Skip to main content
Skip table of contents

Technical Specification

Power Supply

DC

20-34 V

AC

24 V ± 20%

Power consumption

0.5 W at 24 V DC, 0.75 VA at 24 V AC - up too 1 W peaks in max. configuration

Built-in Sensors

Temperature sensor

10k NTC type, range: 0-50˚C, accuracy: ± 0.5˚C, resolution: ± 0.1˚C

Humidity sensor

(applies to versions with humidity sensor)

Range: 0-100% RH, accuracy: ± 2% RH in range 10-90% RH, resolution: ± 0.1% RH

CO2 sensor

(applies to versions with CO2 sensor)

Range: 400-4000 ppm, accuracy: ± 30 ppm

COM1

RS485 interface

Up to 128 devices

Half-duplex

Communication protocols

Modbus RTU/ASCII, BACnet MS/TP

Ports

2 RJ45, screw connector

Baud rate

2400-115200

Front Panel

Surface

White/black glass

Display (applies to version with display)

TFT 0.96"

Backlight (does not apply to the Touch Point Network Sensor series)

3 intensity modes

Buttons (does not apply to the Touch Point Network Sensor series)

5 (Touch Point series) / 3 (Touch Point VAV series)

LED (does not apply to the Touch Point Network Sensor series)

3 blue and 3 red for temperature

3 white for fan (only the Touch Point series)

1 white for occupancy

LED (all series)

1 configurable RGB

Ingress Protection

IP rating

IP20 for indoor installation

Temperature

Operating

From 0°C to +40°C

Storage

From -40°C to +70°C

Humidity

Relative

From 5% to 95% RH (without condensation)

Screw Connector

Type

Removable screw terminals

Maximum cable size

1.5 mm2 (24…16 AWG)

Housing

Material

Plastic, self-extinguishing ABS

Mounting

Standard 60 mm wall back box

Dimensions

Metric

86.00x86.00x14.50 mm

Inches

3.39x3.39x0.57 in