Technical Specification
Power Supply | Voltage | 24 V AC/DC ± 20% |
---|---|---|
Power consumption | 7 W at 24 V DC; 10.5 VA at 24 V AC | |
Universal Inputs | Number of inputs | 8 |
Temperature input | Measurement with attached RTDS | |
Voltage input | Voltage measurement from 0 to 10 V | |
Current input | Current measurement 0-20 mA | |
Resistance input | Measurement of resistance: 0-1000 kΩ | |
Digital input | Output current ~1 mA | |
Measurement resolution | 12-bits (default) or 16-bits | |
Processing time | 10 ms/channel at 12-bits | |
Digital Inputs | Number of inputs | 4 |
Type | Dry contact or fast pulse counter up to 100 Hz | |
Analog Outputs | Number of outputs | 6 |
Voltage range | 0-10 V DC | |
Max. load current | 20 mA (A6 up to 5 mA) | |
Resolution | 12-bits | |
Accuracy | ±0.5% | |
Digital Outputs | Number of outputs | 4 |
Contact material | AgSnO2 | |
Resistive load | 3 A at 230 V AC or 3 A at 30 V DC | |
Inductive load | 75 VA at 230 V AC or 30 W at 30 V DC | |
COM1 | RS485 interface | Up to 128 devices |
Communication protocol | Modbus RTU/ASCII (client) | |
Port | RJ12 | |
Baud rate | 4800-115200 | |
COM2 | RS485 interface | Up to 128 devices |
Communication protocol | Modbus RTU/ASCII (client/server) BACnet MS/TP (client/server) | |
Port | Screw connector | |
Baud rate | 4800-115200 | |
ETH1 | Ethernet interface | 2 ports, switch mode |
Baud rate | 10/100 Mb/s | |
USB1 | USB 2.0 | Type A |
Communication | Open protocols | Modbus RTU/ASCII Modbus TCP/IP BACnet MS/TP BACnet IP M-Bus IP SOX protocol oBIX 1-Wire DALI (iSMA-B-AAC20-D, iSMA-B-AAC20-LCD-D) Free software: AAC20 Updater & iSMA Tool Built-in web server |
Ingress Protection | IP rating | IP40 |
Temperature | Storage | -40˚C to +85˚C (-40°F to +185°F) |
Operating | -10˚C to +50˚C (14°F to 122°F) | |
Humidity | Relative | 5% to 95% (without condensation) |
Screw Connectors | Type | Separable |
Maximum cable size | 2.5 mm2 | |
Dimensions | Width | 110 mm/4.33 in |
Length | 106 mm/4.17 in | |
Height | 62 mm/2.44 in |