State of Triac Outputs (40018)

This 16-bit register contains the state of triac outputs in digital mode. Setting a particular bit in the register activates the corresponding triac output according to the following table:

No. of Bit in the Register

No. of Triac Output

0

1

1

2

2

3

3

4

State of TO for 4TO-H and 4TO-H-IP

Default State of Triac Outputs (40143)

This 16-bit register contains the default state of the triac output device after the start or after resetting the watchdog.

The register bits correspond with triac outputs according to the following table:

No. of Bit in the Register

No. of Triac Output

0

1

1

2

2

3

3

4

Default state for 4TO-H and 4TO-H-IP

Value of 1-4 Triac PWM Outputs (40121-40124)

These 16-bit registers contain the value of the duty that appears on the PWM output (expressed in percents). Output working mode is defined by the CONFIGURATION mode of the triac output.

Default State of 1-4 Triac PWM Outputs (40145-40148)

These 16-bit registers contain the value of the duty that appears on the triac output (expressed in percents) after turning the power on or resetting the watchdog.

Configuration Mode of 1-4 Triac Outputs (40168-40171)

These 16-bit registers contain information about the mode of triac outputs according to the following table:

Register Value

Description

0 (default)

Digital Output

1

PWM 1Hz

2

PWM 10Hz

3

Not supported

4

PWM 0.1 HZ

5

PWM 0.01Hz

TO type settings

Hand Control Status of the Triac Outputs (30015)

This register is available only for modules with the manual control of outputs.

No. of Bit in the Register

Description

0,1

Hand status of outputs 1

2,3

Hand status of outputs 2

4,5

Hand status of outputs 3

6,7

Hand status of outputs 4

TO hand status bits

Value of Hand Status

Status Description

0

AUTO

2

HAND OUT = 0

3

HAND OUT = 1

TO hand status value