Skip to main content
Skip table of contents

Emergency Mode

The system and application(s) of the nano EDGE ENGINE controllers are stored on an SD card. If the SD card is not detected in the device or the device detects frequent reboots (at least 5 times in 6 minutes), which prevent correct operation, the device enters an emergency mode.

What Causes the Emergency Mode?
  • No SD card is detected in the device.

  • The diagnostic process reveals error in I/Os.

  • Storage limit is exceeded.

  • Required files are missing during a start-up of the device.

  • Libraries or files are corrupted.

Operation in Emergency Mode

Upon connecting to the device in the emergency mode, the following notice pops up:

74 Emergency mode.png

Emergency mode notice

In the emergency mode, the device operation is limited:

  • libraries are not loaded;

  • the SD card configuration is not loaded;

  • only the System container with limited options (only Logs and Platform components) is displayed in the tree;

60a Emergency mode.png

Device tree in the emergency mode

  • the ALM LED is lit continuously;

  • the iFnet runs with an IP/port taken from a flash storage;

Note: The flash storage must be synchronized to configuration slots when available.

  • no authorization or credentials are taken from the flash storage (like IP/port).

60 Emergency mode.png

Start screen for a connected device in emergency mode

Possible Actions

When the device enters the emergency mode, take one of a few possible actions:

  1. read logs from the SD card if available;

  2. reboot;

  3. restore to defaults (using the Restore in the System context menu): remove files from the SD card (if available and formatted) excluding only files with IP, port, and credentials (libraries must be also removed);

63 Restore to defaults.png

RestoreToDefaults action

  1. restore to factory defaults (restoring with S1 6th DIP switch): format the SD card (if available), restore default credentials, IP, mask, gateway, iFnet port.

Warning - Factory Default Deletes Application

The process of bringing back factory default settings erases the application from the controller. In such a case, it is required to restore the application from the available backup.

For detailed information on how to restore the backup, please see: Default Communication Settings and Credentials.

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.