Technical Specification

Power supply

DC

24 V DC ± 20%, max. 24.8 W

AC

24 V AC ± 20%, max. 44 VA

Vout (COM1)

Voltage

Max. 40 V DC - depending on the input supply voltage

23 V DC for 24 V DC input supply voltage

33 V DC for 24 V AC input supply voltage

Max. load

Max. 5 W

Voltage output

Voltage

Same as connected power supply

Max. load

10 W

Universal inputs






Number of inputs

8

Voltage input

Voltage measurement: 0-10 V DC

Input impedance: 100 kΩ

Measurement accuracy: ±0.1%

Measurement resolution: 3 mV at 12-bit and 1 mV at 16-bit

Current input

Current measurement: 0-20 mA

Required external resistor: 200 Ω

Measurement accuracy: ±1.1%

Measurement resolution: 15 µA at 12-bit and 5 µA at 16-bit

Digital input

Output current ~1 mA

Resistance input

Measurement of resistance: 0-1000 kΩ

Measurement resolution for 20 kΩ load: 20 Ω at 12-bit and 1 Ω at 16-bit

Measurement resolution for PT1000 and NI1000: 0.1 Ω at 16-bit

Resistance measurement method: voltage divider

Temperature input

Measurement with attached RTDs (resistance temperature detectors)

Accuracy: ±0.1˚C

The PT1000 and NI1000 sensors use 16-bit resolution

Measurement resolution

12-bit (default), 16-bit

Processing time

10 ms/channel at 12-bit

140 ms/channel at 16-bit

Digital inputs

Number of inputs

4

Type

Dry contact or fast pulse counter (saved on SD card)

Max. input frequency

100 Hz

Analog outputs



Number of outputs

6

Voltage range

0-10 V DC

Max. load current

20 mA

Resolution

12-bit

Accuracy

±0.5%

PWM

0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

Digital Outputs

Number of outputs

2

Resistive load (AC1)

3 A at 230 V AC, 3 A at 30 V DC

Inductive load (AC3)

75 VA at 230 V AC or 30 W at 30 V DC

SSR outputs

Number of outputs

4

Load

750 mA at 24 V AC/DC per output

PWM

0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz (recommended load of at least 1 mA for proper functioning of the PWM mode)

DA1

Communication protocol

DALI-2 in compliance with IEC 62386-101, IEC 62386-103

Connector

Screw connector

Power output

12 V at up to 125 mA (170 mA max. current)

Max. load

250 mA total current on the bus

COM1

RS485 communication

Up to 128 devices

Communication protocol

BACnet MS/TP, Modbus RTU

Connectors

Smart Plug (RJ45), screw connector

Baud rate

2400-115200

ETH1

Switches

2 ports, fail-safe protected

Communication protocol

BACnet IP, Modbus TCP/IP

Baud rate

10/100 Mb/s

USB1

Type

USB-C

Power supply

5 V

Ingress protection

IP rating

IP 20 for indoor installation

Temperature

Storage

-40°C to +85°C (-40°F to +185°F)

Operating

0°C to +50°C (32°F to 122°F)

Humidity

Relative

5 to 95% RH (without condensation)

Connector cables

DALI, RS485, and IOs

Separable max. 2.5 mm2 (18 – 12 AWG)

RS485

RJ45

Ethernet

RJ45

Min. cable category

UTP 5E

Housing

Material

Plastic, self-extinguishing PC/ABS

Mounting

DIN rail mounting

DIN EN 50022

Dimensions (12M)

Width

215.50 mm/8.48 in

Length

109.40 mm/4.31 in

Height

61.70 mm/2.43 in