Power supply |
DC |
24 V DC ± 20%, max. 24.8 W |
|---|---|---|
|
AC |
24 V AC ± 20%, max. 44 VA |
|
|
Vout (COM1) |
Voltage |
Max. 40 V DC - depending on the input supply voltage 23 V DC for 24 V DC input supply voltage 33 V DC for 24 V AC input supply voltage |
|
Max. load |
Max. 5 W |
|
|
Voltage output |
Voltage |
Same as connected power supply |
|
Max. load |
10 W |
|
|
Universal inputs
|
Number of inputs |
8 |
|
Voltage input |
Voltage measurement: 0-10 V DC Input impedance: 100 kΩ Measurement accuracy: ±0.1% Measurement resolution: 3 mV at 12-bit and 1 mV at 16-bit |
|
|
Current input |
Current measurement: 0-20 mA Required external resistor: 200 Ω Measurement accuracy: ±1.1% Measurement resolution: 15 µA at 12-bit and 5 µA at 16-bit |
|
|
Digital input |
Output current ~1 mA |
|
|
Resistance input |
Measurement of resistance: 0-1000 kΩ Measurement resolution for 20 kΩ load: 20 Ω at 12-bit and 1 Ω at 16-bit Measurement resolution for PT1000 and NI1000: 0.1 Ω at 16-bit Resistance measurement method: voltage divider |
|
|
Temperature input |
Measurement with attached RTDs (resistance temperature detectors) Accuracy: ±0.1˚C The PT1000 and NI1000 sensors use 16-bit resolution |
|
|
Measurement resolution |
12-bit (default), 16-bit |
|
|
Processing time |
10 ms/channel at 12-bit 140 ms/channel at 16-bit |
|
|
Digital inputs |
Number of inputs |
4 |
|
Type |
Dry contact or fast pulse counter (saved on SD card) |
|
|
Max. input frequency |
100 Hz |
|
|
Analog outputs
|
Number of outputs |
6 |
|
Voltage range |
0-10 V DC |
|
|
Max. load current |
20 mA |
|
|
Resolution |
12-bit |
|
|
Accuracy |
±0.5% |
|
|
PWM |
0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz |
|
|
Digital Outputs |
Number of outputs |
2 |
|
Resistive load (AC1) |
3 A at 230 V AC, 3 A at 30 V DC |
|
|
Inductive load (AC3) |
75 VA at 230 V AC or 30 W at 30 V DC |
|
|
SSR outputs |
Number of outputs |
4 |
|
Load |
750 mA at 24 V AC/DC per output |
|
|
PWM |
0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz (recommended load of at least 1 mA for proper functioning of the PWM mode) |
|
|
DA1 |
Communication protocol |
DALI-2 in compliance with IEC 62386-101, IEC 62386-103 |
|
Connector |
Screw connector |
|
|
Power output |
12 V at up to 125 mA (170 mA max. current) |
|
|
Max. load |
250 mA total current on the bus |
|
|
COM1 |
RS485 communication |
Up to 128 devices |
|
Communication protocol |
BACnet MS/TP, Modbus RTU |
|
|
Connectors |
Smart Plug (RJ45), screw connector |
|
|
Baud rate |
2400-115200 |
|
|
ETH1 |
Switches |
2 ports, fail-safe protected |
|
Communication protocol |
BACnet IP, Modbus TCP/IP |
|
|
Baud rate |
10/100 Mb/s |
|
|
USB1 |
Type |
USB-C |
|
Power supply |
5 V |
|
|
Ingress protection |
IP rating |
IP 20 for indoor installation |
|
Temperature |
Storage |
-40°C to +85°C (-40°F to +185°F) |
|
Operating |
0°C to +50°C (32°F to 122°F) |
|
|
Humidity |
Relative |
5 to 95% RH (without condensation) |
|
Connector cables |
DALI, RS485, and IOs |
Separable max. 2.5 mm2 (18 – 12 AWG) |
|
RS485 |
RJ45 |
|
|
Ethernet |
RJ45 |
|
|
Min. cable category |
UTP 5E |
|
|
Housing |
Material |
Plastic, self-extinguishing PC/ABS |
|
Mounting |
DIN rail mounting |
DIN EN 50022 |
|
Dimensions (12M) |
Width |
215.50 mm/8.48 in |
|
Length |
109.40 mm/4.31 in |
|
|
Height |
61.70 mm/2.43 in |