Modbus Address |
Decimal Address |
Hex Address |
Register Name |
Access |
Description |
||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
30001 |
0 |
0x00 |
VERSION AND MODULE TYPE |
Read-only |
Firmware version and module type (30001) |
||||||||||||||||||||||||||
|
30004 |
3 |
0x03 |
RS485 COUNTER OF RECEIVED FRAMES (32 bits) |
Read-only |
Counter of received messages (30004) Default state is 0 Reset at the unit start and change of transmission parameters |
||||||||||||||||||||||||||
|
30006 |
5 |
0x05 |
RS485 COUNTER OF FRAMES WITH ERROR (32 bits) |
Read-only |
Counter of error messages (30006) Default state is 0 Reset at the unit start and change of transmission parameters. |
||||||||||||||||||||||||||
|
30008 |
7 |
0x07 |
RS485 COUNTER OF SENT FRAMES
|
Read-only |
Counter of sent messages (30008) Default state is 0 Reset at the unit start and change of transmission parameters. |
||||||||||||||||||||||||||
|
30017 |
15 |
0x0F |
STATUS OF SPECIAL INPUTS WORKING AS DIGITAL INPUT |
Read-only |
Status of special inputs working as digital inputs are represented by bits 0 and 1 in register (30017) |
||||||||||||||||||||||||||
|
40001 |
0 |
0x00 |
VERSION AND MODULE TYPE PLUS ENABLE OF ACTIONS |
Read&Write |
Firmware version and module type plus enable of actions
|
||||||||||||||||||||||||||
|
40018 |
17 |
0x11 |
STATE OF DIGITAL OUTPUTS |
Read&Write |
State of digital outputs (40018) |
||||||||||||||||||||||||||
|
40020 |
19 |
0x12 |
SPECIAL INPUTS COMMAND REGISTER |
Read&Write |
Special inputs command register (40020) |
||||||||||||||||||||||||||
|
40021 |
20 |
0x14 |
SPECIAL INPUTS BLOCKING |
Read&Write |
Special inputs blocking (40021) By default set to 0 |
||||||||||||||||||||||||||
|
40022 |
21 |
0x15 |
COUNTER RESET |
Read&Write |
Resetting counters value (40022) Set bit in register to reset corresponding counter |
||||||||||||||||||||||||||
|
40023 |
22 |
0x16 |
COUNTER 1 LSB |
Read&Write Memory |
32-bit counters for each special input counting pulses. |
||||||||||||||||||||||||||
|
40024 |
23 |
0x17 |
COUNTER 1 MSB |
|
|
||||||||||||||||||||||||||
|
40025 |
24 |
0x18 |
COUNTER 2 LSB |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40026 |
25 |
0x19 |
COUNTER 2 MSB |
|
|
||||||||||||||||||||||||||
|
30071 |
70 |
0x46 |
SPECIAL INPUT 1 VOLTAGE |
Read-only |
Special input measure voltage 1-2 (30071, 30073) and Special Input measure temperature 1-2 (30072, 30074) Voltage measurement value is expressed in mV. For current measurements, the formula for the current: where: U – register value, 500 – value of attached resistance Temperature is expressed in Celsius degrees * 10 For a result, divide the registry value by 10: Selection of the type sensor is done using registers from 40151 to 40152 for each input separately |
||||||||||||||||||||||||||
|
30072 |
71 |
0x47 |
SPECIAL INPUT 1 TEMPERATURE |
Read-only |
|
||||||||||||||||||||||||||
|
30073 |
72 |
0x48 |
SPECIAL INPUT 2 VOLTAGE |
Read-only |
|
||||||||||||||||||||||||||
|
30074 |
73 |
0x49 |
SPECIAL INPUT 2 TEMPERATURE |
Read-only |
|
||||||||||||||||||||||||||
|
30087 |
86 |
0x56 |
SPECIAL INPUT 1 VOLTAGE |
Read-only |
|
||||||||||||||||||||||||||
|
30088 |
87 |
0x57 |
SPECIAL INPUT 2 VOLTAGE |
Read-only |
|
||||||||||||||||||||||||||
|
30095 |
94 |
0x5E |
SPECIAL INPUT TEMPERATURE 1 |
Read-only |
|
||||||||||||||||||||||||||
|
30096 |
95 |
0x5F |
SPECIAL INPUT TEMPERATURE 2 |
Read-only |
|
||||||||||||||||||||||||||
|
30103 |
102 |
0x66 |
RESISTIVE INPUT 1 LSB |
Read-only |
Special input resistance measurement 1-2 (30103-30104, 30105-30106) Resistance measurement result is expressed in Ω. |
||||||||||||||||||||||||||
|
30104 |
103 |
0x67 |
RESISTIVE INPUT 1 MSB |
Read-only |
|
||||||||||||||||||||||||||
|
30105 |
104 |
0x68 |
RESISTIVE INPUT 2 LSB |
Read-only |
|
||||||||||||||||||||||||||
|
30106 |
105 |
0x69 |
RESISTIVE INPUT 2 MSB |
Read-only |
|
||||||||||||||||||||||||||
|
40134 |
133 |
0x85 |
MODBUS PROTOCOL TYPE |
Read&Write Memory |
RS485 Modbus protocol type 0 - RTU, 1 - ASCII |
||||||||||||||||||||||||||
|
40136 |
135 |
0x87 |
RS485 BAUD RATE |
Read&Write Memory |
RS485 baud rate (40136) |
||||||||||||||||||||||||||
|
40137 |
136 |
0x88 |
RS485 STOP BITS |
Read&Write Memory |
Stop bits (40137) Supported values are 1 and 2 The default value is 1 |
||||||||||||||||||||||||||
|
40138 |
137 |
0x89 |
RS485 DATA BITS |
Read&Write Memory |
Data bits (40138) Supported values are 7 and 8 The default value is 7 |
||||||||||||||||||||||||||
|
40139 |
138 |
0x8A |
RS485 PARITY BIT |
Read&Write Memory |
The default value is 0 (no parity) Allowed values:
|
||||||||||||||||||||||||||
|
40140 |
139 |
0x8B |
RESPONSE DELAY |
Read&Write Memory |
Response delay time (40140) Delay in ms before sending response The default value is 0 |
||||||||||||||||||||||||||
|
40141 |
140 |
0x8C |
WATCHDOG TIME |
Read&Write Memory |
Watchdog time (40141) Time in seconds before watchdog reset in case of no transmission Setting value of 0 disables the watchdog The default value is 15 s |
||||||||||||||||||||||||||
|
40143 |
142 |
0x8E |
DEFAULT STATE OF DIGITAL OUTPUTS |
Read&Write Memory |
Default state of digital outputs (40143) State of digital outputs assigned at the start of the module and watchdog reset The default value is 0 |
||||||||||||||||||||||||||
|
40151 |
150 |
0x96 |
SPECIAL INPUT 1 CONFIGURATION |
Read&Write Memory |
Configuration of special input and type of temperature sensor The default value is 1
|
||||||||||||||||||||||||||
|
40152 |
151 |
0x97 |
SPECIAL INPUT 2 CONFIGURATION |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40159 |
158 |
0x9E |
FILTER TIME CONSTANT OF THE SPECIAL INPUT 1 |
Read&Write Memory |
Filter time of the special input 1-2 (40159-40160) Filter time constant, expressed in seconds in the range from 0 to 60 seconds The default value is 2 s, setting to 0 s disables the filter |
||||||||||||||||||||||||||
|
40160 |
159 |
0x9F |
FILTER TIME CONSTANT OF THE SPECIAL INPUT 2 |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40176 |
175 |
0xAF |
SPECIAL INPUT 1 CONFIGURATIO MODE |
Read&Write Memory |
TIME VALUE [ms] |
||||||||||||||||||||||||||
|
40177 |
176 |
0xB0 |
SPECIAL INPUT 1 TIME VALUE |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40180 |
179 |
0xB3 |
SPECIAL INPUT 2 CONFIGURATIO MODE |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40181 |
180 |
0xB4 |
SPECIAL INPUT 2 TIME VALUE |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40242 |
241 |
0xF1 |
RADIO TX POWER |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40243 |
242 |
0xF2 |
RADIO CHANNEL |
Read&Write Memory |
Radio channel (40243) |
||||||||||||||||||||||||||
|
40244 |
243 |
0xF3 |
RADIO BAUD RATE |
Read&Write Memory |
Radio baud rate (20249) |
||||||||||||||||||||||||||
|
40249 |
248 |
0xF8 |
RADIO AESKEY D1-D0 |
Read&Write Memory |
Radio transmission 128 bit encryption key (40249-40256) Default values: 1111 2222 3333 4444 5555 6666 7777 8888 |
||||||||||||||||||||||||||
|
40250 |
249 |
0xF9 |
RADIO AESKEY D3-D2 |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40251 |
250 |
0xFA |
RADIO AESKEY D5-D4 |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40252 |
251 |
0xFB |
RADIO AESKEY D7-D6 |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40253 |
252 |
0xFC |
RADIO AESKEY D9-D8 |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40254 |
253 |
0xFD |
RADIO AESKEY D11-D10 |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40255 |
254 |
0xFE |
RADIO AESKEY D13-D12 |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40256 |
255 |
0xFF |
RADIO AESKEY D15-D14 |
Read&Write Memory |
|
||||||||||||||||||||||||||
|
40257 |
256 |
0x0100 |
RADIO COUNTER OF RECEIVED FRAMES (32 – bits) |
Read&Write Memory |
Counter of received messages (30004) Default state is 0 Reset at the unit start and change of transmission parameters |
||||||||||||||||||||||||||
|
40259 |
258 |
0x0102 |
RADIO COUNTER OF ERROT FRAMES (32 – bits) |
Read&Write Memory |
Counter of error messages (30006) Default state is 0 Reset at the unit start and change of transmission parameters |
||||||||||||||||||||||||||
|
40261 |
260 |
0x0104 |
RADIO COUNTER OF TRANSMITTED FRAMES (32 – bits) |
Read&Write Memory |
Counter of sent messages (30008) Default state is 0 Reset at the unit start and change of transmission parameters |
||||||||||||||||||||||||||
|
40263 - 40390 |
262 - 389 |
0x0106 – 0x0185 |
WIRELESS DEVICE STATUS 1 ÷ 128 |
Read-only |
Bit 7: 0 - Int8 RX POWER [dBm] Bit 8: 0 - Down; 1 - Ok |
List of Modbus registers