In its out-of-the-box state, as well as after restoring the default values, the device has the following default register values:

Register Name

Default Value

COUNTER 1-12

0

COUNTER 12-24 (24I and 24I-IP)0

USER BAUD RATE

7680 (76800 bps)

STOP BITS

1

DATA BITS

8

PARITY BITS

0

RESPONSE DELAY

0

WATCHDOG TIME

0 (disabled)

DEFAULT STATE OF DIGITAL OUTPUTS (1-12)

0

DEFAULT STATE OF THE ANALOG OUTPUTS (DIGITAL 1-6)

0

DEFAULT STATE OF THE ANALOG OUTPUTS (1-6)

0

UNIVERSAL INPUT CONFIGURATION (1-8)

3 (10K3A1 NTC (°C))

INPUT FILTER TIME CONSTANT (1-8)

2

UNIVERSAL INPUT RESOLUTION (1-8)

1 (12-bit)

ANALOG OUTPUT CONFIGURATION (1-6)

1 (voltage)

COV INCREMENT (BACnet only)

1

Only for IP Modules

USERNAME

admin

PASSWORD

1000

IP ADDRESS

192.168.1.123

MASK

255.255.255.0

GATEWAY

192.168.1.1

DHCPDisabled

HTTP PORT

80

MODBUS TCP PORT

502

MODBUS TCP TIMEOUT

60 s

RS485 TIMEOUT

500 ms

RS485 BIASING RESISTORS (MINI only)

DISABLED

SEND MODBUS ERRORS

ENABLED

BACNET ID

826+rotary switch value (for example, 826001)

BACNET UDP PORT

47808 (0xBAC0)

Default values


Restoring Default Settings

To restore the default configuration of all registers, follow the steps below:

  • turn off the power supply;
  • set section 6 of the S3 switch to on;
  • turn on the power supply, the power LED will start blinking;
  • switch section 6 of the S3 switch to off to restore the default settings. To cancel the reset, turn off the power, and switch section 6 of the S3 switch to the off position.