In its out-of-the-box state, as well as after restoring the default values, the device has the following default register values:Register NameDefault ValueCOUNTER 1-120COUNTER 12-24 (24I and 24I-IP)0USER BAUD RATE7680 (76800 bps)STOP BITS1DATA BITS8PARITY BITS0RESPONSE DELAY0WATCHDOG TIME0 (disabled)DEFAULT STATE OF DIGITAL OUTPUTS (1-12)0DEFAULT STATE OF THE ANALOG OUTPUTS (DIGITAL 1-6)0DEFAULT STATE OF THE ANALOG OUTPUTS (1-6)0UNIVERSAL INPUT CONFIGURATION (1-8)3 (10K3A1 NTC (°C))INPUT FILTER TIME CONSTANT (1-8)2UNIVERSAL INPUT RESOLUTION (1-8)1 (12-bit)ANALOG OUTPUT CONFIGURATION (1-6)1 (voltage)Only for IP ModulesUSERNAMEadminPASSWORD1000IP ADDRESS192.168.1.123MASK255.255.255.0GATEWAY192.168.1.1DHCPDisabledHTTP PORT80MODBUS TCP PORT502MODBUS TCP TIMEOUT60 sRS485 TIMEOUT500 msRS485 BIASING RESISTORS (MINI only)DISABLEDSEND MODBUS ERRORSENABLEDDefault values
Restoring Default Settings
To restore the default configuration of all registers, follow the steps below:
-
turn off the power supply;
-
set section 6 of the S3 switch to on;
-
turn on the power supply, the power LED will start blinking;
-
switch section 6 of the S3 switch to off to restore the default settings. To cancel the reset, turn off the power, and switch section 6 of the S3 switch to the off position.