List of BACnet Objects
BACnet Name | BACnet Type | ID | Access | COV | Description |
---|---|---|---|---|---|
UI-1 | Analog Input | 0 | Read-only | Yes | Universal input current value |
UI-2 | Analog Input | 1 | Read-only | Yes | |
UI-3 | Analog Input | 2 | Read-only | Yes | |
UI-4 | Analog Input | 3 | Read-only | Yes | |
UI-5 | Analog Input | 4 | Read-only | Yes | |
UI-6 | Analog Input | 5 | Read-only | Yes | |
UI-7 | Analog Input | 6 | Read-only | Yes | |
UI-8 | Analog Input | 7 | Read-only | Yes | |
AO-1 | Analog Output | 0 | Read/write | Yes | Analog output current value |
AO-2 | Analog Output | 1 | Read/write | Yes | |
AO-3 | Analog Output | 2 | Read/write | Yes | |
AO-4 | Analog Output | 3 | Read/write | Yes | |
AO-5 | Analog Output | 4 | Read/write | Yes | |
AO-6 | Analog Output | 5 | Read/write | Yes | |
BI-1 | Binary Input | 0 | Read-only | Yes | Digital input current value |
BI-2 | Binary Input | 1 | Read-only | Yes | |
BI-3 | Binary Input | 2 | Read-only | Yes | |
BI-4 | Binary Input | 3 | Read-only | Yes | |
BI-5 | Binary Input | 4 | Read-only | Yes | |
BI-6 | Binary Input | 5 | Read-only | Yes | |
BI-7 | Binary Input | 6 | Read-only | Yes | |
BI-8 | Binary Input | 7 | Read-only | Yes | |
BI-9 | Binary Input | 8 | Read-only | Yes | |
BI-10 | Binary Input | 9 | Read-only | Yes | |
BI-11 | Binary Input | 10 | Read-only | Yes | |
BI-12 | Binary Input | 11 | Read-only | Yes | |
For 24I and 24I-IP only | |||||
BI-13 | Binary Input | 12 | Read-only | Yes | |
BI-14 | Binary Input | 13 | Read-only | Yes | |
BI-15 | Binary Input | 14 | Read-only | Yes | |
BI-16 | Binary Input | 15 | Read-only | Yes | |
BI-17 | Binary Input | 16 | Read-only | Yes | |
BI-18 | Binary Input | 17 | Read-only | Yes | |
BI-19 | Binary Input | 18 | Read-only | Yes | |
BI-20 | Binary Input | 19 | Read-only | Yes | |
BI-21 | Binary Input | 20 | Read-only | Yes | |
BI-22 | Binary Input | 21 | Read-only | Yes | |
BI-23 | Binary Input | 22 | Read-only | Yes | |
BI-24 | Binary Input | 23 | Read-only | Yes | |
BO-1 | Binary Output | 0 | Read/write | Yes | Digital output current value |
BO-2 | Binary Output | 1 | Read/write | Yes | |
BO-3 | Binary Output | 2 | Read/write | Yes | |
BO-4 | Binary Output | 3 | Read/write | Yes | |
BO-5 | Binary Output | 4 | Read/write | Yes | |
BO-6 | Binary Output | 5 | Read/write | Yes | |
BO-7 | Binary Output | 6 | Read/write | Yes | |
BO-8 | Binary Output | 7 | Read/write | Yes | |
BO-9 | Binary Output | 8 | Read/write | Yes | |
BO-10 | Binary Output | 9 | Read/write | Yes | |
BO-11 | Binary Output | 10 | Read/write | Yes | |
BO-12 | Binary Output | 11 | Read/write | Yes | |
UI-1_DRY_ CONTACT | Binary Value | 0 | Read-only | No | Universal input dry contact binary value |
UI-2_DRY_ CONTACT | Binary Value | 1 | Read-only | No | |
UI-3_DRY_ CONTACT | Binary Value | 2 | Read-only | No | |
UI-4_DRY_ CONTACT | Binary Value | 3 | Read-only | No | |
UI-5_DRY_ CONTACT | Binary Value | 4 | Read-only | No | |
UI-6_DRY_ CONTACT | Binary Value | 5 | Read-only | No | |
UI-7_DRY_ CONTACT | Binary Value | 6 | Read-only | No | |
UI-8_DRY_ CONTACT | Binary Value | 7 | Read-only | No | |
UP_TIME | Analog Value | 0 | Read-only | No | Module working time [s] |
WATCHDOG | Analog Value | 1 | Read/write | No | Watchdog time value [s] |
BI-1_COUNTER | Analog Value | 2 | Read/write | No | Digital input counter value |
BI-2_COUNTER | Analog Value | 3 | Read/write | No | |
BI-3_COUNTER | Analog Value | 4 | Read/write | No | |
BI-4_COUNTER | Analog Value | 5 | Read/write | No | |
BI-5_COUNTER | Analog Value | 6 | Read/write | No | |
BI-6_COUNTER | Analog Value | 7 | Read/write | No | |
BI-7_COUNTER | Analog Value | 8 | Read/write | No | |
BI-8_COUNTER | Analog Value | 9 | Read/write | No | |
BI-9_COUNTER | Analog Value | 10 | Read/write | No | |
BI-10_COUNTER | Analog Value | 11 | Read/write | No | |
BI-11_COUNTER | Analog Value | 12 | Read/write | No | |
BI-12_COUNTER | Analog Value | 13 | Read/write | No | |
For 24I and 24I-IP only | |||||
BI-13_COUNTER | Analog Value | 42 | Read/write | No | |
BI-14_COUNTER | Analog Value | 43 | Read/write | No | |
BI-15_COUNTER | Analog Value | 44 | Read/write | No | |
BI-16_COUNTER | Analog Value | 45 | Read/write | No | |
BI-17_COUNTER | Analog Value | 46 | Read/write | No | |
BI-18_COUNTER | Analog Value | 47 | Read/write | No | |
BI-19_COUNTER | Analog Value | 48 | Read/write | No | |
BI-20_COUNTER | Analog Value | 49 | Read/write | No | |
BI-21_COUNTER | Analog Value | 50 | Read/write | No | |
BI-22_COUNTER | Analog Value | 51 | Read/write | No | |
BI-23_COUNTER | Analog Value | 52 | Read/write | No | |
BI-24_COUNTER | Analog Value | 53 | Read/write | No | |
UI-1_FILTER | Analog Value | 14 | Read/write | No | Universal input low pass filter time value |
UI-2_FILTER | Analog Value | 15 | Read/write | No | |
UI-3_FILTER | Analog Value | 16 | Read/write | No | |
UI-4_FILTER | Analog Value | 17 | Read/write | No | |
UI-5_FILTER | Analog Value | 18 | Read/write | No | |
UI-6_FILTER | Analog Value | 19 | Read/write | No | |
UI-7_FILTER | Analog Value | 20 | Read/write | No | |
UI-8_FILTER | Analog Value | 21 | Read/write | No | |
AO-1_HAND_VALE | Analog Value | 22 | Read-only | No | Analog output value in hand mode value |
AO-2_HAND_VALE | Analog Value | 23 | Read-only | No | |
AO-3_HAND_VALE | Analog Value | 24 | Read-only | No | |
AO-4_HAND_VALE | Analog Value | 25 | Read-only | No | |
UI-1_CONFIGURATION | Multistate Value | 1 | Read/write | No | Universal input configuration: |
UI-2_CONFIGURATION | Multistate Value | 2 | Read/write | No | |
UI-3_CONFIGURATION | Multistate Value | 3 | Read/write | No | |
UI-4_CONFIGURATION | Multistate Value | 4 | Read/write | No | |
UI-5_CONFIGURATION | Multistate Value | 5 | Read/write | No | |
UI-6_CONFIGURATION | Multistate Value | 6 | Read/write | No | |
UI-7_CONFIGURATION | Multistate Value | 7 | Read/write | No | |
UI-8_CONFIGURATION | Multistate Value | 8 | Read/write | No | |
UI-1_RESOLUTION | Multistate Value | 9 | Read/write | No | Universal input resolution: |
UI-2_RESOLUTION | Multistate Value | 10 | Read/write | No | |
UI-3_RESOLUTION | Multistate Value | 11 | Read/write | No | |
UI-4_RESOLUTION | Multistate Value | 12 | Read/write | No | |
UI-5_RESOLUTION | Multistate Value | 13 | Read/write | No | |
UI-6_RESOLUTION | Multistate Value | 14 | Read/write | No | |
UI-7_RESOLUTION | Multistate Value | 15 | Read/write | No | |
UI-8_RESOLUTION | Multistate Value | 16 | Read/write | No | |
AO-1_CONFIGURATION | Multistate Value | 17 | Read/write | No | Analog output working mode |
AO-2_CONFIGURATION | Multistate Value | 18 | Read/write | No | |
AO-3_CONFIGURATION | Multistate Value | 19 | Read/write | No | |
AO-4_CONFIGURATION | Multistate Value | 20 | Read/write | No | |
AO-5_CONFIGURATION | Multistate Value | 21 | Read/write | No | |
AO-6_CONFIGURATION | Multistate Value | 22 | Read/write | No | |
AO-1_HAND_STATUS | Multistate Value | 23 | Read-only | No | Analog output value in hand mode status: hand/auto |
AO-2_HAND_STATUS | Multistate Value | 24 | Read-only | No | |
AO-3_HAND_STATUS | Multistate Value | 25 | Read-only | No | |
AO-4_HAND_STATUS | Multistate Value | 26 | Read-only | No | |
BO-1_HAND_STATUS | Multistate Value | 23 | Read-only | No | Digital output value in hand mode status: hand/auto |
BO-2_HAND_STATUS | Multistate Value | 24 | Read-only | No | |
BO-3_HAND_STATUS | Multistate Value | 25 | Read-only | No | |
BO-4_HAND_STATUS | Multistate Value | 26 | Read-only | No | |
For 12O-H and 12O-H-IP only | |||||
BO-5_HAND_STATUS | Multistate Value | 27 | Read-only | No | |
BO-6_HAND_STATUS | Multistate Value | 28 | Read-only | No | |
BO-7_HAND_STATUS | Multistate Value | 29 | Read-only | No | |
BO-8_HAND_STATUS | Multistate Value | 30 | Read-only | No | |
BO-9_HAND_STATUS | Multistate Value | 31 | Read-only | No | |
BO-10_HAND_STATUS | Multistate Value | 32 | Read-only | No | |
BO-11_HAND_STATUS | Multistate Value | 33 | Read-only | No | |
BO-12_HAND_STATUS | Multistate Value | 34 | Read-only | No | |
BIA-1_COUNTER | Accumulator | 0 | Read/write | No | Digital input counter value |
BIA-2_COUNTER | Accumulator | 1 | Read/write | No | |
BIA-3_COUNTER | Accumulator | 2 | Read/write | No | |
BIA-4_COUNTER | Accumulator | 3 | Read/write | No | |
BIA-5_COUNTER | Accumulator | 4 | Read/write | No | |
BIA-6_COUNTER | Accumulator | 5 | Read/write | No | |
BIA-7_COUNTER | Accumulator | 6 | Read/write | No | |
BIA-8_COUNTER | Accumulator | 7 | Read/write | No | |
BIA-9_COUNTER | Accumulator | 8 | Read/write | No | |
BIA-10_COUNTER | Accumulator | 9 | Read/write | No | |
BIA-11_COUNTER | Accumulator | 10 | Read/write | No | |
BIA-12_COUNTER | Accumulator | 11 | Read/write | No | |
For 24I and 24I-IP only | |||||
BIA-13_COUNTER | Accumulator | 12 | Read/write | No | |
BIA-14_COUNTER | Accumulator | 13 | Read/write | No | |
BIA-15_COUNTER | Accumulator | 14 | Read/write | No | |
BIA-16_COUNTER | Accumulator | 15 | Read/write | No | |
BIA-17_COUNTER | Accumulator | 16 | Read/write | No | |
BIA-18_COUNTER | Accumulator | 17 | Read/write | No | |
BIA-19_COUNTER | Accumulator | 18 | Read/write | No | |
BIA-20_COUNTER | Accumulator | 19 | Read/write | No | |
BIA-21_COUNTER | Accumulator | 20 | Read/write | No | |
BIA-22_COUNTER | Accumulator | 21 | Read/write | No | |
BIA-23_COUNTER | Accumulator | 22 | Read/write | No | |
BIA-24_COUNTER | Accumulator | 23 | Read/write | No | |
For MINI 4TO-H and 4TO-H-IP only | |||||
TO-1 | Binary Output | 0 | Read/write | Yes | Triac output current value (in digital output operation mode) |
TO-2 | Binary Output | 1 | Read/write | Yes | |
TO-3 | Binary Output | 2 | Read/write | Yes | |
TO-4 | Binary Output | 3 | Read/write | Yes | |
TO-1_PWM VALUE | Analog Output | 0 | Read/write | Yes | Triac output current value (in PWM operation mode) |
TO-2_PWM VALUE | Analog Output | 1 | Read/write | Yes | |
TO-3_PWM VALUE | Analog Output | 2 | Read/write | Yes | |
TO-4_PWM VALUE | Analog Output | 3 | Read/write | Yes | |
TO-1_CONFIGURATION | Multistate Value | 17 | Read/write | No | Triac output operation mode configuration, options: |
TO-1_CONFIGURATION | Multistate Value | 18 | Read/write | No | |
TO-1_CONFIGURATION | Multistate Value | 19 | Read/write | No | |
TO-1_CONFIGURATION | Multistate Value | 20 | Read/write | No | |
TO-1_ HAND_STATUS | Multistate Value | 23 | Read-only | No | Triac output hand mode status |
TO-1_ HAND_STATUS | Multistate Value | 24 | Read-only | No | |
TO-1_ HAND_STATUS | Multistate Value | 25 | Read-only | No | |
TO-1_ HAND_STATUS | Multistate Value | 26 | Read-only | No | |
For MINI 4I4O-H and 4I4O-H-IP only | |||||
BI-1_INPUT_MODE | Multistate Value | 27 | Read/write | No | Ordinary IO (def) Monostable Relay Bistable Relay Time Relay NO [ms] Time Relay NC [ms] Time Relay NO [s] Time Relay NC [s] Input Forwarding (4U4O-H, 4U4O-H-IP only) Heating Cooling |
BI-2_INPUT_MODE | Multistate Value | 28 | Read/write | No | |
BI-3_INPUT_MODE | Multistate Value | 29 | Read/write | No | |
BI-4_INPUT_MODE | Multistate Value | 30 | Read/write | No | |
BI-1_MODE_TIME | Analog Value | 26 | Read/write | No | Time Value object for Time Relay Mode |
BI-2_MODE_TIME | Analog Value | 27 | Read/write | No | |
BI-3_MODE_TIME | Analog Value | 28 | Read/write | No | |
BI-4_MODE_TIME | Analog Value | 29 | Read/write | No | |
BI-1_BLOCK_INPUT | Binary Value | 12 | Read/write | No | Digital input blocking command |
BI-2_BLOCK_INPUT | Binary Value | 13 | Read/write | No | |
BI-3_BLOCK_INPUT | Binary Value | 14 | Read/write | No | |
BI-4_BLOCK_INPUT | Binary Value | 15 | Read/write | No | |
BI-1_COMMAND | Binary Value | 8 | Read/write | No | Digital input remote command |
BI-2_COMMAND | Binary Value | 9 | Read/write | No | |
BI-3_COMMAND | Binary Value | 10 | Read/write | No | |
BI-4_COMMAND | Binary Value | 11 | Read/write | No | |
For MINI 4U4O-H and 4U4O-H-IP only | |||||
BI-1_SETPOINT | Analog Value | 30 | Read/write | No | SETPOINT for heating/cooling modes Default: 0 |
BI-2_SETPOINT | Analog Value | 31 | Read/write | No | |
BI-3_SETPOINT | Analog Value | 32 | Read/write | No | |
BI-4_SETPOINT | Analog Value | 33 | Read/write | No | |
BI-1_DIFFERENTIAL | Analog Value | 34 | Read/write | No | DIFFERENTIAL for heating/cooling modes Default: 0 |
BI-2_ DIFFERENTIAL | Analog Value | 35 | Read/write | No | |
BI-3_ DIFFERENTIAL | Analog Value | 36 | Read/write | No | |
BI-4_ DIFFERENTIAL | Analog Value | 37 | Read/write | No |