BACnet NameBACnet TypeIDAccessCOVDescriptionUI-1Analog Input0Read-onlyYesUniversal input current valueUI-2Analog Input1Read-onlyYesUI-3Analog Input2Read-onlyYesUI-4Analog Input3Read-onlyYesUI-5Analog Input4Read-onlyYesUI-6Analog Input5Read-onlyYesUI-7Analog Input6Read-onlyYesUI-8Analog Input7Read-onlyYesAO-1Analog Output0Read/writeYesAnalog output current valueAO-2Analog Output1Read/writeYesAO-3Analog Output2Read/writeYesAO-4Analog Output3Read/writeYesAO-5Analog Output4Read/writeYesAO-6Analog Output5Read/writeYesBI-1Binary Input0Read-onlyYesDigital input current valueBI-2Binary Input1Read-onlyYesBI-3Binary Input2Read-onlyYesBI-4Binary Input3Read-onlyYesBI-5Binary Input4Read-onlyYesBI-6Binary Input5Read-onlyYesBI-7Binary Input6Read-onlyYesBI-8Binary Input7Read-onlyYesBI-9Binary Input8Read-onlyYesBI-10Binary Input9Read-onlyYesBI-11Binary Input10Read-onlyYesBI-12Binary Input11Read-onlyYesFor 24I and 24I-IP onlyBI-13Binary Input12Read-onlyYesBI-14Binary Input13Read-onlyYesBI-15Binary Input14Read-onlyYesBI-16Binary Input15Read-onlyYesBI-17Binary Input16Read-onlyYesBI-18Binary Input17Read-onlyYesBI-19Binary Input18Read-onlyYesBI-20Binary Input19Read-onlyYesBI-21Binary Input20Read-onlyYesBI-22Binary Input21Read-onlyYesBI-23Binary Input22Read-onlyYesBI-24Binary Input23Read-onlyYesBO-1Binary Output0Read/writeYesDigital output current valueBO-2Binary Output1Read/writeYesBO-3Binary Output2Read/writeYesBO-4Binary Output3Read/writeYesBO-5Binary Output4Read/writeYesBO-6Binary Output5Read/writeYesBO-7Binary Output6Read/writeYesBO-8Binary Output7Read/writeYesBO-9Binary Output8Read/writeYesBO-10Binary Output9Read/writeYesBO-11Binary Output10Read/writeYesBO-12Binary Output11Read/writeYesUI-1_DRY_ CONTACTBinary Value0Read-onlyNoUniversal input dry contact binary valueUI-2_DRY_ CONTACTBinary Value1Read-onlyNoUI-3_DRY_ CONTACTBinary Value2Read-onlyNoUI-4_DRY_ CONTACTBinary Value3Read-onlyNoUI-5_DRY_ CONTACTBinary Value4Read-onlyNoUI-6_DRY_ CONTACTBinary Value5Read-onlyNoUI-7_DRY_ CONTACTBinary Value6Read-onlyNoUI-8_DRY_ CONTACTBinary Value7Read-onlyNoUP_TIMEAnalog Value0Read-onlyNoModule working time [s]WATCHDOGAnalog Value1Read/writeNoWatchdog time value [s]0 - disableBI-1_COUNTERAnalog Value2Read/writeNoDigital input counter valueAnalog Value BACnet object(The same function is also available using the Accumulator BACnet object.)BI-2_COUNTERAnalog Value3Read/writeNoBI-3_COUNTERAnalog Value4Read/writeNoBI-4_COUNTERAnalog Value5Read/writeNoBI-5_COUNTERAnalog Value6Read/writeNoBI-6_COUNTERAnalog Value7Read/writeNoBI-7_COUNTERAnalog Value8Read/writeNoBI-8_COUNTERAnalog Value9Read/writeNoBI-9_COUNTERAnalog Value10Read/writeNoBI-10_COUNTERAnalog Value11Read/writeNoBI-11_COUNTERAnalog Value12Read/writeNoBI-12_COUNTERAnalog Value13Read/writeNoFor 24I and 24I-IP onlyBI-13_COUNTERAnalog Value42Read/writeNoBI-14_COUNTERAnalog Value43Read/writeNoBI-15_COUNTERAnalog Value44Read/writeNoBI-16_COUNTERAnalog Value45Read/writeNoBI-17_COUNTERAnalog Value46Read/writeNoBI-18_COUNTERAnalog Value47Read/writeNoBI-19_COUNTERAnalog Value48Read/writeNoBI-20_COUNTERAnalog Value49Read/writeNoBI-21_COUNTERAnalog Value50Read/writeNoBI-22_COUNTERAnalog Value51Read/writeNoBI-23_COUNTERAnalog Value52Read/writeNoBI-24_COUNTERAnalog Value53Read/writeNoUI-1_FILTERAnalog Value14Read/writeNoUniversal input low pass filter time value(default value: 2 s)UI-2_FILTERAnalog Value15Read/writeNoUI-3_FILTERAnalog Value16Read/writeNoUI-4_FILTERAnalog Value17Read/writeNoUI-5_FILTERAnalog Value18Read/writeNoUI-6_FILTERAnalog Value19Read/writeNoUI-7_FILTERAnalog Value20Read/writeNoUI-8_FILTERAnalog Value21Read/writeNoAO-1_HAND_VALEAnalog Value22Read-onlyNoAnalog output value in hand mode valueAO-2_HAND_VALEAnalog Value23Read-onlyNoAO-3_HAND_VALEAnalog Value24Read-onlyNoAO-4_HAND_VALEAnalog Value25Read-onlyNoUI-1_CONFIGURATIONMultistate Value1Read/writeNoUniversal input configuration:- voltage- resistance- temperature sensor typeUI-2_CONFIGURATIONMultistate Value2Read/writeNoUI-3_CONFIGURATIONMultistate Value3Read/writeNoUI-4_CONFIGURATIONMultistate Value4Read/writeNoUI-5_CONFIGURATIONMultistate Value5Read/writeNoUI-6_CONFIGURATIONMultistate Value6Read/writeNoUI-7_CONFIGURATIONMultistate Value7Read/writeNoUI-8_CONFIGURATIONMultistate Value8Read/writeNoUI-1_RESOLUTIONMultistate Value9Read/writeNoUniversal input resolution:- 12-bit (default)- 16-bitUI-2_RESOLUTIONMultistate Value10Read/writeNoUI-3_RESOLUTIONMultistate Value11Read/writeNoUI-4_RESOLUTIONMultistate Value12Read/writeNoUI-5_RESOLUTIONMultistate Value13Read/writeNoUI-6_RESOLUTIONMultistate Value14Read/writeNoUI-7_RESOLUTIONMultistate Value15Read/writeNoUI-8_RESOLUTIONMultistate Value16Read/writeNoAO-1_CONFIGURATIONMultistate Value17Read/writeNoAnalog output working mode(default mode 0-10 V)AO-2_CONFIGURATIONMultistate Value18Read/writeNoAO-3_CONFIGURATIONMultistate Value19Read/writeNoAO-4_CONFIGURATIONMultistate Value20Read/writeNoAO-5_CONFIGURATIONMultistate Value21Read/writeNoAO-6_CONFIGURATIONMultistate Value22Read/writeNoAO-1_HAND_STATUSMultistate Value23Read-onlyNoAnalog output value in hand mode status: hand/autoAO-2_HAND_STATUSMultistate Value24Read-onlyNoAO-3_HAND_STATUSMultistate Value25Read-onlyNoAO-4_HAND_STATUSMultistate Value26Read-onlyNoBO-1_HAND_STATUSMultistate Value23Read-onlyNoDigital output value in hand mode status: hand/autoBO-2_HAND_STATUSMultistate Value24Read-onlyNoBO-3_HAND_STATUSMultistate Value25Read-onlyNoBO-4_HAND_STATUSMultistate Value26Read-onlyNoFor 12O-H and 12O-H-IP onlyBO-5_HAND_STATUSMultistate Value27Read-onlyNoBO-6_HAND_STATUSMultistate Value28Read-onlyNoBO-7_HAND_STATUSMultistate Value29Read-onlyNoBO-8_HAND_STATUSMultistate Value30Read-onlyNoBO-9_HAND_STATUSMultistate Value31Read-onlyNoBO-10_HAND_STATUSMultistate Value32Read-onlyNoBO-11_HAND_STATUSMultistate Value33Read-onlyNoBO-12_HAND_STATUSMultistate Value34Read-onlyNoBIA-1_COUNTERAccumulator0Read/writeNoDigital input counter valueAccumulator BACnet object(The same function is also available using the Analog Value BACnet object.BIA-2_COUNTERAccumulator1Read/writeNoBIA-3_COUNTERAccumulator2Read/writeNoBIA-4_COUNTERAccumulator3Read/writeNoBIA-5_COUNTERAccumulator4Read/writeNoBIA-6_COUNTERAccumulator5Read/writeNoBIA-7_COUNTERAccumulator6Read/writeNoBIA-8_COUNTERAccumulator7Read/writeNoBIA-9_COUNTERAccumulator8Read/writeNoBIA-10_COUNTERAccumulator9Read/writeNoBIA-11_COUNTERAccumulator10Read/writeNoBIA-12_COUNTERAccumulator11Read/writeNoFor 24I and 24I-IP onlyBIA-13_COUNTERAccumulator12Read/writeNoBIA-14_COUNTERAccumulator13Read/writeNoBIA-15_COUNTERAccumulator14Read/writeNoBIA-16_COUNTERAccumulator15Read/writeNoBIA-17_COUNTERAccumulator16Read/writeNoBIA-18_COUNTERAccumulator17Read/writeNoBIA-19_COUNTERAccumulator18Read/writeNoBIA-20_COUNTERAccumulator19Read/writeNoBIA-21_COUNTERAccumulator20Read/writeNoBIA-22_COUNTERAccumulator21Read/writeNoBIA-23_COUNTERAccumulator22Read/writeNoBIA-24_COUNTERAccumulator23Read/writeNoFor MINI 4TO-H and 4TO-H-IP onlyTO-1Binary Output0Read/writeYesTriac output current value (in digital output operation mode)TO-2Binary Output1Read/writeYesTO-3Binary Output2Read/writeYesTO-4Binary Output3Read/writeYesTO-1_PWM VALUEAnalog Output0Read/writeYesTriac output current value (in PWM operation mode)TO-2_PWM VALUEAnalog Output1Read/writeYesTO-3_PWM VALUEAnalog Output2Read/writeYesTO-4_PWM VALUEAnalog Output3Read/writeYesTO-1_CONFIGURATIONMultistate Value17Read/writeNoTriac output operation mode configuration, options:- digital output- PWMTO-1_CONFIGURATIONMultistate Value18Read/writeNoTO-1_CONFIGURATIONMultistate Value19Read/writeNoTO-1_CONFIGURATIONMultistate Value20Read/writeNoTO-1_ HAND_STATUSMultistate Value23Read-onlyNoTriac output hand mode statusTO-1_ HAND_STATUSMultistate Value24Read-onlyNoTO-1_ HAND_STATUSMultistate Value25Read-onlyNoTO-1_ HAND_STATUSMultistate Value26Read-onlyNoFor MINI 4I4O-H and 4I4O-H-IP onlyBI-1_INPUT_MODEMultistate Value27Read/writeNoOrdinary IO (def)Monostable RelayBistable RelayTime Relay NO [ms]Time Relay NC [ms]Time Relay NO [s]Time Relay NC [s]Input Forwarding(4U4O-H, 4U4O-H-IP only)HeatingCoolingBI-2_INPUT_MODEMultistate Value28Read/writeNoBI-3_INPUT_MODEMultistate Value29Read/writeNoBI-4_INPUT_MODEMultistate Value30Read/writeNoBI-1_MODE_TIMEAnalog Value26Read/writeNoTime Value object for Time Relay ModeBI-2_MODE_TIMEAnalog Value27Read/writeNoBI-3_MODE_TIMEAnalog Value28Read/writeNoBI-4_MODE_TIMEAnalog Value29Read/writeNoBI-1_BLOCK_INPUTBinary Value12Read/writeNoDigital input blocking commandBI-2_BLOCK_INPUTBinary Value13Read/writeNoBI-3_BLOCK_INPUTBinary Value14Read/writeNoBI-4_BLOCK_INPUTBinary Value15Read/writeNoBI-1_COMMANDBinary Value8Read/writeNoDigital input remote commandBI-2_COMMANDBinary Value9Read/writeNoBI-3_COMMANDBinary Value10Read/writeNoBI-4_COMMANDBinary Value11Read/writeNoFor MINI 4U4O-H and 4U4O-H-IP onlyBI-1_SETPOINTAnalog Value30Read/writeNoSETPOINT for heating/cooling modesDefault: 0BI-2_SETPOINTAnalog Value31Read/writeNoBI-3_SETPOINTAnalog Value32Read/writeNoBI-4_SETPOINTAnalog Value33Read/writeNoBI-1_DIFFERENTIALAnalog Value34Read/writeNoDIFFERENTIAL for heating/cooling modesDefault: 0BI-2_ DIFFERENTIALAnalog Value35Read/writeNoBI-3_ DIFFERENTIALAnalog Value36Read/writeNoBI-4_ DIFFERENTIALAnalog Value37Read/writeNoList of BACnet objects