Technical Specification
Power Supply | DC | 20-34 V |
---|---|---|
AC | 24 V ± 20% | |
Power consumption | 0.5 W at 24 V DC, 0.75 VA at 24 V AC - up too 1 W peaks in max. configuration | |
Built-in Sensors | Temperature sensor | 10k NTC type, range: 0-50˚C, accuracy: ± 0.5˚C, resolution: ± 0.1˚C |
Humidity sensor (applies to versions with humidity sensor) | Range: 0-100% RH, accuracy: ± 2% RH in range 10-90% RH, resolution: ± 0.1% RH | |
CO2 sensor (applies to versions with CO2 sensor) | Range: 400-4000 ppm, accuracy: ± 30 ppm | |
COM1 | RS485 interface | Up to 128 devices |
Half-duplex | ||
Communication protocols | Modbus RTU/ASCII, BACnet MS/TP | |
Ports | 2 RJ45, screw connector | |
Baud rate | 2400-115200 | |
Front Panel | Surface | White/black glass |
Display (applies to version with display) | TFT 0.96" | |
Backlight | 3 intensity modes | |
Buttons | 5 (Touch Point series) / 3 (Touch Point VAV series) | |
LED | 3 blue and 3 red for temperature | |
3 white for fan (only the Touch Point series) | ||
1 white for occupancy | ||
1 configurable RGB | ||
Ingress Protection | IP rating | IP20 for indoor installation |
Temperature | Operating | From 0°C to +40°C |
Storage | From -40°C to +70°C | |
Humidity | Relative | From 5% to 95% RH (without condensation) |
Screw Connector | Type | Removable screw terminals |
Maximum cable size | 1.5 mm2 (24…16 AWG) | |
Housing | Material | Plastic, self-extinguishing ABS |
Mounting | Standard 60 mm wall back box | |
Dimensions | Metric | 86.00x86.00x14.50 mm |
Inches | 3.39x3.39x0.57 in |