inactive(def) 1: active |