Note
Please note that if the switch 1 on the S3 DIP switch is on, than configuration of the reheater, and perimeter type from any other source is blocked (BACnet/Modbus), as well as any changes made to the referring parameters will not be written to the device.
|
BACnet ID |
Modbus address (dec) |
Object/register name |
Units |
Access |
Default value |
Description |
|---|---|---|---|---|---|---|
|
Configuration |
||||||
|
AV37 |
40238 (237) |
SetpointOffsetRange |
N/a |
Read/write |
3 |
Sets the setpoint offset range to be changed by the user (e.g., a value of 5 means a range from -5 to +5), (min = 0, max = 10) Connected to CP AV59 |
|
AV38 |
40239 (238) |
U4PressureSensorRange |
N/a |
Read/write |
100 |
Sets the relative range of the pressure sensor used (min = 0, max = 1000) Connected to CP AO37 |
|
BV4 |
00105 (104) |
PresenceSensorInvert |
True/false |
Read/write |
True |
Allows to invert the I1 input signal if required: false (normal), true (invert) Connected to CP BO66 |
|
BV5 |
00106 (105) |
WindowContactInvert |
True/false |
Read/write |
False |
Allows to invert the I2 input signal if required: false (normal), true (invert) Connected to CP BO67 |
|
BV8 |
00109 (108) |
DualHeat |
True/false |
Read/write |
False |
Allows to enable dual heating mode with repeater and perimeter: false (no), true (yes) Connected to CP BO69 |
|
BO2 |
00123 (122) |
Units |
True/false |
Read/write |
False |
Allows to change the unit in the application provided that the BACnet configuration is allowed in the Device Configuration Source variable: false (metric), true (imperial) Connected to CP BO2 |
|
MSV12 |
40273 (272) |
ReheaterType |
N/a |
Read/write |
None |
Allows to set the reheater type: 1: none 2: TimeProp 3: staged 4: float Connected to CP MSV10 |
|
MSV13 |
40274 (273) |
PerimeterType |
N/a |
Read/write |
None |
Allows to set the perimeter type: 1: none 2: TimeProp 3: digital 4: float Connected to CP MSV11 |
|
MSV14 |
40275 (274) |
HeaterPriority |
N/a |
Read/write |
Reheater |
Possibility to select heating priority for heating sources: 1: reheater 2: perimeter 3: simultaneous Connected to CP MSV14 |
|
MSV21 |
40282 (281) |
U1DischargeTempType |
N/a |
Read/write |
10K3A1 NTC |
Allows to select the discharge temperature type: 1: Voltage measurement 2: Current 3: Resistance input 4: 10K3A1 NTC 5: 10K4A1 NTC 6: 10K NTC Carel 7: 20K6A1 NTC 8: 2,2K3A1 NTC 9: 3K3A1 NTC 10: 30K6A1 NTC 11: SIE1 12: TAC1 13: SAT1 14: PT1000 15: NI1000 16: NI1000 21C 17: NI1000 LG F 18: 10K Type2 NTC F 19: 10K Type3 NTC F 20: 20K NTC F 21: 3K NTC F 22: PT1000 F 23: NI1000 32F 24: NI1000 70F Connected to CP MSV12 |
|
MSV22 |
40283 (282) |
U2SpaceTempType |
N/a |
Read/write |
10K3A1 NTC |
Allows to select the space temperature type: 1: Voltage measurement 2: Current 3: Resistance input 4: 10K3A1 NTC 5: 10K4A1 NTC 6: 10K NTC Carel 7: 20K6A1 NTC 8: 2,2K3A1 NTC 9: 3K3A1 NTC 10: 30K6A1 NTC 11: SIE1 12: TAC1 13: SAT1 14: PT1000 15: NI1000 16: NI1000 21C 17: NI1000 LG F 18: 10K Type2 NTC F 19: 10K Type3 NTC F 20: 20K NTC F 21: 3K NTC F 22: PT1000 F 23: NI1000 32F 24: NI1000 70F Connected to CP MSV13 |
|
BV9 |
00110 (109) |
DamperDirection |
True/false |
Read/write |
False |
Sets the damper opening direction: false (CW), true (CCW) Connected to CP BO65 |
|
AV1 |
40202 (201) |
OccHeatTempSetpoint |
°C/°F |
Read/write |
21/70 |
Temperature setpoint for heating in the occupied state |
|
AV3 |
40204 (203) |
StandbyHeatTempSetpoint |
°C/°F |
Read/write |
19/67 |
Temperature setpoint for heating in the standby state |
|
AV5 |
40206 (205) |
UnoccHeatTempSetpoint |
°C/°F |
Read/write |
16/64 |
Temperature setpoint for heating in the unoccupied state |
|
AV6 |
40207 (206) |
SpacePressureSetpoint |
Pa |
Read/write |
0 |
Pressure setpoint for the room (regardless of the occupancy status) |
|
AV64 |
40292 (291) |
UserSetPosition |
% |
Read/write |
0 |
User-set damper opening level (after selecting the User Position mode in the Damper Command variable) (min = 0, max = 100) Connected to CP AO26 |
|
AO0 |
30251 (250) |
DamperPosition |
% |
Read-only |
N/a |
Actual damper opening level coming from the Rotary Actuator component (Position Feedback signal) Connected to CP AO24 |
|
MSV7 |
40268 (267) |
DamperCommand |
N/a |
Read/write |
None |
Allows to set different damper command modes for calibration, balancing, or testing: 1: Auto 2: - 3: - 4: - 5: User position 6: Full open 7: Full close 8: Calibrate Connected to CP MSV5 |
|
Other |
||||||
|
AI0 |
30001 (0) |
UpTime |
s |
Read-only |
N/a |
Device’s up time |
|
AI1 |
30005 (4) |
SpaceTemperature |
°C/°F |
Read-only |
N/a |
Calculated space temperature |
|
AI3 |
30004 (3) |
U2SpaceTemperature |
°C/°F |
Read-only |
N/a |
Actual temperature sensor value from the local U2 input |
|
AI4 |
30301 (300) |
PanelTemperature |
°C/°F |
Read-only |
N/a |
Actual temperature sensor value from the room panel |
|
AI5 |
30006 (5) |
SpacePressure |
Pa |
Read-only |
N/a |
Calculated space pressure |
|
AI8 |
30009 (8) |
U4PressureSensor |
ppm |
Read-only |
N/a |
Actual pressure sensor value from the local U4 input |
|
AI9 |
30010 (9) |
EffectiveTempSetpoint |
°C/°F |
Read-only |
N/a |
Calculated effective temperature setpoint based on occupancy status and heating or cooling temperature setpoints (depending on demand) |
|
AI10 |
30011 (10) |
CentralTempSetpoint |
°C/°F |
Read-only |
N/a |
Calculated Central Temperature Setpoint based on setpoints and occupancy status |
|
AI13 |
30014 (13) |
DischargeTemperature |
°C/°F |
Read-only |
N/a |
Calculated discharge temperature |
|
AI14 |
30015 (14) |
ActDischTempSetpoint |
°C/°F |
Read-only |
N/a |
Calculated discharge temperature setpoint based on the effective temperature setpoint and heating demand for high-limiting discharge temperature |
|
AI16 |
30017 (16) |
U1DischTemperature |
°C/°F |
Read-only |
N/a |
Actual discharge temperature sensor value comes from the U1 input |
|
AI17 |
30018 (17) |
U3SetpointOffset |
°C/°F |
Read-only |
N/a |
Actual setpoint offset value (calculated from resistance) from the U3 input |
|
AI100 |
30103 (102) |
AppVersion |
N/a |
Read-only |
1.0 |
Current application version |
|
AV7 |
40208 (207) |
MaxDischTempSetpoint |
°C/°F |
Read/write |
32/90 |
High limit of discharge temperature supplied to the room |
|
AV8 |
40209 (208) |
MinDischTempSetpoint |
°C/°F |
Read/write |
13/55 |
Low limit of discharge temperature supplied to the room |
|
AV10 |
40211 (210) |
NetTemperature |
°C/°F |
Read/write |
-327 |
Temperature sensor value from the network |
|
AV18 |
40219 (218) |
NetDuctInTemp |
°C/°F |
Read/write |
-327 |
Discharge temperature sensor value from the network |
|
AV19 |
40220 (219) |
NetOutdoorTemp |
°C/°F |
Read/write |
-327 |
Outside air temperature sensor value from the network |
|
AV20 |
40221 (220) |
LoadShedding |
% |
Read/write |
0 |
Load-shedding level required from the network (min = 0, max = 100) |
|
AV21 |
40222 (221) |
MaxDamperPosition |
% |
Read/write |
100 |
Maximum damper open position limit (min = 0, max = 100) |
|
AV22 |
40223 (222) |
MinDamperPosition |
% |
Read/write |
0 |
Minimum damper open position limit (min = 0, max = 100) |
|
AV25 |
40226 (225) |
DamperDriveTime |
s |
Read/write |
90 |
Time required to reach full damper open position (from 0% to 100%) (min = 0) |
|
AV26 |
40227 (226) |
DamperResponse |
% |
Read/write |
15 |
Sets the value of how much the control signal must change to perform the next damper movement |
|
AV27 |
40228 (227) |
U4PressureSensorMin |
Pa |
Read/write |
0 |
Min value of pressure sensor range |
|
AV28 |
40229 (228) |
MaxOatReheater |
°C/°F |
Read/write |
32/90 |
Maximum outside air temperature limit that allows the use of a reheater |
|
AV29 |
40230 (229) |
MaxOatPerimeter |
°C/°F |
Read/write |
18/65 |
Maximum outside air temperature limit that allows the use of a perimeter |
|
AV30 |
40231 (230) |
FloatReheaterValveDriveTime |
s |
Read/write |
120 |
Time required to reach full reheater valve open (from 0% to 100%) |
|
AV32 |
40233 (232) |
TimePropReheaterPeriod |
s |
Read/write |
60 |
Time required for a PWM valve for a full cycle time of a reheater |
|
AV31 |
40232 (231) |
FloatPerimeterValveDriveTime |
s |
Read/write |
120 |
Time required to reach full perimeter valve open (from 0% to 100%) |
|
AV33 |
40234 (233) |
TimePropPerimeterPeriod |
s |
Read/write |
60 |
Time required for a PWM valve for a full cycle time of a perimeter |
|
AV34 |
40235 (234) |
BypassTimeOverride |
min |
Read/write |
120 |
Time required to maintain the bypass occupancy status (after expiration it returns to the previous status) |
|
AV35 |
40236 (235) |
StandbyTimeOverride |
min |
Read/write |
15 |
Time required to change the occupancy status to standby (after motion detection disappears) |
|
AV40 |
40241 (240) |
NetPressure |
Pa |
Read/write |
-327 |
Pressure sensor value comes from the network |
|
AV41 |
40242 (241) |
NetOffsetSetpoint |
°C/°F |
Read/write |
0 |
Offset temperature setpoint value from the network |
|
AV56 |
40502 (501) |
PanelTempSetpoint |
°C/°F |
Read/write |
N/a |
Temperature setpoint from the room panel |
|
AV58 |
40504 (503) |
OffsetTempSetpoint |
°C/°F |
Read/write |
N/a |
Temperature offset for setpoint from the room panel |
|
AV67 |
40295 (294) |
DamperControl |
% |
Read/write |
0 |
Damper opening level control resulting from the application |
|
AO1 |
40252 (251) |
ReheaterControl |
% |
Read-only |
N/a |
Reheater valve opening level control resulting from the application |
|
AO3 |
40254 (253) |
PerimeterControl |
% |
Read-only |
N/a |
Perimeter valve opening level control resulting from the application |
|
BI0 |
10302 (301) |
PresenceSensor |
True/false |
Read-only |
N/a |
Actual presence sensor state from the I1 input |
|
BI1 |
10304 (303) |
WindowContact |
True/false |
Read-only |
N/a |
Actual window contact state from the I2 input |
|
BV1 |
00102 (101) |
WarmUpHeater |
True/false |
Read/write |
False |
Allows to use the reheater also in the Morning WarmUp mode (in the HVAC Mode variable): false (disabled), true (enabled) |
|
BV12 |
00113 (112) |
DeviceConfigurationSource |
True/false |
Read/write |
False |
Allows to choose to set a source of the device application configuration: false (BACcnet), true (DIP switch) |
|
BO0 |
00121 (120) |
PerimeterStatus |
True/false |
Read/write |
False |
Perimeter digital control status (if configured as digital) from the application: false (off), true (on) |
|
BO16 |
00017 (116) |
PanelHeating |
True/false |
Read/write |
N/a |
Heating mode status to be displayed as an icon on the Control Point room panel false (no heating), true (heating) Connected to CP BO16 |
|
BO55 |
00156 (155) |
PanelSetpointMode |
True/false |
Read/write |
N/a |
Sets the temperature setpoint mode in the Control Point room panel - directly or as an offset false (offset), true (setpoint) Connected to CP BO55 |
|
BO56 |
00157 (156) |
PanelSetpointDisplay |
True/false |
Read/write |
N/a |
Allows to select which value to be displayed during the offset editing according to the set Panel Setpoint Mode false (offset), true (setpoint) Connected to CP BO56 |
|
MSI2 |
30023 (22) |
OccupancyStatus |
N/a |
Read-only |
Unoccupied |
Current occupancy status: 1: occupied 2: unoccupied 3: bypass 4: standby |
|
MSV1 |
40262 (261) |
HVACMode |
N/a |
Read/write |
Auto
|
Allows to set the operating mode for the VAV device: 1: Auto 2: Heat 3: Morning WarmUp 4: Cool 5: Night Purge 6: PreCool 7: Off (depressurize) 8: Fire (pressurize) |
|
MSV2 |
40263 (262) |
OccupancyMode |
N/a |
Read/write |
Unoccupied |
Allows to set room the occupancy mode from the BMS system: 1: occupied 2: unoccupied 3: bypass 4: standby |
|
MSV3 |
40701 (700) |
PanelOccupancy Status |
N/a |
Read/write |
Unoccupied |
Current room occupancy status dedicated to Control Point room panel 1: unoccupied 2: occupied 3: standby 4: bypass Connected to CP MSV3 |
|
MSV4 |
40702 (701) |
PanelOccupancyMode |
N/a |
Read/write |
Unoccupied |
Status of set room occupancy mode from Control Point room panel 1: unoccupied 2: occupied Connected to CP MSV4 |
|
MSV5 |
40703 (702) |
PanelOccupancyReset |
N/a |
Read/write |
Unoccupied |
Resetting the room occupancy mode from occupied to unoccupied in the Control Point room panel 1: unoccupied 2: occupied |
|
MSV9 |
40270 (269) |
ReheaterCommand |
N/a |
Read/write |
None |
Allows to set different reheater command modes for testing 1: Auto/none (null) 2: Full open 3: Full close Connected to CP MSV7 |
|
MSV10 |
40271 (270) |
PerimeterCommand |
N/a |
Read/write |
None |
Allows to set different perimeter command modes for testing 1: Auto/none (null) 2: Full open 3: Full close Connected to CP MSV8 |
|
MSV23 |
40284 (283) |
TemperatureInputSelector |
N/a |
Read/write |
Panel |
Allows to choose the temperature source for control logic: 1: panel 2: input 3: network Connected to CP MSV15 |
|
MSV24 |
40285 (284) |
SetpointOffsetSelector |
N/a |
Read/write |
Panel |
Allows to choose the setpoint offset source for control logic: 1: panel 2: input 3: network Connected to CP MSV16 |
|
MSV25 |
40286 (285) |
PressureInputSelector |
N/a |
Read/write |
Input |
Allows to select the pressure source for control logic: 1: panel – not in use 2: input 3: network Connected to CP MSV17 |
|
MSO0 |
40291 (290) |
ReheaterStatus |
N/a |
Read/write |
Off |
Reheater staged control status (if configured as digital or staged) from application: 1: off 2: stage 1 on 3: stage 2 on |