| BACnet Name | BACnet Type | ID | Access | COV | Description |
|---|---|---|---|---|---|
|
UI-1 |
Analog Input |
0 |
Read-only |
Yes |
Universal input current value |
|
UI-2 |
Analog Input |
1 |
Read-only |
Yes |
|
|
UI-3 |
Analog Input |
2 |
Read-only |
Yes |
|
|
UI-4 |
Analog Input |
3 |
Read-only |
Yes |
|
|
UI-5 |
Analog Input |
4 |
Read-only |
Yes |
|
|
UI-6 |
Analog Input |
5 |
Read-only |
Yes |
|
|
UI-7 |
Analog Input |
6 |
Read-only |
Yes |
|
|
UI-8 |
Analog Input |
7 |
Read-only |
Yes |
|
|
AO-1 |
Analog Output |
0 |
Read/write |
Yes |
Analog output current value |
|
AO-2 |
Analog Output |
1 |
Read/write |
Yes |
|
|
AO-3 |
Analog Output |
2 |
Read/write |
Yes |
|
|
AO-4 |
Analog Output |
3 |
Read/write |
Yes |
|
|
AO-5 |
Analog Output |
4 |
Read/write |
Yes |
|
|
AO-6 |
Analog Output |
5 |
Read/write |
Yes |
|
|
BI-1 |
Binary Input |
0 |
Read-only |
Yes |
Digital input current value |
|
BI-2 |
Binary Input |
1 |
Read-only |
Yes |
|
|
BI-3 |
Binary Input |
2 |
Read-only |
Yes |
|
|
BI-4 |
Binary Input |
3 |
Read-only |
Yes |
|
|
BI-5 |
Binary Input |
4 |
Read-only |
Yes |
|
|
BI-6 |
Binary Input |
5 |
Read-only |
Yes |
|
|
BI-7 |
Binary Input |
6 |
Read-only |
Yes |
|
|
BI-8 |
Binary Input |
7 |
Read-only |
Yes |
|
|
BI-9 |
Binary Input |
8 |
Read-only |
Yes |
|
|
BI-10 |
Binary Input |
9 |
Read-only |
Yes |
|
|
BI-11 |
Binary Input |
10 |
Read-only |
Yes |
|
|
BI-12 |
Binary Input |
11 |
Read-only |
Yes |
|
| For 24I and 24I-IP only | |||||
| BI-13 | Binary Input | 12 | Read-only | Yes | |
| BI-14 | Binary Input | 13 | Read-only | Yes | |
| BI-15 | Binary Input | 14 | Read-only | Yes | |
| BI-16 | Binary Input | 15 | Read-only | Yes | |
| BI-17 | Binary Input | 16 | Read-only | Yes | |
| BI-18 | Binary Input | 17 | Read-only | Yes | |
| BI-19 | Binary Input | 18 | Read-only | Yes | |
| BI-20 | Binary Input | 19 | Read-only | Yes | |
| BI-21 | Binary Input | 20 | Read-only | Yes | |
| BI-22 | Binary Input | 21 | Read-only | Yes | |
| BI-23 | Binary Input | 22 | Read-only | Yes | |
| BI-24 | Binary Input | 23 | Read-only | Yes | |
|
BO-1 |
Binary Output |
0 |
Read/write |
Yes |
Digital output current value |
|
BO-2 |
Binary Output |
1 |
Read/write |
Yes |
|
|
BO-3 |
Binary Output |
2 |
Read/write |
Yes |
|
|
BO-4 |
Binary Output |
3 |
Read/write |
Yes |
|
|
BO-5 |
Binary Output |
4 |
Read/write |
Yes |
|
|
BO-6 |
Binary Output |
5 |
Read/write |
Yes |
|
|
BO-7 |
Binary Output |
6 |
Read/write |
Yes |
|
|
BO-8 |
Binary Output |
7 |
Read/write |
Yes |
|
|
BO-9 |
Binary Output |
8 |
Read/write |
Yes |
|
|
BO-10 |
Binary Output |
9 |
Read/write |
Yes |
|
|
BO-11 |
Binary Output |
10 |
Read/write |
Yes |
|
|
BO-12 |
Binary Output |
11 |
Read/write |
Yes |
|
|
UI-1_DRY_ CONTACT |
Binary Value |
0 |
Read-only |
No |
Universal input dry contact binary value |
|
UI-2_DRY_ CONTACT |
Binary Value |
1 |
Read-only |
No |
|
|
UI-3_DRY_ CONTACT |
Binary Value |
2 |
Read-only |
No |
|
|
UI-4_DRY_ CONTACT |
Binary Value |
3 |
Read-only |
No |
|
|
UI-5_DRY_ CONTACT |
Binary Value |
4 |
Read-only |
No |
|
|
UI-6_DRY_ CONTACT |
Binary Value |
5 |
Read-only |
No |
|
|
UI-7_DRY_ CONTACT |
Binary Value |
6 |
Read-only |
No |
|
|
UI-8_DRY_ CONTACT |
Binary Value |
7 |
Read-only |
No |
|
|
UP_TIME |
Analog Value |
0 |
Read-only |
No |
Module working time [s] |
|
WATCHDOG |
Analog Value |
1 |
Read/write |
No |
Watchdog time value [s]
|
|
BI-1_COUNTER |
Analog Value |
2 |
Read/write |
No |
Digital input counter value
|
|
BI-2_COUNTER |
Analog Value |
3 |
Read/write |
No |
|
|
BI-3_COUNTER |
Analog Value |
4 |
Read/write |
No |
|
|
BI-4_COUNTER |
Analog Value |
5 |
Read/write |
No |
|
|
BI-5_COUNTER |
Analog Value |
6 |
Read/write |
No |
|
|
BI-6_COUNTER |
Analog Value |
7 |
Read/write |
No |
|
|
BI-7_COUNTER |
Analog Value |
8 |
Read/write |
No |
|
|
BI-8_COUNTER |
Analog Value |
9 |
Read/write |
No |
|
|
BI-9_COUNTER |
Analog Value |
10 |
Read/write |
No |
|
|
BI-10_COUNTER |
Analog Value |
11 |
Read/write |
No |
|
|
BI-11_COUNTER |
Analog Value |
12 |
Read/write |
No |
|
|
BI-12_COUNTER |
Analog Value |
13 |
Read/write |
No |
|
| For 24I and 24I-IP only | |||||
| BI-13_COUNTER | Analog Value | 42 | Read/write | No | |
| BI-14_COUNTER | Analog Value | 43 | Read/write | No | |
| BI-15_COUNTER | Analog Value | 44 | Read/write | No | |
| BI-16_COUNTER | Analog Value | 45 | Read/write | No | |
| BI-17_COUNTER | Analog Value | 46 | Read/write | No | |
| BI-18_COUNTER | Analog Value | 47 | Read/write | No | |
| BI-19_COUNTER | Analog Value | 48 | Read/write | No | |
| BI-20_COUNTER | Analog Value | 49 | Read/write | No | |
| BI-21_COUNTER | Analog Value | 50 | Read/write | No | |
| BI-22_COUNTER | Analog Value | 51 | Read/write | No | |
| BI-23_COUNTER | Analog Value | 52 | Read/write | No | |
| BI-24_COUNTER | Analog Value | 53 | Read/write | No | |
|
UI-1_FILTER |
Analog Value |
14 |
Read/write |
No |
Universal input low pass filter time value
|
|
UI-2_FILTER |
Analog Value |
15 |
Read/write |
No |
|
|
UI-3_FILTER |
Analog Value |
16 |
Read/write |
No |
|
|
UI-4_FILTER |
Analog Value |
17 |
Read/write |
No |
|
|
UI-5_FILTER |
Analog Value |
18 |
Read/write |
No |
|
|
UI-6_FILTER |
Analog Value |
19 |
Read/write |
No |
|
|
UI-7_FILTER |
Analog Value |
20 |
Read/write |
No |
|
|
UI-8_FILTER |
Analog Value |
21 |
Read/write |
No |
|
|
AO-1_HAND_VALE |
Analog Value |
22 |
Read-only |
No |
Analog output value in hand mode value |
|
AO-2_HAND_VALE |
Analog Value |
23 |
Read-only |
No |
|
|
AO-3_HAND_VALE |
Analog Value |
24 |
Read-only |
No |
|
|
AO-4_HAND_VALE |
Analog Value |
25 |
Read-only |
No |
|
|
UI-1_CONFIGURATION |
Multistate Value |
1 |
Read/write |
No |
Universal input configuration:
|
|
UI-2_CONFIGURATION |
Multistate Value |
2 |
Read/write |
No |
|
|
UI-3_CONFIGURATION |
Multistate Value |
3 |
Read/write |
No |
|
|
UI-4_CONFIGURATION |
Multistate Value |
4 |
Read/write |
No |
|
|
UI-5_CONFIGURATION |
Multistate Value |
5 |
Read/write |
No |
|
|
UI-6_CONFIGURATION |
Multistate Value |
6 |
Read/write |
No |
|
|
UI-7_CONFIGURATION |
Multistate Value |
7 |
Read/write |
No |
|
|
UI-8_CONFIGURATION |
Multistate Value |
8 |
Read/write |
No |
|
|
UI-1_RESOLUTION |
Multistate Value |
9 |
Read/write |
No |
Universal input resolution:
|
|
UI-2_RESOLUTION |
Multistate Value |
10 |
Read/write |
No |
|
|
UI-3_RESOLUTION |
Multistate Value |
11 |
Read/write |
No |
|
|
UI-4_RESOLUTION |
Multistate Value |
12 |
Read/write |
No |
|
|
UI-5_RESOLUTION |
Multistate Value |
13 |
Read/write |
No |
|
|
UI-6_RESOLUTION |
Multistate Value |
14 |
Read/write |
No |
|
|
UI-7_RESOLUTION |
Multistate Value |
15 |
Read/write |
No |
|
|
UI-8_RESOLUTION |
Multistate Value |
16 |
Read/write |
No |
|
|
AO-1_CONFIGURATION |
Multistate Value |
17 |
Read/write |
No |
Analog output working mode
|
|
AO-2_CONFIGURATION |
Multistate Value |
18 |
Read/write |
No |
|
|
AO-3_CONFIGURATION |
Multistate Value |
19 |
Read/write |
No |
|
|
AO-4_CONFIGURATION |
Multistate Value |
20 |
Read/write |
No |
|
|
AO-5_CONFIGURATION |
Multistate Value |
21 |
Read/write |
No |
|
|
AO-6_CONFIGURATION |
Multistate Value |
22 |
Read/write |
No |
|
|
AO-1_HAND_STATUS |
Multistate Value |
23 |
Read-only |
No |
Analog output value in hand mode status: hand/auto |
|
AO-2_HAND_STATUS |
Multistate Value |
24 |
Read-only |
No |
|
|
AO-3_HAND_STATUS |
Multistate Value |
25 |
Read-only |
No |
|
|
AO-4_HAND_STATUS |
Multistate Value |
26 |
Read-only |
No |
|
|
BO-1_HAND_STATUS |
Multistate Value |
23 |
Read-only |
No |
Digital output value in hand mode status: hand/auto |
| BO-2_HAND_STATUS | Multistate Value | 24 | Read-only | No | |
|
BO-3_HAND_STATUS |
Multistate Value |
25 |
Read-only |
No |
|
|
BO-4_HAND_STATUS |
Multistate Value |
26 |
Read-only |
No |
|
| For 12O-H and 12O-H-IP only | |||||
| BO-5_HAND_STATUS | Multistate Value | 27 | Read-only | No | |
| BO-6_HAND_STATUS | Multistate Value | 28 | Read-only | No | |
| BO-7_HAND_STATUS | Multistate Value | 29 | Read-only | No | |
| BO-8_HAND_STATUS | Multistate Value | 30 | Read-only | No | |
| BO-9_HAND_STATUS | Multistate Value | 31 | Read-only | No | |
| BO-10_HAND_STATUS | Multistate Value | 32 | Read-only | No | |
| BO-11_HAND_STATUS | Multistate Value | 33 | Read-only | No | |
| BO-12_HAND_STATUS | Multistate Value | 34 | Read-only | No | |
|
BIA-1_COUNTER |
Accumulator |
0 |
Read/write |
No |
Digital input counter value
|
|
BIA-2_COUNTER |
Accumulator |
1 |
Read/write |
No |
|
|
BIA-3_COUNTER |
Accumulator |
2 |
Read/write |
No |
|
|
BIA-4_COUNTER |
Accumulator |
3 |
Read/write |
No |
|
|
BIA-5_COUNTER |
Accumulator |
4 |
Read/write |
No |
|
|
BIA-6_COUNTER |
Accumulator |
5 |
Read/write |
No |
|
|
BIA-7_COUNTER |
Accumulator |
6 |
Read/write |
No |
|
|
BIA-8_COUNTER |
Accumulator |
7 |
Read/write |
No |
|
|
BIA-9_COUNTER |
Accumulator |
8 |
Read/write |
No |
|
|
BIA-10_COUNTER |
Accumulator |
9 |
Read/write |
No |
|
|
BIA-11_COUNTER |
Accumulator |
10 |
Read/write |
No |
|
|
BIA-12_COUNTER |
Accumulator |
11 |
Read/write |
No |
|
| For 24I and 24I-IP only | |||||
| BIA-13_COUNTER | Accumulator | 12 | Read/write | No | |
| BIA-14_COUNTER | Accumulator | 13 | Read/write | No | |
| BIA-15_COUNTER | Accumulator | 14 | Read/write | No | |
| BIA-16_COUNTER | Accumulator | 15 | Read/write | No | |
| BIA-17_COUNTER | Accumulator | 16 | Read/write | No | |
| BIA-18_COUNTER | Accumulator | 17 | Read/write | No | |
| BIA-19_COUNTER | Accumulator | 18 | Read/write | No | |
| BIA-20_COUNTER | Accumulator | 19 | Read/write | No | |
| BIA-21_COUNTER | Accumulator | 20 | Read/write | No | |
| BIA-22_COUNTER | Accumulator | 21 | Read/write | No | |
| BIA-23_COUNTER | Accumulator | 22 | Read/write | No | |
| BIA-24_COUNTER | Accumulator | 23 | Read/write | No | |
|
For MINI 4TO-H and 4TO-H-IP only |
|||||
|
TO-1 |
Binary Output |
0 |
Read/write |
Yes |
Triac output current value (in digital output operation mode) |
|
TO-2 |
Binary Output |
1 |
Read/write |
Yes |
|
|
TO-3 |
Binary Output |
2 |
Read/write |
Yes |
|
|
TO-4 |
Binary Output |
3 |
Read/write |
Yes |
|
|
TO-1_PWM VALUE |
Analog Output |
0 |
Read/write |
Yes |
Triac output current value (in PWM operation mode) |
|
TO-2_PWM VALUE |
Analog Output |
1 |
Read/write |
Yes |
|
|
TO-3_PWM VALUE |
Analog Output |
2 |
Read/write |
Yes |
|
|
TO-4_PWM VALUE |
Analog Output |
3 |
Read/write |
Yes |
|
|
TO-1_CONFIGURATION |
Multistate Value |
17 |
Read/write |
No |
Triac output operation mode configuration, options:
|
|
TO-1_CONFIGURATION |
Multistate Value |
18 |
Read/write |
No |
|
|
TO-1_CONFIGURATION |
Multistate Value |
19 |
Read/write |
No |
|
|
TO-1_CONFIGURATION |
Multistate Value |
20 |
Read/write |
No |
|
|
TO-1_ HAND_STATUS |
Multistate Value |
23 |
Read-only |
No |
Triac output hand mode status |
|
TO-1_ HAND_STATUS |
Multistate Value |
24 |
Read-only |
No |
|
|
TO-1_ HAND_STATUS |
Multistate Value |
25 |
Read-only |
No |
|
|
TO-1_ HAND_STATUS |
Multistate Value |
26 |
Read-only |
No |
|
|
For MINI 4I4O-H/4I4O-H-IP and 4U4O-H/4U4O-H-IP only |
|||||
|
BI-1_INPUT_MODE |
Multistate Value |
27 |
Read/write |
No |
Ordinary IO (def) Monostable Relay Bistable Relay Time Relay NO [ms] Time Relay NC [ms] Time Relay NO [s] Time Relay NC [s] Input Forwarding (4U4O-H, 4U4O-H-IP only) Heating Cooling |
|
BI-2_INPUT_MODE |
Multistate Value |
28 |
Read/write |
No |
|
|
BI-3_INPUT_MODE |
Multistate Value |
29 |
Read/write |
No |
|
|
BI-4_INPUT_MODE |
Multistate Value |
30 |
Read/write |
No |
|
|
For MINI 4I4O-H and 4I4O-H-IP only |
|||||
|
BI-1_MODE_TIME |
Analog Value |
26 |
Read/write |
No |
Time Value object for Time Relay Mode |
|
BI-2_MODE_TIME |
Analog Value |
27 |
Read/write |
No |
|
|
BI-3_MODE_TIME |
Analog Value |
28 |
Read/write |
No |
|
|
BI-4_MODE_TIME |
Analog Value |
29 |
Read/write |
No |
|
|
BI-1_BLOCK_INPUT |
Binary Value |
12 |
Read/write |
No |
Digital input blocking command |
|
BI-2_BLOCK_INPUT |
Binary Value |
13 |
Read/write |
No |
|
|
BI-3_BLOCK_INPUT |
Binary Value |
14 |
Read/write |
No |
|
|
BI-4_BLOCK_INPUT |
Binary Value |
15 |
Read/write |
No |
|
|
BI-1_COMMAND |
Binary Value |
8 |
Read/write |
No |
Digital input remote command |
|
BI-2_COMMAND |
Binary Value |
9 |
Read/write |
No |
|
|
BI-3_COMMAND |
Binary Value |
10 |
Read/write |
No |
|
|
BI-4_COMMAND |
Binary Value |
11 |
Read/write |
No |
|
|
For MINI 4U4O-H and 4U4O-H-IP only |
|||||
|
BI-1_SETPOINT |
Analog Value |
30 |
Read/write |
No |
SETPOINT for heating/cooling modes Default: 0 |
|
BI-2_SETPOINT |
Analog Value |
31 |
Read/write |
No |
|
|
BI-3_SETPOINT |
Analog Value |
32 |
Read/write |
No |
|
|
BI-4_SETPOINT |
Analog Value |
33 |
Read/write |
No |
|
|
BI-1_DIFFERENTIAL |
Analog Value |
34 |
Read/write |
No |
DIFFERENTIAL for heating/cooling modes Default: 0 |
|
BI-2_ DIFFERENTIAL |
Analog Value |
35 |
Read/write |
No |
|
|
BI-3_ DIFFERENTIAL |
Analog Value |
36 |
Read/write |
No |
|
|
BI-4_ DIFFERENTIAL |
Analog Value |
37 |
Read/write |
No |
|