Switches 5 and 6: CV Temperature Source
The default application can work with 4 different CV temperature sources. The CV temperature source is selected by the S3 CFG DIP switches number 5 and 6. The configuration table is presented below.
No. | Name | On | Off | Default | |
---|---|---|---|---|---|
5 | Temperature control value source | 5-off | 6-off | Room panel (iSMA-B-LP, Touch Point) | Room panel |
5-off | 6-on | Room sensor, SI3 | |||
6 | 5-on | 6-off | Air return temperature, SI1 | ||
5-on | 6-on | Network temperature |
Source description:
- room panel: the temperature is sourced from the iSMA-B-LP/Touch Point room panel connected to the FCU controller by RJ12 socket;
- room sensor: the temperature is sourced from the sensor connected to the S3 special input;
- air return temperature: the temperature is sourced from the sensor connected to the S1 special input–for more information about the Air Return Temp, please see section Return Temperature Sensor Control;
- network temperature: the temperature is sourced from the network variable; this source is dedicated for the slave device in the master-slave working mode.