RAC18-IP Panel Connection and Configuration

The RAC18-IP controller works with three types of dedicated panels:

  • Touch Point panel;

  • LP panel with LCD display;

  • SP panel without display, fully passive;

  • FP panel.

The default application allows the user to select, which temperature sensor source is chosen to control algorithm.

The sensor is selected by the S3 DIP switches number 5 and 6.

No.

Name

Switches Configuration

Function

5

CV temperature source

5-Off

6-Off

LCD panel

5-Off

6-On

Room sensor SI3

6

5-On

6-Off

Air return temp SI1

5-On

6-On

Slave